Page 20
CPS
– User Manual
Inspecting the digital buses
Bicolor (red/green) LEDs located above each line start, on the motherboard, allows for inspection of
the bus links as follows
:
LED appearance
Status
Red + Green LEDs lit (LEDs
blink rapidly, almost
imperceptibly)
Orange
in appearance
Normal operation.
Red LED
question
Green LED
response
Red LED blinks once per
second (green LED is off)
Red
in appearance
Communication fault.
Missing or faulting module.
Irregular blinking
Poor communication quality
Both LEDs off.
No active modules
Mini-switches
Mini switch A
allows the CPS controller to download and
read the user program. When the switch is in the
“MEM”
position (open padlock), the user program memory is
accessible and the message
“switch open” is displayed on
screen. The CPS central controller waits to download the
program from the
COM
_CPS software. The CPS central
controller goes into
“shut-down” mode when mini switch A is
in the
“MEM” position.
When the
COM
_CPS software programming is complete,
the mini switch should be flipped back to the
“Prog” position
(closed padlock), and the central controller should be
rebooted to initialize all of the newly loaded settings.
Mini switch B
only used for the central controller
’s internal
microprocessor. It should always be in the
“Run” position.
Internal relay and buzzer
The CPS central controller is equipped with
3
internal
relays [R1, R2, R3]
and a shared
Buzzer
.
The operating settings for the relays and the buzzer can be set with the
COM
_CPS software (see
table below).
The internal buzzer is activated when a specific program-defined event occurs (fault or alarm).
All lines share relays R1, R2, and R3.
The buzzer
’s pitch will vary according to the alarm threshold. Alarms 1 and 2 have the same
frequency. Alarms 3 and 4 have a different pitch, allowing the operator to distinguish between alarm
levels.
The buzzer can be disconnected by removing the
“buzzer activation strap” (J10) located on the
motherboard next to the buzzer (cf -: Overview of the Motherboard).
Function / Component
Relay R1
Relay R2
Relay R3
Buzzer
AL 1
X
X
X
X
AL 2
X
X
X
X
AL 3
X
X
X
X
AL 4
X
X
X
X
Module error
X
X
X
System fault*
X
X
X
Out of Range and Fault
X
X
X
X
Positive security
X
X
*
: (System fault
)
alarm is triggered if there is a communication fault betweenmodules, a short-
circuit in a power supply line, or a module inversion.
X
: Function can be activated or deactivated
: Default configuration setting, cannot be changed by user.
Bus 2
Bus 4
Bus 8
Communication DEL of the bus
Bus 6
interface
USB
P r o g
M E M
A
Run
P
rg
B
Programming with
COM_CPS
Micro
programming
COM_CPS
Summary of Contents for CPS Series
Page 1: ...CPS_CPS 10 System Part Number NPCPSGB Revision J 2 The Fixed Gas Detection Experts User manual...
Page 25: ...CPS User Manual Page 25...
Page 35: ...CPS User Manual Page 35...
Page 54: ...Page 54 CPS User Manual...
Page 57: ...CPS User Manual Page 57 Chapter 8 Annexes JBUS MODBUS Protocol...
Page 58: ...Page 58 CPS User Manual...
Page 59: ...CPS User Manual Page 59...
Page 60: ...Page 60 CPS User Manual...
Page 61: ...CPS User Manual Page 61...
Page 62: ...Page 62 CPS User Manual...
Page 63: ...CPS User Manual Page 63...
Page 64: ...Page 64 CPS User Manual...
Page 65: ...CPS User Manual Page 65...
Page 66: ...Page 66 CPS User Manual...
Page 67: ...CPS User Manual Page 67...
Page 68: ...Page 68 CPS User Manual...
Page 69: ...CPS User Manual Page 69...
Page 70: ...Page 70 CPS User Manual...
Page 71: ...CPS User Manual Page 71...
Page 72: ...Page 72 CPS User Manual...
Page 73: ...CPS User Manual Page 73 Chapter 9 UE Declaration of Conformity...
Page 74: ...Page 74 CPS User Manual...
Page 75: ......