Oliver IGD TOCSIN 102 SERIES Operation Manual Download Page 2

Page 2 of 9

The Tocsin 102 and 103 series Pellistors are flammable gas detectors based on well proven catalytic 
principles. The units can be used either as conventional 3 wire 4-20mA transmitters or as 4 wire 
addressable modules capable of integration onto an IGD data highway. Either option allows integration with 
Tocsin 625, 700 and 920 series control panels.

Pellistors are capable of detecting all flammable gases but are usually made sensitive to the particular 
target gas during calibration. It is therefore important that detectors are correctly installed and calibrated for 
correct operation.  

Siting of the detector should also be carefully considered to take into account air flows, site geometry and 
the characteristics of the target gas. This instruction manual is intended fo ruse by competent persons who 
can either demonstrate previous experience and training with gas detection systems or have completed 
training courses at Oliver IGD Limited. Performance of the system will be a function of how well the system 
is installed and calibrated.

Oliver IGD Limited can help advise on the correct siting and calibration of gas detectors. 

Mounting And Cable Information 

145.0
126.0

128.5

COVER SECURING SCREW

M20 x 1.5

40.0

25.0

Ø7.0

EXTERNAL EARTH

MKIII FLAMMABLE 
GAS DETECTOR 

SHOWN

40.0

Ø110

128.0

OLIVER

IGD

TOCSIN 102

A N A L O G U E  O R  A D D R E S S A B L E  P E L L I S T O R  F L A M M A B L E  G A S  D E T E C T O R

ATEX CERTIFIED MODELS

LE

 

B

A

A

T

M

M

O

M

S

A

P

L

F

H

 

E

A

 

R

F

E

O

 

E

C

N

E

S

E

R

P

 

E

H

T

 

N

I

 

N

E

P

O

 

T

O

N

 

O

D

 

G

NI

N

R

A

W

Serial

Gas

Date

Model

OLIVER

IGD

xxxx

Oliver IGD Ltd  Stockport  England

Tel: +44(0) 161 483 1415

Web: internationalgasdetectors.com

JB3

II 2 D G
IECExEXV160002X
ExVeritas 16ATEX0140X
Ex tb III Db,  M20 Entries

Ex db IIC T6

The following information is provided to enable safe 
installation and operation of the Tocsin 102 Pellistor.

It is vitally important for correct and safe operation that
appropriate cable types and sizes are used and all earth
bonding points observed. It is also important to observe
all instructions for entry terminations. Failure to follow these 
instructions may result in a system which may be dangerous
or fail to operate correctly. 

Summary of Contents for TOCSIN 102 SERIES

Page 1: ...ationalgasdetectors com www internationalgasdetectors com IGD OLIVER Triton House Crosby St SK2 6TS England Oliver IGD Limited Ref T102P VERSION 6 00 TOCSIN 102 103 TOC 30 SERIES PELLISTOR OPERATION M...

Page 2: ...of how well the system is installed and calibrated Oliver IGD Limited can help advise on the correct siting and calibration of gas detectors Mounting And Cable Information 145 0 126 0 128 5 COVER SEC...

Page 3: ...glands and blanking plugs should have O Ring seals or sealing washers to maintain IP66 rating use Atex rated glands and blanking plugs Taper glands and blanking plugs should use suitable thread seala...

Page 4: ...cal applications would be boiler rooms school laboratories commercial kitchens etc Cabling should have a suitable level of protection for the area into which the detector is fitted and be of a screene...

Page 5: ...is designed to take input from a standard pellistor and give either a linear 4 20mA current source output or digital RS485 addressable output Status LED s are provided to indicate mode of operation a...

Page 6: ...rrent Note the meter will read half the head drive current Use the UP DOWN buttons to increase or decrease the set point Fault LED flashes on every button press For MK3 and MK5 IGD pellistors set to 1...

Page 7: ...h the LED flashing connect a multimeter as indicated to read the CAL mA output Use the UP DOWN buttons to increase or decrease the set point Note that 12mA mid scale or 50 LEL is indicated on the mete...

Page 8: ...ading to stabilise minimum of 60 seconds Press and hold either button until LED goes off then release LED s will then flash in turn for 5 seconds during zero The unit will then automatically return to...

Page 9: ...possible to set other address combinations by connecting the unit to an IGD configuration terminal This should only be undertaken by trained technicians and is beyond the scope of this manual OLIVER I...