background image

+

-

9-30 V

Jumper required if using

a single power source.

If the Digital Input requires higher

than 4.7 V, use an external pull-up

resistor (10 K, up to 30 V max)

Open/Off > 4.7 V

Closed/On = 0 V

DI

COM

Digital Level Input

NPN

+

-

9-30 V

Jumper required if using

a single power source.

Open-drain with +5 V internal pull-up

Vout max = 4.7 V

Open/Off = 4.7 V

Closed/On = 0 V

DI

COM

Digital Level Input

Internal pull-up

NPN

Jumper required if using

a single power source.

NPN

NPN

15. Digital Level Output - Active Low

16. Digital Level Output - Active Low

10 K

External pull-up

+

+

-

-

9-30 V

COIL

VIN

COM

PLC Voltage Input

Relay

10 K

Pull-Down Resistor

(Optional)

©2020 OleumTech Corpora�on. All rights reserved. OleumTech and WIO are registered trademarks of OleumTech Corpora�on in the United States.

Specifica�ons, design, product descrip�ons, and availability subject to change without no�ce. 

Quick Start Guide

Modular Wireless I/O System 

- RM1K

80-3143-001_H

17. Digital Level Output - Active High

[email protected] 

www.prosoft-technology.com 

1.661.716.5100

Go to wio.oleumtech.com to download the full

User Guide for detailed installa�on and other

helpful informa�on. Advanced User Interface

So�ware is also available at the site for download.

4-20 mA

Analog

Input

V-
SIG-
SIG+

V+

+

-

Ext Power

18. 4-20 mA Output

14. 

NPN Output

Jumper required if using

a single power source.

Open-drain (NPN) Outputs

Inductive Load (Sink Current):

  1 Amp/30 Vdc 

Relay

+

-

+

-

9-30 V

Reviews: