background image

I N S T R U C T I O N S

© 2016 OJ Electronics A/S

1

67027E 07/16 (LOA)

Type OSA4-10

English

RELAY MODULE FOR CS4

TM

Relay module for controlling electric heating 

panels, etc., featuring night setback, frost pro-

tection and floor sensing thermostat mode.

Only for use in combination with the Central 

Controller for wireless communication.

PRODUCT PROGRAMME

OSA4-10 

 

 Relay module incl. mount-

ing box

OSC4/MCS4-10  

Central Controller incl.

 

 

floor sensor

WARNING

 – Important Safety Instructions 

Disconnect the power supply before carrying 

out any installation or maintenance work on this 

unit and associated components. This unit and 

associated components should only be installed 

by a competent person (i.e. a qualified electri-

cian). Electrical installation must be in accord-

ance with appropriate statutory regulations

INSTALLING THE RELAY MODULE

The Relay module is designed for flush mount-

ing in a wall socket or in the accompanying 

mounting box.

Fig. 1:

1.  Slide the power button down to Off “0”.

2.  Release the front cover ONLY by inserting a 

small screwdriver into the hole on either side 

of the Relay module.

Fig. 2, 2a eller 2b:

3.  Connect the wires in accordance with the 

diagram. 

4.  Mount the unit in a wall socket or the accom-

panying mounting box. 

5.  Fit the frame and carefully press the cover 

onto the Relay module. Ensure that both 

the power slide button on the cover and the 

power switch pin are down.

DO NOT

 open the Relay module by releasing 

the four fixing clips on the back.

APPLICATION

The relay module can be used for three different 

control types: Night setback, Frost protection or 

with an external floor sensor.

Fig. 2: Night setback

Connect the heating panel to terminal 4. The 

relay module sets the heating panel in setback 

mode according to the time programmed in the 

4-event time schedule from the Central Control-

ler (most heating panels have a built-in ”night 

setback input-connector”). 

Fig. 2a: Frost protection

Short-circuit terminals 5 and 6 to set the relay 

module to frost protection.  

The relay module enters frost protection mode 

and uses the built-in room sensor to maintain 

the frost protection temperature.  

In frost protection mode, the relay module 

ensures that the heating panel maintains the 

setpoint set on the Central Controller.

 

Fig. 2b: Thermostat with external sensor

Connect a floor sensor to terminals 5 and 6. 

Now the relay module works as a thermostat 

controlling the heating according the floor 

temperature.  

The relay module controls the temperature ac-

cording to the 4-event time schedule from the 

Central Controller.

MOUNTING THE RELAY MODULE 

The accompanying mounting box makes it 

easy to mount the Relay module on the wall. 

Draughts and direct sunlight or other heat 

sources must be avoided. 

Fig. 3:

Observe the minimum distance of 0,5m, from 

large metal surfaces, electronic equipment, 

electric motors, etc.

Fig. 3a:

To ensure good signal transmission the unit 

should be mounted as high as possible.

The unit should be mounted min. 0,5m above 

the floor, away from the heating source, in such 

a way that the unit is unaffected by the floor 

heat. 

Fig. 3b:

To ensure good wireless transmission without 

interference, 

all wireless units

 in the Comfort 

System CS4

TM

 should always be placed with 

min. 1,0m between them.

SETTINGS

See user manual for CS4

TM

 for further options 

and how to plan you system. 

LED READOUTS

Green ON:

 Power ON, Relay module OK.

Green flashes 

quickly:

 Connection sequence in 

progress

Green flashes 

slowly:

 No connection to Central 

Controller

Red ON:

 Relay ON, power to heating 

source

Red flashes 

quickly:

 Error  code
1 flash

E1:  Internal sensor 

defective or 

short-circuited.

2 flashes E2:   External  sensor 

defective or 

short-circuited

5 flashes E5:   Internal 

overheating. 

Inspect the 

installation.

6 flashes E6:   Communica-

tion error

FACTORY RESET

Allows factory settings to be re-

stored and cancels the connection 

to the Central Controller.

1.  Remove the cover by inserting 

a small screwdriver into the hole 

on one side of the thermostat. 

2.  Now hold the screwdriver on 

the contact points under the LEDs. 

Hold it until both LEDs flash three times. The 

relay module has now been reset.

3.  Mount the cover and turn the power off and 

on again. The relay module will now connect 

to the Central Controller.

CERTIFICATION

OJ Electronics A/S hereby declares that  

the product conforms with the following 

Directives of the European Parliament and 

of the Council: 

LVD, EMC, R&TTE, RoHS and WEEE 

Applied standards

Please see the document “EC DECLARATION OF 

CONFORMITY” in the back.

CLASSIFICATION

The product is a Class II device (enhanced insu-

lation) and must be connected in the following 

way: 

Term. 1:   Neutral (N)

Term. 2:   Phase (L) 230 V ±10 %, 50/60 Hz 

Term. 3-4:  Load, max. 16 A / 3600 W

Term. X:   Do not connect 

Term. 5-6:  Night setback, frost protection or  

 

external floor sensor

ENVIRONMENT AND RECYCLING

Please help us to protect the environment by 

disposing of the packaging in accordance with 

national regulations for waste processing.

RECYCLING OF OBSOLETE APPLIANCES

Appliances with this label must not be 

disposed of with general household 

waste. They must be collected 

separately and disposed of in 

compliance with local regulations.

TECHNICAL DATA

Voltage  .......................... 230 V AC ±10 % 50 Hz

Max. pre-fuse .............................................. 16 A

Built-in circuit breaker .................... 2-pole, 16 A

Output relay ............  Make contact - SPST - NO

Output ...............................  Max. 16 A / 3600 W

Control principle ...................................  PWM/PI

Stand-by power ........................................... 1 W

RF frequency band ...............................868 MHz

RF transmission range ..... 100 metres/open field 

Frost protection ..................................+5/+10 °C

Ambient operating temperature ..........+0/+25 °C

Pollution degree ...............................................  2

Overvoltage ...............................................Cat. II

Rated impulse voltage ................................  4 kV

Enclosure rating ........................................ IP 21*

Dimensions .....................  H/81, W/81, D/40 mm

Mounting depth ......................................  20 mm

EU Registered Design  ........ 001101349-0001/2

Automatic action type 1

* IP 21 applies only to front with cover after 

mounting in a flush box

The relay module is maintenance free.

OJ ELECTRONICS A/S

Stenager 13B · DK-6400 Sønderborg

Tel: +45 73 12 13 14 · Fax: +45 73 12 13 13

[email protected] · www.ojelectronics.com

Reviews: