Conventional 

2, 4 and 6 zone Fire 

Alarm

 Panels

921163600_09_022

GENERAL

The family of fire detection panels consist of 

3

 types (

2, 

4 and 6 zone) with identical operation and indications. The panels have 

2 independent siren outputs, Alarm, Fault Relay and a programmable AUX relay. The required batteries for the panels are two 
A-9

20

 (12V/

2.6

Ah). All functions and indications are according to European Norms EN 54-2 and EN 54-4.

Top cover 
retaining screws

Control Keyboard and 
indication leds

Mounting holes

Battery compartment 
two Α-920

 MODE selection 
    microswitch

Relay  

outputs 

connection  terminals

Zone connection terminal

General output connection 

(Sirens,24V)

Mains voltage connection 
terminal block (220-240V AC)

Figure 1. 

Schematic diagram of the panel

                

Mounting hole

Extra earth 
terminals

Page 1 from 10

Thank you for your trust in our products  

Olympia Electronics -  European manufacturer

Summary of Contents for BS-1632

Page 1: ...12V 2 6Ah All functions and indications are according to European Norms EN 54 2 and EN 54 4 Top cover retaining screws Control Keyboard and indication leds Mounting holes Battery compartment two 920 M...

Page 2: ...respond to the siren outputs If a siren out has a short circuit or open circuit then the corresponding LED will blink If a siren is disabled the corresponding LED will light The next group of indicato...

Page 3: ...iren 1 and Siren2 LED lights for the siren 2 Using the keys 1 and 2 we can enable or disable the respective sirens The disabled sirens have a LED lighted The panel exits this mode if no key is pressed...

Page 4: ...nd corresponding functions 921163600_09_022 Fault zone 1 Alarm zone 2 Alarm zone 1 Without Delay 30 second Delay 60 second Delay 90 Second Delay LED ON LED OFF LED OFF LED OFF LED OFF LED OFF LED ON L...

Page 5: ...res with a cross section cable of 1 5mm Page 5 from 10 Figure 2 Connecting 4 detector bases to zone 1 Each base can accept BS 655 BS 660 or BS 657 detectors A remote indication LED BS 572 is connected...

Page 6: ...larm condition ATTENTION The relays are rated at 30VDC and 5A maximum No 230VAC signals can be connected to these relays Siren Sounder Connections Each panel offers 2 independent circuits for connecti...

Page 7: ...sed is 2 5mm Connecting the mains power supply 220 240V AC The panel has holes on the back side for all the wiring to pass through You can connect cables with max conductor diametre of 2 5mm to the pa...

Page 8: ...r is deactivated and the LED is turned off When a siren output has an open circuit then the internal buzzer is activated and the corresponding fault LED lights If the problem is corrected then the buz...

Page 9: ...rrents outside limits be connected All relays output must be protected with a fuse of the same rating Outputs Relays 325 x 240 x 85 mm 54 2 54 4 2 years Dimensions Weight Produced in accordance to Gua...

Page 10: ...erini P C 60300 P O Box 06 Eginio Pierias Greece www olympia electronics gr info olympia electronics gr CONVENTIONAL 6 ZONE FIRE ALARM PANEL INSTALL IN ACCORDANCE WITH PRODUCT MANUAL 921163600_08_021...

Reviews: