P R E S E N T A T I O N   O F   D I F F E R E N T   V E R S I O N S  

The 

OLC  10,  OLC  10  TWIN

  and 

OLCT  10

 

EXPLO

  combustible  gas  detectors  are  detectors  fitted  with  catalytic 

sensors and intended for use in boiler rooms and parking lots. 
 
The 

OLCT  10

 

TOX

  gas  detectors  are  4-20mA  transmitters  equipped  with  electrochemical  sensors  and  especially 

designed to detect toxic gases in commercial and light industrial applications (parking lots, boiler room, etc). 

 

Different versions available 

 

-

 

OLC 10: combustible gas 

-

 

OLC 10 TWIN: combustible gas 

-

 

OLCT 10 EXPLO: combustible gas (transmitter version, 4-20 mA output) 

-

 

OLCT 10 TOX: toxic gas (transmitter version, 4-20 mA output) 

 
 
 

I I .  

M E C H A N I C A L  

I N S T A L L A T I O N  

O F  

D I F F E R E N T  

V E R S I O N S ,   D I M E N S I O N S   A N D   M O U N T I N G  

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
The OLC/OLCT 10 gas detectors-transmitters are mounted vertically with the cable entries positioned downwards.  
 
Drill two holes 

104 mm

 apart on the base to mount the units. 

104 mm 

www.acornfiresecurity.com

www.acornfiresecurity.com

Summary of Contents for OLC 10

Page 1: ...User Manual OLC 10 OLCT 10 Analog Gas Detector Part Number NPO10GB Revision H 0 The Fixed Gas Detection Experts www acornfiresecurity com www acornfiresecurity com...

Page 2: ...2 www acornfiresecurity com www acornfiresecurity com...

Page 3: ...USE C L A U S E S C O N C E R N I N G P R O P E R T Y Drawings plans specifications and information included in this document contain confidential information that is the property of OLDHAM None of th...

Page 4: ...4 www acornfiresecurity com www acornfiresecurity com...

Page 5: ...3 3 Periodic maintenance with an OLCT 10 transmitter comb or toxic gas 13 4 Periodic maintenance with several OLCT 10 transmitters for toxic gas 15 5 Sensor replacement 15 6 Scrapping 15 V TECHNICAL S...

Page 6: ...6 www acornfiresecurity com www acornfiresecurity com...

Page 7: ...ht industrial applications parking lots boiler room etc Different versions available OLC 10 combustible gas OLC 10 TWIN combustible gas OLCT 10 EXPLO combustible gas transmitter version 4 20 mA output...

Page 8: ...8 www acornfiresecurity com www acornfiresecurity com...

Page 9: ...fferent based upon the use of an OLC 10 or OLCT 10 Cable to be used 3 conductors 3x1 mm LiYCY type 1 2 3 1 2 3 e g CONTROLLER MX 15 Connect the 3 wires based on the corresponding numbering on the sens...

Page 10: ...onding numbering on the controller Connect the 3 wires based on the corresponding numbering on the first sensor Connect the 4 wires based on the corresponding numbering on the previous and the followi...

Page 11: ...s As a result a signal fault may not be detected In the event that 2 networks are used it is cost effective to use a single cable 2 pairs subject to compliance with wiring as follows IN 1 2 3 IN OUT C...

Page 12: ...ple channel 1 is a channel connected to two sensors for detection of CO channel 2 is a channel connected to two sensors for detection of NO detector 1 CO also acts as junction box for detector 2 NO de...

Page 13: ...sponsible for setting safety practices and policies 1 Periodic maintenance with an OLC 10 detector comb gas The maintenance position was selected on the controller in order to disable its relays see m...

Page 14: ...f you use a gas concentration lower than 100 of the scale calculate rule of three and adjust to obtain the corresponding value from 0 to 1600 mV Stop calibration gas injection remove the calibration c...

Page 15: ...ansmitter in the loop and end with the first 5 Sensor replacement Sensor has to be replaced as a result of impracticable calibration or as a preventive measure Perform a new calibration after a sensor...

Page 16: ...16 www acornfiresecurity com www acornfiresecurity com...

Page 17: ...stance 300 m in 1 5 mm with MX 15 controller 2 cable glands M16 cable diameter 4 to 8 mm Dimensions Width 118 mm Height 157 mm Depth 60 mm Material Plastic Protection IP65 Storage 6 months safe from a...

Page 18: ...300 ohms Connection 3 wire terminal block 2 wires for power supply 1 wire for signal 1 cable gland M16 cable diameter 4 to 8 mm Dimensions Width 118 mm Height 157 mm Depth 60 mm Material Plastic Prote...

Page 19: ...t wires with copy on 1 terminal with 2 wires 2 cable gland M16 cable diameter 4 to 8 mm Dimensions Width 118 mm Height 157 mm Depth 60 mm Material Plastic Protection IP65 Storage 6 months safe from ai...

Page 20: ...30 C Estimated lifetime 24 months Temperature range 10 to 60 C Humidity range 20 RH to 90 RH Pressure range 1 bar 10 Linearity deviation 0 10 ppm 0 3 ppm 10 30 ppm 5 relative Temperature drift 0 4 ppm...

Page 21: ...ut wires with copy on 1 terminal block with 2 wires 2 cable glands M16 cable diameter 4 to 8 mm Dimensions Width 118 mm Height 157 mm Depth 60 mm Material Plastic Protection IP65 Storage 6 months safe...

Page 22: ...nput wires with copy on 1 terminal block with 2 wires 2 cable glands M16 cable diameter 4 to 8 mm Dimensions Width 118 mm Height 157 mm Depth 60 mm Material Plastic Protection IP65 Storage 6 months sa...

Page 23: ...mounted type will result in measurement errors and will require a recalibration of the detector 2 Metrological specifications for OLC 10 combustible gas detector The OLC 10 combustible gas detector is...

Page 24: ...played 1 injected butane x 100 x 0 95 butane acetone coefficient 63 LEL 1 5 LEL butane Note LEL varies based on sources Those reported here are required by European standard EN 50054 The coefficients...

Page 25: ...VII DECLAR ATIONS OF CONF ORMITY www acornfiresecurity com www acornfiresecurity com...