11
– Technical Specifications
51
Chapter 11
│Technical Specifications
MX 32 Controller
Function
Function
Gas Detection Controller
Number of lines
1 or 2 as per model
Display and indicators
Display
Back-lit graphic LCD
Status indicators
- 7 LEDs for each of the 2 lines
- 1 Power On/Off visual indicator
- 1 General failure indicator
Keys
Selection
5 multifunction soft-touch keys
Alarm release
Dedicated soft-touch key
Alarms
Limits
Parameter setting by
COM 32
application
Indicators
6 status LEDs per line (high- and low-range
excess, Alarm 3, Alarm 2, Alarm 1, failure)
Internal relay
■
4 fully programmable relays (configuration
over
COM 32
)
■
1 failure relay (non configurable)
■
DPCO relays, contact rating: 5A/250Vac-
30Vdc
■
Screw terminals. Can accept 2.5 mm² (14AWG)
wire
Electrical characteristics
AC power supply
■
100 to 240Vac, 50/60 Hz
■
Maximum 24Vdc output current 1.5A with
derating (see next page)
DC power supply
■
22 to 28Vdc
■
Maximum power consumption 3.5A @ 24Vdc.
1.5A per line and rest is for controller
consumption
Summary of Contents for MX 32