background image

Sequence Of Operation

1. 

Room temperature drops causing the room thermostat to call 
for fi rst stage heat by connecting “W1” to “R”. Th

  e control veri-

fi es the limit switch is closed and both low and high pressure 
switches are open. Th

  e control energizes the induced draft  mo-

tor on high speed and waits for the low pressure switch to close. 
Th

  e inducer remains on high speed and begins a 15 second pre-

purge period. Th

  e high pressure switch is ignored. If the low 

pressure switch does not close within 60 seconds, the control 
will fl ash “2” on the red Status LED, and de-energize the 
inducer for 60 minutes.

2. 

When the 15 second pre-purge time has elapsed, the control en-
ergizes the HSI output for a 5 second warm-up period (10 sec-
onds on retries). Th

  e control energizes the low main gas valve. 

4 seconds aft er the gas is energized, the control de-energizes the 
HSI output and leaves the gas energized another 1 second for 
fl ame proving. If fl ame is present at the end of trial for ignition 
time, the control leaves the gas valve energized, inducer on high 
speed, and begins heat blower on delay. Th

  e control always 

ignites on high inducer/low gas and ignores second stage call 
for heat until low heat is established for 
15 seconds.

3. 

Blower on delay time begins when the gas valve is energized. 
Th

  e control provides the ECM (Electronically Commutated 

Motor) low heat speed signal when fl ame is proven, and starts 
a 30 second soft  start (slowly ramp up) blower delay before full 
capacity blower level.

4. 

When there is a demand for 2nd stage heat from thermostat W2 
or automatic staging, the control changes the inducer from low 
to high speed. When high pressure switch closes, the control 
changes indoor blower speed from Low heat to High heat and 
energizes high gas output. If the High pressure switch is open 
the Green LED will fl ash. If the High pressure switch is closed 
the Green LED will be on. High gas valve drops out while High 
pressure switch is open because it is directly in series with the 
High pressure switch.

5. 

When the thermostat W2 call ends and W1 remains (two stage 
thermostat), the control de-energizes the high gas output and 
immediately changes inducer speed from high to low. With the 
thermostat heating contacts open (single stage thermostat), the 
fl ames extinguish immediately and the inducer blower stops 
aft er a 5 second post purge time.

6. 

Blower off  delay is handled by the ECM 
(Electronically Commutated Motor). Th

  e control de-energizes 

the ECM heat signal when the gas valve de-energizes, and starts 
a programmed soft  stop (slowly ramp down) delay period.

In The Event Of Flame Failure:

If fl ame is lost, the control de-energizes the gas valve within 2 sec-
onds, switches the induced draft  motor to high speed (if not already 
on high), and begins timing the inter-purge delay. Th

  e indoor blower 

motor will be energized and/or remain energized on heat speed for 
the programmed delay off  time. When the inter-purge delay is over, 
the control will re-cycle up to 5 fl ame losses (4 re-cycles) within a 
single call for heat before going into lockout. Th e control fl ashes “8” 
on the red LED if lockout is due to too many fl ame losses.

Checking Furnace Input

Th

  e natural gas supply pressure should be a maximum of 7” w.c. and 

minimum of 5” w.c. Th

  e burner manifold pressure is factory set to 

3.5” w.c. High Fire, 1.5” w.c. Low Fire. Th

  e input rating of the fur-

nace is based on 1000 BTU/cu. ft . gas with a specifi c gravity of 0.6.

Since heating values for the gas vary geographically, the actual fur-
nace input and output will vary accordingly. For example, natural gas 
with a 1000 BTU/cu. ft . heating value will reduce the input to 93% 
of the rated input. Natural gas with a 1100 BTU/cu. ft . heating value 
will increase the input to approximately 103% of the rated input. Th is 
is not usually a problem; however, adjustments to compensate for 
this can be made by minor adjustments to the burner manifold pres-
sure or by changing the burner orifi ce size.

Any adjustments to the burner manifold pressure should be carried 
out with the use of a manometer or calibrated magnehelic gauge. Do 
not adjust the gas valve pressure regulator more than ±0.3” w.c.

NOTICE

IMPORTANT: Never adjust the input of the furnace to 
exceed the input shown on the rating plate.

which should be followed to ensure proper installation and 
operation.

In the previous example where the heating value of the gas is 1100 
BTU/cu. ft ., the burner manifold pressure can be reduced 3% to 3.4” 
w.c., which is within the ±0.3” w.c. specifi cation to bring the input 
into compliance. Refer also to “Setting the Gas Manifold Pressure” 
and “High Altitude in the Gas Supply & Piping” section of this man-
ual. Contact the fuel supplier for specifi c gas heating content values.

Input =

Heating Value of Gas x 3600

Time in Sec. for 1 cu. ft.

where:

• 

input is expressed in BTU/Hr

• 

heating value of the gas is expressed in BTU/ft

3

•  and time is the number of seconds required for 

the test dial to indicate 1 cubic foot.

If using a gas meter with SI (metric) units:

• 

1 cubic foot = 0.0283 cubic meters

• 

1 cubic meter = 35.315 cubic feet

• 

0.01 cubic meter = 0.3531 cubic feet

• 

0.5 cubic meter = 1.766 cubic feet

22 - STARTUP PROCEDURES

43

Summary of Contents for G95V 100

Page 1: ...ertified Company G95V NATURAL AND PROPANE GAS TWO STAGE HIGH EFFICIENCY CONDENSING WARM AIR FURNACE INSTALLATION OPERATION MAINTENANCE MANUAL Manufactured by ECR International Inc 2201 Dwyer Avenue Ut...

Page 2: ...Using Indoor Combustion Air 15 11 Determining Combustion Air 15 12 Venting Guidelines 18 13 Terminations 22 14 Vent Clearances 26 15 Vent And Draining Options Up ow 29 16 Condensate Drains 33 17 Gas...

Page 3: ...mercial heating applications from 60 000 to 120 000 BTU Hr The 95 efficient furnace series is CSA design certified as a Category IV indirect or direct vent central forced air furnace When installed as...

Page 4: ...line or other flammable vapors and liquids or other combustible materials in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any...

Page 5: ...INS FOIL COVERED FIBER GLASS INSULATION Inhalation of fiberglass particles is associated with respiratory disease including cancer WARNING Natural gas and propane are normally odorized by the fuel sup...

Page 6: ...IBLES Figure 1 Furnace Dimensions D FRONT SIDE S B A C C C FILTER VENT D AIRFLOW Table 2 FURNACE CLEARANCE TO COMBUSTIBLES SIDE Distance A 1 or Non Combustible Floor B 0 Service Clearance 24 or more C...

Page 7: ...ctly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size GAS VENT DIRE...

Page 8: ...Draft Blower 1 4 Two Stage Gas Valve 1 14 Pressure Switch Assembly 1 5 Air High Temperature Limit 1 15 Front Manifold Cover Pressure Tap 2 6 Vent and Drain Assembly 1 16 PFC Choke Coil 1 7 Drain for...

Page 9: ...als of the Heating Refrigeration and Air Conditioning Institute of Canada HRAI or by any other method which is suitable for local condi tions provided the results obtained are in substantial agreement...

Page 10: ...alled in the horizontal position the furnace may be supported from the bottom or suspended Figure 3 I If the furnace is to be installed in a commercial repair ga rage the burners and ignition source m...

Page 11: ...n and threaded rod Secure the furnace with 2 minimum slot ted angle or equivalent as shown in Figure 4 The furnace must be supported in such a way as to not allow twisting or sagging of the cabinet Po...

Page 12: ...e the furnace to cycle on the high temperature limit and may damage the heat exchanger Excessive airflow may result in an excessively noisy duct system and may result in undesirable consequences such...

Page 13: ...d the base Models capable of 5 tons of airflow for air conditioning must have dual return air inlets for optimal airflow and air filtration If not specifically stated by the filter manufacturer for ef...

Page 14: ...Natural Gas or Propane Installation Code In the United States refer to the latest ANSI Z223 1 National Fuel Gas Code NEPA 54 or AGA GAMA Venting Tables for Category I furnaces The furnace products of...

Page 15: ...on the criteria used when calculating the air supply for a confined space Exposure to the following substances in the combustion air supply but not limited to the following will also require OUTDOOR...

