TECHNICAL  DOCUMENT 

EPC 

EPC3 Quick Start Guide 

ELECTRONIC 

 

Telephone: 
Fax: 
Website: 

(414) 327-1700 
(414) 327-0532 
www.oilgear.com 

OILGEAR 

2300 S. 51st. Street 

Milwaukee, WI USA 53219 

Issued:        June, 16 2015 

Bulletin

 836270B 

 

USB Driver Installation: 

The curre

nt PC interface is installed under “Oilgear Applications” 

while  the  older  PC  interfaces  were  installed  under  OAsys 
Applications.  If you are upgrading from older software both start 
menu  groups  may  appear  in  the  list.    The  link  to  “Install  USB 
Drivers  for 

EPC3”  however  will  only  appear  under  the  “Oilgear 

Applications” menu. 

USB Cable Connection:

  

The  EPC  must  be  “off-line”  before  removing  the  USB 
communications cable.  Failure to do so may result in a reset of 
the EPC3 with temporary loss of closed loop control and may lead 
to equipment damage or personal injury. 

On/Offline connection can be toggled by the “eye” button on the 
EPC3 toolbar below, grey indicates OFFLINE. 

EPC Output Notice: 

The EPC valve driver and LVDT oscillator outputs cannot be directly shorted. 

Shorting the valve driver outputs terminals J1-3 and J1-4 or LVDT Oscillator terminals J6-3 and J6-4 will 
result in permanent damage of the EPC device. 

The outputs of the EPC can be monitored with the EPC Support Software (for more information refer to the 
online help in the software).  When attempting to measure the current at the output terminals make certain 
that a load is present in your meter circuit to prevent EPC damage.

 

 

 
 
 
 
 
 
 
 
 
 
 