4.4 Bleeding the system of air
You can use the
relay test
function (see section
Relay test
) to make it easier to bleed
the system of air.
● Use the relay test to run the pump for a while, then stop, then run the pump again.
● Bleed and fill (pressurize) the circuits during each break.
● Repeat until bleeding is complete.
● If necessary, switch the positions of the change-over and control valves during
bleeding.
22 (74)
M8009 2147EN