5

Connection of the Weighing System

DANGER

Electric shock hazard!
The electrical connection may only be carried out by an authorised electrician.

Disconnect the power supply from the complete heating system before working
on the pellet boiler.

5.1

Electrical connection of the weighing system

Electrical connection of FA

Cable routing, connection of the distribution box to the weighing circuit board (meas-
uring transducer), connection to the boiler controller FA and power supply.

The wires from the load cell to the distribution may not be extended!

Ensure correct polarity for the signal cables when connecting. The polarity of the
connection signal is described on the next page.

8

5 Connection of the Weighing System

Installation manual

Summary of Contents for S158 EN 2.1

Page 1: ...Installation manual Weighing System Storage Tank ENGLISH S158 EN ...

Page 2: ...n valid from Approved 02 2021 Christian Wohlinger Author ÖkoFEN Forschungs EntwicklungsgesmbH A 4133 Niederkappel Gewerbepark 1 Tel 43 0 72 86 74 50 Fax 43 0 72 86 74 50 210 E Mail oekofen pelletsheizung at www oekofen com by ÖkoFEN Forschungs und EntwicklungsgesmbH Subject to modifcations ...

Page 3: ... Function conditions 6 4 Installation of the Weighing System 7 4 1 Installation of the weighing cells 7 4 2 Installation of the dummy weighing cells 7 5 Connection of the Weighing System 8 5 1 Electrical connection of the weighing system 8 5 2 Settings in the boiler controller 12 Contents ...

Page 4: ...re reference Please pass on the documentation to the new user if you decide to part with the unit at a later date Please contact your authorised dealer if you have any questions ÖkoFEN attaches great importance to the development of new products Our R D Department repeatedlychallenges the effectiveness of tried and tested systems and works continuously on improvements In thisway we secure our tech...

Page 5: ...ng risk DANGER Danger indicates a situation that could lead to death or lifethreatening injury WARNING Warning indicates a situation that could lead life threatening or serious injury CAUTION Caution indicates a situation that could lead to injury NOTICE indicates a situation that could lead to property damage 2 Types of safety warning sign 5 Installation manual ...

Page 6: ...ce and disappears when the filling weight is above the set minimum weight 3 1 Function conditions The pellets must be stored in a FleXILO storage tank with or without vibration plate The minimum height of vthe storage increases by 10 cm when weighing cells are installed Weighing cells can be used from boiler controller FA V2 03 CMP 1 4 with the software version V2 36 and boiler controller CMP 06 w...

Page 7: ...s and dummy weighing cells after the Flexilo is fully assembled and positioned Do not attempt to fit this system to a Flexilo containing fuel In order to ensure correct weight measurement the weighing cells 1 and the dummy weigh ing cells 2 must be installed diagonally opposite one another 4 1 Installation of the weighing cells 4 2 Installation of the dummy weighing cells 4 Installation of the Wei...

Page 8: ...n of the weighing system Electrical connection of FA Cable routing connection of the distribution box to the weighing circuit board meas uring transducer connection to the boiler controller FA and power supply The wires from the load cell to the distribution may not be extended Ensure correct polarity for the signal cables when connecting The polarity of the connection signal is described on the n...

Page 9: ...ansducer connection to the boiler controller CMP 0 6 and power supply The wires from the load cell to the distribution may not be extended Ensure correct polarity for the signal cables when connecting The polarity of the connection signal is described on the next page 5 Connection of the Weighing System 9 Installation manual ...

Page 10: ...wer supply The wires from the load cell to the distribution may not be extended Ensure correct polarity for the signal cables when connecting The polarity of the connection signal is described on the next page 1 Measuring signal from the weighing cells 2x 2 Measuring signal to the Boiler con troller 1x X3 3 Power supply 1x X1 10 5 Connection of the Weighing System Installation manual ...

Page 11: ...ays terminal 5 on the plug of the Boiler controller 0 10 Volt The terminal closest to the marking X3 is always terminal 6 on the plug of the Boiler controller GND Incorrect pin assignment The offset value is always dis played rather than the cur rent weight 3 Connection of the power supply ÖkoFEN recommends that the power supply is always connected to the weighing system via the Boiler control ler...

Page 12: ... the current weight to 0 by putting in the negative of the current weight shown in P 132 Therefore you have to turn the thumbweel left Pelletronic Touch Textile tank Level detection system of textile tank by weighting cells The threshold value Minimum weight for a warning message is adjustable The warning message appears on the operating device and will be terminated when filling level rerises abo...

Page 13: ......

Page 14: ......

Page 15: ......

Page 16: ......