7.2 Compressor units
RE
MODEL / RATED
CAPACITY (kW)
3~ 400 V, 50 Hz, PE
28
33
38
42
48
56
66
76
84
96
Number of compressors
1
1
1
1
1
2
2
2
2
2
Compressor type
28
33
38
42
48 28+28 33+33 38+38 42+42 48+48
Number of compressors
1
1
1
1
1
2
2
2
2
2
Number of evaporators
1
1
1
1
1
2
2
2
2
2
Number of condensers
1
1
1
1
1
2
2
2
2
2
MODEL / RATED CAPACITY (kW)
3~ 400 V, 50 Hz, PE
28
33
38
42
48
Heat pump version
05
05
05
05
05
Refrigerant
R-410A R-410A R-410A R-410A R-410A
Number of refrigerant circuits
1
1
1
1
1
Number of compressors
1
1
1
1
1
Number of evaporators
1
1
1
1
1
Number of condensers
1
1
1
1
1
Refrigerant circuit (EU517/2014)
Contains fluoridized greenhouse gases
yes
yes
yes
yes
yes
Hermetically sealed device
yes
yes
yes
yes
yes
To be checked periodically for leaks
(maximum refrigerant charge: 10 CO
2
-eq t)
no
no
no
no
yes
Refrigerant
R-410A R-410A R-410A R-410A R-410A
Refrigerant’s GWP value (global warming potential) 2,088
2,088
2,088
2,088
2,088
Refrigerant charge, g*
5,250
5,200
5,300
5,100
5,100
Refrigerant charge, kg*
5.25
5.2
5.3
5.1
5.1
Refrigerant charge, CO
2
-eq kg*
10,962 10,858 11,066 10,649 10,649
Refrigerant charge, CO
2
-eq t*
10.962 10.858 11.066 10.649 10.649
Low pressure switch
Cut-off pressure, low, bar (g)
3.4 ± 0.5 3.4 ± 0.5 3.4 ± 0.5 3.4 ± 0.5 3.4 ± 0.5
Recovery pressure, bar (g)
5.9 ± 0.5 5.9 ± 0.5 5.9 ± 0.5 5.9 ± 0.5 5.9 ± 0.5
High pressure switch
Cut-off pressure, high, bar (g)
45 ± 1.2 45 ± 1.2 45 ± 1.2 45 ± 1.2 45 ± 1.2
Recovery pressure, bar (g)
35 ± 2.0 35 ± 2.0 35 ± 2.0 35 ± 2.0 35 ± 2.0
Compressor
Compressor type
scroll
scroll
scroll
scroll
scroll
*Always check the refrigerant charge from the name plate primarily. Pay attention to
any changes made to the refrigerant charge after installation.
M8009 2147EN
45 (74)
Summary of Contents for RE 28 05
Page 1: ...M8009 2147EN 25 October 2021 Installation and operation manual RE 28 48 RE 56 96...
Page 2: ......
Page 45: ...RE 04 dimensions single unit configuration Two units M8009 2147EN 43 74...
Page 46: ...RE 04 dimensions two unit configuration 44 74 M8009 2147EN...
Page 61: ...7 4 EN 14285 Technical data sheets RE 28 RE 28 Technical data sheet ver 1 M8009 2147EN 59 74...
Page 62: ...RE 33 RE 33 Technical data sheet ver 1 60 74 M8009 2147EN...
Page 63: ...RE 38 RE 38 Technical data sheet ver 1 M8009 2147EN 61 74...
Page 64: ...RE 42 RE 42 Technical data sheet ver 1 62 74 M8009 2147EN...
Page 71: ...Wilo Stratos 40 1 12 Wilo Yonos MAXO 40 0 5 16 M8009 2147EN 69 74...
Page 77: ......