background image

8

charge is used, the system shall be vented down to atmospheric pressure to enable work to take 

place.This operation is absolutely vital if brazing operations on the pipework are to take place. 

Ensure that the outlet for the vacuum pump is not close to any ignition sources and there is 

ventilation available. 

8 CHARGING PROCEDURES 

In addition to conventional charging procedures,the following requirements shall be followed. 

- Ensure  that  contamination  of  different  refrigerants  does  not  occur  when  using  charging

equipment. Hoses or lines shall be as short as possible to minimise the amount of refrigerant

contained in them.

- Cylinders shall be kept upright.

- Ensure that the refrigeration system is earthed prior to charging the system with refrigerant.

- Label the system when charging is complete (if not already).

- Extreme care shall be taken not to overfill the refrigeration system.

Prior to recharging the system it shall be pressure tested with OFN. The system shall be leak

tested on completion of charging but prior to commissioning. A follow up leak test shall be

carried out prior to leaving the site.

9 DECOMMISSIONING 

Before carrying out this procedure, it is essential that the technician is completely familiar 

with the equipment and all its detail. It is recommended good practice that all refrigerants are 

recovered safely. Prior to the task being carried out, an oil and refrigerant sample shall be taken 

in case analysis is required prior to re-use of reclaimed refrigerant. It is essential that electrical 

power is available before the task is commenced.   

a) Become familiar with the equipment and its operation.

b) Isolate system electrically.

c) Before attempting the procedure ensure that :mechanical handling equipment is available, if

required,  for  handling  refrigerant  cylinders;  all  personal  protective  equipment  is  available  and

being used correctly; the recovery process is supervised at all  times by a competent person;

recovery    equipment    and    cylinders conform to the appropriate standards.

d) Pump down refrigerant system,if possible.

e) If a vacuum is not possible, make a manifold so that refrigerant can be removed from various

parts of the system.

f) Make sure that cylinder is situated on the scales before recovery takes place.

g) Start the recovery machine and operate in accordance with manufacturer's instructions.

h) Do not overfill cylinders. (No more than 80 % volume liquid charge).

i) Do not exceed the maximum working pressure of the cylinder,even temporarily.

j) When the cylinders have been filled correctly and the process completed, make sure

that the cylinders and the equipment are removed from site promptly and all isolation

valves on the equipment are closed off.

k) Recovered refrigerant shall not be charged into another refrigeration system

unless it has been cleaned and checked.

10 LABELLING 

Equipment shall be labelled stating that it has been de-commissioned and emptied of refri- 

gerant.The label shall be dated and signed. 

Summary of Contents for COMFORT 14E

Page 1: ...INSTRUCTION FOR USE AND MAINTENANCE EN COMFORT 14 E Caution risk of fire...

Page 2: ...reness 1 2 Name of Parts 12 3 Accessories 13 4 Appearance and Function of Control Panel 14 5 Appearance and Function of Remote Control 15 6 Operation Introduction 16 7 Installation 19 8 Maintenance 22...

Page 3: ...room without continuously operating ignition sources for example open flames an operating gas appliance or an operating electric heater Do not pierce or burn Be aware the refrigerants may not contain...

Page 4: ...sued by an accredited organization that ensures competence in handling refrigerants according to a specific evaluation recognized by associations in the industry Repairs must be performed based on the...

Page 5: ...d the hazards involved Children shall not play with the appliance Cleaning and user maintenance shall not be made by children without supervision 13 This appliance is not intended for use by persons i...

Page 6: ...cification 22 Servicing shall only be performed as recommended by the equipment manufacturer Maintenance and repair requiring the assistance of other skilled personnel shall be carried out under the s...

Page 7: ...adequately sealed or intrinsically safe 1 5 Presence of fire extinguisher If any hot work is to be conducted on the refrigeration equipment or any associated parts propriate fire extinguishing equipm...

Page 8: ...f a fault exists that could compromise safety then no electrical supply shall be connected to the circuit until it is satisfactorily dealt with If the fault cannot be corrected immediately but it is n...

Page 9: ...uipment shall be set at a percentage of the LFL of the refrigerant and shall be calibrated to the refrigerant employed and the appropriate percentage of gas 25 maximum is confirmed Leak detection flui...

Page 10: ...and refrigerant sample shall be taken in case analysis is required prior to re use of reclaimed refrigerant It is essential that electrical power is available before the task is commenced a Become fa...

Page 11: ...der and the relevant Waste Transfer Note arranged Do not mix refrigerants in recovery units and especially not in cylinders If compressors or compressor oils are to be removed ensure that they have be...

Page 12: ...k is possible Discharge capacitors in a way that won t cause any spark The standard procedure to short circuit the capacitor terminals usually creates sparks Reassemble sealed enclosures accurately If...

Page 13: ...gerant circuit Purge the refrigerant circuit with nitrogen for 5 min Evacuate again Cut out the compressor and drain the oil Transportation marking and storage for units that employ flammable refriger...

Page 14: ...l not cause a leak of the refrigerant charge The maximum number of pieces of equipment permitted to be stored together will be determined by local regulations 2 Name of Parts Fig 1 1 Louver 6 Drainage...

Page 15: ...tity Exhaust hose 1 Housing adaptor 1 Window Connector 1 Remote Controller 1 Window Slider Kit 1 After unpacking please check whether the above mentioned accessories are included and check their purpo...

Page 16: ...ance and Function of Control Panel A Power on off 1 Cooling B Fan speed 2 Dehumidifying C Temperature up 3 Fan D Temperature down 4 High fan speed E Operation mode 5 Medium fan speed F Timer on off 6...

Page 17: ...rol Remote Control Notes Do not drop the remote Do not place the remote control in a location exposed to direct sunlight 1 POWER Power on off 2 TIMER Timer on off 3 MODE Operation MODE 4 TEMP Temperat...

Page 18: ...ction 1 Find a place where there is power supply nearby 2 As shown in Fig 5 and Fig 5a install the exhaust hose and adjust the window position Fig 5 Fig 5a 3 Insert the power cord into a grounded AC22...

Page 19: ...ply is AC220 240V 50Hz 6 2 Cooling operation Press the Mode button until the Cool icon appears Press the DOWN or UP button to select a desired room temperature 16 31 Press the SPEED button to select f...

Page 20: ...LEEP button again can cancel the setting 6 7 Water drainage Water Full Alarm The inner water tray in the portable air conditioner has one water level safety switches it controls the water level When w...

Page 21: ...nd stable surface Don t block the air outlet ensure clearance of 30 cm on all sides See Fig 8 Do not install in wet areas such as bathrooms laundry etc Socket wiring should be in accordance with the l...

Page 22: ...e Fig 9 Window Kit Installation The window kit can be installed in a vertical or horizontal position As shown Fig 10 and Fig 10a check the min and max size of the window before the installation 1 Inst...

Page 23: ...tray inside the portable air conditioner monitors the water level When the water level reaches capacity the water full indicator lights up When the water reservoir is full remove the rubber plug at th...

Page 24: ...gged with dust dirt the air filter should be cleaned once every two weeks Remove Filter Open the air inlet grille and take off air filter Cleaning Clean the air filter with neutral detergent in lukewa...

Page 25: ...aust air hose is not connected or blocked Connect or clean the exhaust air hose Temperature setting is too high Reset the temperature Air inlet is blocked Clean the air inlet 3 Noisy The ground is not...

Page 26: ...be of acceptable quality and the failure does not amount to a major failure If you have any queries regarding your product or its warranty please find contacts below I nostri prodotti sono forniti di...

Reviews: