oke-2020TH user manual V19-9 en.PDF
Required Temp./ Humid. Setup process
Master mode Setup process
1. Press SET button (5 sec)
for requested Humid./
Temp.
2.
Humid. or Temp
.
➢
Humid. Set range : 0 ∽ 99.9
%
➢
Temp. range : -55.0
∽ 99.9
C
1. Press
Up / Down
button
for requested set Humid./
Temp.
1. Press
SET button during
5 seconds
(or wait 10
seconds) to save new
value and then return to
normal function display
1. Press shortly SET button
For
Humid. Or Temp.
till display “
OK
” and then the
value will auto save.
➢
Operation range :
-
55℃~99.9℃ / 0%~100%
➢
External size (mm) : 76(W) x 34(H) x 75(D)
➢
Cutting size (mm) :70(W) x 30(H)
➢
Delay time : 0 ~ 9 MIN (1min/unit)
➢
Correct Current Humidity. :
-9.9~+9.9
℃ (0.1℃/units)
/ -
9.9~+9.9% (0.1%/units)
➢
Input sensor :
NTC (5K
Ω 25℃) /
HIH-4000(5V)
sensor
➢
Sensor accuracy : Temp 1% / Humidity 2 %
➢
Power supply :
100~240VAC 50/60Hz (free Volt)
➢
Power Consumption : Aver. 5VA
↓
➢
Ambient temp./ Humidity : 0
℃
~50
℃
/ 80%
↓
➢
Output : 2 relay ON/OFF (250VAC 2A) (R1: Temp, R2:
Humidity)
➢
Output deviation :
0.0℃~9.0℃ (0.1℃/units) /
0.0~9.0%
(0.1%/units)
1. Press
SET button during 5 seconds
for requested Humid. or Temp.
2. Press
Up / Down
button for requested set Humid. or Temp
3. Press SET button shortly to switch required function
4. Press SET button during 5 seconds (or after 10 seconds) Master mode
will save with new value saving
automatically and return to normal function mode.
.
➢
Set the
Highest value
for Required Temp./Humid.
➢
When change the required value, it
should be lower than HSP
➢
Set the
Lowest value
for Required Temp./Humid.
➢
When change the required value, it
should be higher than LSP
➢
When set the function, just Output display lamp will be blinking
without any operation during the set delay-time.
➢
When ended the set delay-time, Output display lamp will be blink
and then start the real Output “ON”
➢
(
♠
P
ease refer the below
graph for the Output Delay-time Value
)
❖
Output control graph for the Output
Deviation Value Chart
➢
When - Set Temp.: 0C/ delay-time : 0 min /
Deviation : 5.0C / mode: C(cooling)
➢
Output control ON/OFF graph for the Temp.
Output Deviation Value
❖
Output control graph for the Output
Delay-time Value Chart
➢
When
–
Set delay-time : 0 min
➢
When
–
Set delay-time : 2 min
Output OFF
Output ON
Output OFF
Output ON
Delay
Time
❖
Specification Details
➢
When set the function, the required Output will ON/OFF depend on
the Deviation value
➢
When equal current Temp./Humid. With required value, the Output
will
OFF
and when there are any deviation value, Output will
ON
➢
(
♠
P
ease refer the below
graph for the Output Deviation Value
)
➢
When there are any different in between the current Temp./Humid.
and the required values, function will allow to correct the values
discretionally.
➢
Just correct the different Temp./humid. Values in between with
current and required values
➢
Set the Output mode (Temp./Humid.) function
➢
When if set as C(D) mode, the Output will be ON when the current
Temp.(Humid.)
is higher than the required Temp.(Humid.) value
➢
When if set as H(H) mode, the Output will be ON when the current
Temp.(Humid.) is
lower than required Temp.(Humid.) value
5. Press SET button during 5 seconds, and then new values will be saved
6. Or after 10 seconds, new values will be saved automatically
7. Return to normal function mode display