CONFIGURATION OF THE THERMOSTAT
N.
Keys
Display
Range
Description
Default
“
OFF
”
5 seconds
1
CL
-4,0°C ÷+4,0°C
Temperature adjustment
0°C
2
AH
20°C ÷ 35°C
Maximum settable temperature
30°C
3
AL
5°C ÷ 18°C
Minimum settable temperature
16°C
4
bL
1 ÷ 50%
Display backlighting
(in “low consumption” mode)
20
5
rE
rE / rD
rE - In case of power failure, the thermostat
saves its status (ON or OFF) into memory.
rD - In case of power failure, at restart, the
thermostat will be set to OFF.
rE
6
PP
OO / PP
PP - Protects the valve/pump in case of
inactivity for a long period of time: every
7 days the valve switches on for 15
seconds.
OO - Function disabled
PP
enabled
7
CH
CO / CH
Mode selection:
CO - Cooling only
CH - Cooling and Heating
CH
8
RES
OFF / 2 / 10 /
100
OFF= no water temp. sensor
2: NTC - 2K
10: NTC - 10K
100: NTC - 100K
External sensor: water temp. ONLY (no air)
OFF
EN
The configuration menu allows to set the operating characteristics of the thermostat according to the system or per
-
sonal needs.
- Switch off the thermostat (
“
OFF
” is displayed).
- Keep the “Mode” key (14) pressed for approximately 5 seconds; you enter the configuration menu.
- Set the desired value with the “arrow” keys (15 and 16).
- Press the “Mode” key (14) to switch to the next parameter or the key “Fan” (13) to return to the previous one.
- Press the on/off key (12) to exit the configuration.
- To restore the factory settings, keep button “Mode” (14) pressed for approximately 5 seconds; the message “
DEF
”
appears on the display.
If no key is pressed within 30 seconds, display backlighting lowers to the value set in the field “bL” (from “0” to “50%”).
When exiting the configuration mode, the changed parameters will be saved automatically.