Warnings and Cautions
The OilSafe
®
Advanced Bulk System is designed for the storage of machinery lubricating oils and other NON-VOLATILE
fluids. STORAGE OF FLUIDSWITH A FLASHPOINT BELOW 150°F (65.5°C) IS STRICTLY PROHIBITED.
Components within this system consist of materials that may not be compatible with your fluid. ALWAYS consult
your supplier and refer to thefluid manufacturer’s Material Safety Data Sheet (“MSDS”) before introducing a fluid to
this system.
WARNING!
When replacing tanks, a Whitmore employee must be present to participate in, or supervise
theremoval of tanks on frames.
ALWAYS ensure the main power supply is first locked out and the system depressurized before
any service is performed on this system. NEVER connect or disconnect lines or change filter
elements or undertake any service work when this system is running or energized. SEVERE
INJURY OR DEATH MAY OCCUR.
CAUTION!
System Operating Pressure should NEVER exceed 300 PSI. Operating pressures can be
regulated by adjusting pump bypass relief valves located on pump heads to suit specific
lubricant viscosities and temperatures.
IMPORTANT:
ALWAYS REFER TO THIS MANUAL OR CONSULT YOUR SUPPLIER FOR MORE INFORMATION.
•
ALWAYS ensure that you wear appropriate Personal Protective Equipment (“PPE”) when operating this system.
•
ALWAYS ensure that all system hoses, filters, and fittings are securely fastened and in good working condition.
•
THE FIRE SAFETY VALVES (LOCATED ON THE UNDERSIDE OF EACH TANK) MUST BE IN THE OPEN
POSITION WHEN OPERATING THE SYSTEM AND IN THE CLOSED POSITION WHEN SERVICING THE
SYSTEM.
•
ALWAYS ensure that the System Pressure Return Hoses (discharging to the upper port on the rear face of each tank)
are never restricted or damaged.
•
THE BULK TANKS MUST ALWAYS BE VENTED TO ATMOSPHERE (preferably utilizing a Desiccant Air Breather).
•
When filling Bulk Tanks from drums or barrels always ensure the grounding cable is connected to the drum or barrel
before starting the pump.
•
ALWAYS ensure the system is appropriately grounded to earth utilizing the grounding jacks provided at the rear
base of the system, together with relevant grounding equipment as specified and installed by your authorized
electrical personnel in accordance with your local and federal regulations and safety procedures.
•
Ambient room temperature where the system is installed should be in the range of 60°F (15°C) TO 80°F (26°C) with
optimum room temperature being 70°F (21°C). For ambient temperatures below 60°F (15°C) consult the manufacturer
or your supplier for the supply of electric blanket heaters for oil barrels, pails, and bulk tanks to ensure stability of
lubricant viscosity, condition, and system performance. Temperatures less than (<60°F / 15°C) can result in lubricant
viscosity increasing above the rated ISO Code you specified at the time of order. Such adverse viscosity changes can
cause higher system operating pressures than those set at the factory. System operating pressure should never
exceed 300 PSI. Contact the manufacturer for more information prior to commissioning the system if the ambient
room temperature will ever fall below 60°F (15°C).
WARNING
!
FAILURE TO FOLLOW System installation, safety and operating instructions may result in SEVERE
INJURYOR DEATH, damage to plant and equipment and void warranties.