Page 16: ...wn negative pressure could be a problem if natural infiltration from the outdoors does not match the rate at which air is exhausted Figure 5 Combustion Dilution Air From Heated Inside Sources Case 2 C...

Page 17: ...ut which requires a pair of 8 round pipes to obtain sufficient combustion and ventilation air the duct could be an equiv alent rectangular duct 8 x 7 for example Based on 50 free area for the inlet gr...

Page 18: ...ufac turer s instructions DO NOT COMMON VENT WITH ANY OTHER APPLI ANCE If venting vertically do not vent up a chimney serving another appliance or install in a chase with a metal or high temperature p...

Page 19: ...uld have a 1 or 2 snorkel intake fitting Figure 9 6 Include the 2 vestibule elbows when calculating total vent length for all models 2 75 70 65 60 55 50 45 3 100 95 90 85 80 75 70 80 2 50 45 40 35 30...

Page 20: ...on may be located at the end of a patio deck Piping running beneath the deck must be suitably insulated and suspended in a manner to prevent condensate from collecting and freezing Do not locate the t...

Page 21: ...ustion air is greatly reduced The direct vent configuration is unaffected by any other ap pliances exhaust fans or other devices that tend to create negative pressure conditions while operating No ven...

Page 22: ...6 foot radius of the termi nation Do not terminate under a deck unless there is adequate clearance to prevent damage from the flue gases A termination may be located at the end of a patio deck Piping...

Page 23: ...urfaces that may be periodi cally exposed to flue gases are present consider treating with a sealer such as Thompson s Water Seal Additional information about seal ers may be obtained from the Thompso...

Page 24: ...ric clothes dryer except in the case where two or more of these furnaces are multi vented See Multiple Venting Refer to Figures 17A and 17B for terminal clearances FURNACE CONNECTION NOTICE IMPORTANT...

Page 25: ...t tool will punch too deep and open holes Use caulking on the inside of the cabinet to seal any holes Insure that the combustion door gasket is in good condition NOTICE IMPORTANT Keep pressure switch...

Page 26: ...14 VENT CLEARANCES Figure 17A 17B Direct Vent Non Direct Termination Clearances 26...

Page 27: ...upply inlet to building or the combustion air inlet to any other appliance 6 inches 15 cm for appliances 10 000 Btuh 3kW 12 inches 30 cm for appliances 10 000 Btuh 3kW and 100 000 Btuh 30 kW 36 inches...

Page 28: ...air supply inlet to building or the combustion air inlet to any other appliance 6 inches 15 cm for appliances 10 000 Btuh 3kW 12 inches 30 cm for appliances 10 000 Btuh 3kW and 100 000 Btuh 30 kW 36 i...

Page 29: ...hose clamps Tubing should slope towards drain trap with no sags Instructions for Upflow with Top Venting 1 Connect two 2 2 Street elbows in parts bag to the coupler on the exhauster Add 2 nipple for...

Page 30: ...l Left with Top Venting 1 Remove 2 5 knockout and connect 2 nipple approximately 2 5 long field supplied to the coupler on the exhauster Ensure exhauster coupler drain outlet is facing downward 15 6 R...

Page 31: ...ION HORIZONTAL RIGHT Instructions for Horizontal Right with Right Side Venting 1 Connect two 2 2 Street elbows in parts bag to the coupler on the exhauster Add 2 nipple for 120K BTU units Ensure exhau...

Page 32: ...h supplied hose clamps Tubing should slope towards drain trap with no sags Instructions for Downflow with Right Side Venting 1 Remove 2 5 knockout and connect 2 nipple approximately 7 long field suppl...

Page 33: ...nough to reach either side panel however it must be cut near the blower division panel This is to prevent kinking in the drain lines CAUTION The two inlets to the drain trap are for vent pipe and con...

Page 34: ...al route of the drain tube to create a vapor lock which will prevent condensate from draining away freely and result in erratic furnace operation A typical configuration would be to cement the side br...

Page 35: ...possible Some local codes call for the manual gas shut off valve to be located between 4 to 5 feet above floor level to prevent tampering by small children Ensure that the valve is readily acces sibl...

Page 36: ...plate to alert subsequent service technicians of the conversion LP TO NATURAL GAS Although the furnace is manufactured initially as a natural gas appliance if after an LP gas conversion it becomes nec...

Page 37: ...tural Gas regulator springs color coded silver plain from regulator sleeves 12 Insert the L P regulator springs provided in the conversion kit and color coded white into the regulator sleeves 13 Repla...

Page 38: ...alibrated U tube manometer to the outlet pressure boss Hose should overlap boss 3 8 The manometer must have a scale range of at least 0 to 15 of water column 3 Turn on the gas supply and electrical po...

Page 39: ...rmers condensate pumps and electronic air cleaners If adding ac cessory equipment to the furnace circuit ensure that the combined amperages listed on the appliance rating plates does not exceed the ra...

Page 40: ...furnace The ignition control may not sense flame if L1 and L2 are reversed The ground is also essential NOTICE IMPORTANT Electrical wiring and components must be protected from moisture including wat...

Page 41: ...arby lamps or appliances exposure to sunlight heat from inside wall stacks etc Thermostat Heat Anticipator Setting 0 1 AMP Honeywell The low voltage terminals are located in the control box mounted to...

Page 42: ...point above room temperature to light the furnace 7 After the burners are lit set the room thermostat to the desired temperature To Shut Down The Furnace 1 Set the room thermostat to its lowest settin...

Page 43: ...nal when the gas valve de energizes and starts a programmed soft stop slowly ramp down delay period In The Event Of Flame Failure If flame is lost the control de energizes the gas valve within 2 sec o...

Page 44: ...c Input A C Tonnage ADJUST Jumper COOL Jumper CFM 60000 3 Ton NORM A 1200 B 1000 C 800 D 600 80000 3 Ton NORM A 1200 B 1000 C 800 D 600 80000 4 Ton NORM A 1600 B 1200 C 1000 D 800 100000 5 Ton NORM A...

Page 45: ...irect measurement with elec tronic or sloped manometers and velometers or by counting the number of times the amber CFM LED on the control board flashes Each flash signifies 100 CFM count the flashes...

Page 46: ...the ECM variable speed motor will slowly ramp down This feature allows for increased energy efficiency and reduced noise levels Continuous Fan Operation When the thermostat continuous fan G switch is...

Page 47: ...precipita tion to remove dust are an excellent filtration device A 16 x 25 model is an ideal fit with this furnace in the case of a side mounted return air inlet The furnace control module is supplie...

Page 48: ...ollowing HEAT EXCHANGER The heat exchanger should be inspected for corrosion The flue passages heat exchanger tubes should be free of scale or excessive corrosion The top row of heat exchanger tubing...

Page 49: ...sion can significantly increase the internal resistance of the connection A relatively small increase in resistance can result in a large decrease in flame signal DRAINAGE The condensate drainage syst...

Page 50: ...25 TROUBLESHOOTING FLOWCHART 50...

Page 51: ...Obstruction or restrictions in venting preventing proper air flow 3 Flashes Pressure switches closed with inducer off Pressure switches stuck closed Pressure switches mis wired or jumpered 4 Flashes...

Page 52: ...han 5 seconds 26 DIAGNOSTIC CODES FOR STATUS LED A RED LED is provided to indicate furnace operating status LED Condition Fault Condition Check 8 Flashes Lockout due to too many flame dropouts Check s...

Page 53: ...27 WIRE DIAGRAM FOR TWO STAGE FURNACE WITH ECM Figure 38 Wire Diagram For Two Stage Furnace With ECM 53...

Page 54: ...damage Clamp and gasket all vent exits to furnace panels to insure airtight seal Equivalent vent length must be less than the allowable length in Table 6 Direct and Non Direct Vent Lengths If there i...

Page 55: ...ONT MANIFOLD COVER 100 5 120 5 PLASTIC FRONT MANIFOLD COVER WITH GASKETS 11 550001660 PFC CHOKE COIL 80 4 100 5 120 5 12 550001532 DOOR SWITCH ALL MODELS 13 550001657 1HP ECM MOTOR 120 5 550001861 1HP...

Page 56: ...G95V NATURAL AND PROPANE GAS TWO STAGE HIGH EFFICIENCY CONDENSING WARM AIR FURNACE ECR International 2201 Dwyer Avenue Utica New York 13504 USA www ecrinternational com 56...

Reviews: