2. Mounting 

2-1 Caution 

Danger

 

 

For prevention of electrical shock, power supply to the control panel should be 

disconnected before installation work. 

 

Caution

 

 

For installation, do not use any parts other than originally supplied ones.   

Failure to this may result in injury or breakdown of the cooling unit. 

In case screws are used for installation instead of the original bolts, 

put a plate between the screw and the cap nut so as the direct torque not to 

be transmitted. Or, the cap nut may cause slipping. 

 

Cut out the mounting surface of the enclosure as specified in the drawing of page 8. 

 

 

COOLCABI must be placed horizontally and   

perpendicularly within a tolerance of 

±

2

  in order 

to keep stable operation of the unit and 

to make a smooth drainage. 

 

 

 

Locate  the  unit  so  as  to  assure  good  ventilation 

and distance of at least 200mm from the walls or 

other units.   

Also,  there  should  be  no  hindrance  to  the  air 

circulation inside the control panel. 

Failure  to  the  above  may  result  in  poor  cooling 

performance or condensation. 

 

 

The supply voltage must be as specified on the rating 

plate of the unit. 

Electrical connection should be made via appropriate   

circuit breakers as shown in the right. 

Ground  the  wire  without  fail  to  prevent  electrical 

shocks 

Electrical works required for installation of the unit must be done only 

by specialists. 

Improper installation may result in electrical shocks or fires. 

For protection of the compressor, wait at least 30 minutes after installation 

before connecting power to start operation. 

 

Hermetically seal the control panel all round. 

Inferior sealing may cause condensation which lead to poor cooling efficiency. 

Put covers on the components inside the enclosure to protect them from 

cutting dust during installation work. 

[Short circuit] 

Electric  components  or  other  objects  near  the  cool 

air outlet may disturb cool air circulation. If the cool 

air  hit  against  them,  it  will  directly  return  to  the 

suction port without being distributed to the whole 

area in the enclosure. This causes not only troubles 

of  the  components  but  may  negatively  affect 

operation  of  the  cooling  unit  which  lead  to 

overcurrent and product failure. 

In  case  such  short  circuit  is  found  during  cooling 

operation,  improve  the  environment  by  attaching 

rectifying  plates  or  installing  agitation  fans  as 

necessary. 

Rectifying 
plate 

Agitation fan 

Control equipment 

COOLCABI 

Cool 
air 

COOLCABI 

Enclosure  Enclosure 

COOL 
CABI 

200mm or more 

Enclosure 

COOL 
CABI 

Wall, 
other units 

200mm 
or more 

Earth 

Breaker for 
Leakage 

R  S 

COOL 
CABI 

Summary of Contents for COOL CABI OCA-S300BC

Page 1: ...OCA S300BC OCA S300BCS OCA S600BC OCA S1000BC OCA S1600BC...

Page 2: ...2 20 50 85 RH 70...

Page 3: ...3 M6 2 200mm 30...

Page 4: ...4 P 5 P 6 OCA S300BC 4 0 P 6 2 2 P 6 2 OCA S1000BC S1600BC 4 OCA S300BC...

Page 5: ...5 OCA S1000BC OCA S1600BC OCA S300BC OCA S300BCS OCA S600BC OCA S1000BC OCA S1600BC...

Page 6: ...6 OCA S300BC OCA S300BCS OCA S600BC OCA S1000BC OCA S1600BC OCA S600BC...

Page 7: ...7 40 25 45 P 3 70 4 4 45...

Page 8: ...8 10 AWG24 12 0 2 2 5mm2 6 7mm OCA S1600BC a 240V 1 5A 2 P 11 12 L N E 1 2 3 AC200V or AC100V IN...

Page 9: ...9 1 30mA 30 ON OFF 1 6 ON OFF ON OFF P 10 35 Set Up Down 35 30 45 Set Up Down 3 30 Set Down Up RUN ALARM Down Up Set...

Page 10: ...t 3 Set Up Down Set 5 3 10 1 6 ON OFF 30 0 90 Up Down 3 45 35 51 2 1 20 0 0 99 0 1 99 1 100 1 99 9900 24 412 0 0 1 0 1 0 0 1 0 P 15 5 1 2 1 P 15 5 1 2 1 0 1 OPEN CLOSE OPEN CLOSE 0 1 0 0 0 3 0 1 2 3 P...

Page 11: ...11 P 13 14 0 0 1 OPEN CLOSE 0 1 0 1 2 3 P 11 12 1 0 3 0 1 2 3 7 7 60 3 3 3 10 ON OFF Set 3 30 Set 3 AS Ao 1 2 2 3 OPEN 0 8 AS 0 AS 1 AS 2 AS 3...

Page 12: ...E3 E4 CLOSE E5 SE OPEN E1 E3 E4 OPEN 3 E3 E5 SE CLOSE E1 E4 CLOSE E3 E5 SE OPEN E1 E4 OPEN E4 P 10 0 Ao 1 AS 1 2 2 3 0 OPEN CLOSE CLOSE OPEN 1 OPEN CLOSE CLOSE OPEN 2 E5 SE OPEN E1 E3 E4 OPEN E5 SE C...

Page 13: ...13 35 5 35 30 4 P 12 3 30 1 30 5 35 30 ON OFF ON OFF 35 30 ON OFF ON OFF...

Page 14: ...14 7 3 5 5 35 ON OFF ON OFF 35 45 ON OFF ON OFF 30 30...

Page 15: ...15 45 P 12 43 P 12 Set 3 P 12 Set 1 P 12...

Page 16: ...16 OFF 1 1 OCA S300BC OCA S300BCS OCA S600BC OCA S1000BC OCA S1600BC OCA S600BC P 17 OCA S600BC P 17...

Page 17: ...200V OCA S1000BC A200 FM 1000BCIN 200V FM 1000BCOUT 200V OCA S1600BC A200 FM 1600BCIN 200V FM 1600BCOUT 200V OCA S300BC A100 FM 300BCIN 100V FM 300BCOUT 100V OCA S600BC A100 FM 600BCIN 100V FM 600BCO...

Page 18: ...134a HFC R407C 100g 130g 170g 400g 450g 1430 1770 W H D mm 300 500 150 200 590 200 300 550 200 350 900 200 390 950 220 16 0kg 14 0kg 18 0kg 33 0kg 36 0kg OCA S300BC A200 R OCA S600BC A200 R OCA S1000B...

Page 19: ...3 20 2A 26 2 23 8A 2 265 250W 365 385W 665 770W 805 890W 310 300W 475 530W 1065 995W 1200 1135W 100W 250W 400W 470W A 65dB 68dB HFC R134a HFC R407C 140g 180g 410g 510g 1430 1770 W H D mm 300 500 150 3...

Page 20: ...20 OCA S300BC OCA S300BCS OCA S600BC OCA S1000BC OCA S1600BC 1 M6 35mm 4 M6 35mm 6 M6 35mm 4 M6 35mm 6 M6 4 M6 6 M6 4 M6 6 M6 4 M6 6 M6 4 M6 6 M6 4 M6 6 M6 4 M6 6 1 1 2 1 1 1 1 1 2 M4 4 M4 4 M4 8 R...

Page 21: ...21 OCA S300BC OCA S300BCS R 12 4 M6 14 6 M6 14 12...

Page 22: ...22 OCA S600BC OCA S1000BC R 12 6 M6 14 2 M8 13 4 M6 14 12...

Page 23: ...23 OCA S1600BC R 12 6 M6 14 2 M8 13...

Page 24: ...24 1 13 64 19 10 27 4 4 431 1304 7000 21 TEL 053 522 5572 FAX 053 522 5573 9 2019 5...

Page 25: ...OCA S1600BC Contents 1 Safety Precautions 2 Mounting 3 Wiring 4 Operation 5 Alarm Safeguard 6 Maintenance 7 Specifications 8 Warranty period 9 Waste disposal Please read this brochure carefully before...

Page 26: ...in short life or damage of the unit Shocks and vibrations should be strictly avoided at the site of use Never tamper or repair the main body Please consult with your local supplier for repairing servi...

Page 27: ...as shown in the right Ground the wire without fail to prevent electrical shocks Electrical works required for installation of the unit must be done only by specialists Improper installation may result...

Page 28: ...panel is fixed with 2 screws on the lower side with its upper rim hanging on the main body lift it up after removing the screws to release 3 Secure the enclosed 2 fixing bolts on the upper side 4 Att...

Page 29: ...ease lift up evenly using eyebolts whenever lifting up a cooling unit Lifting up one side only may result in breakdown or damage of the product Cutouts for External Mounting View from outside the pane...

Page 30: ...edded Mounting OCA S300BC OCA S300BCS OCA S600BC OCA S1000BC OCA S1600BC Arrangement of packing Ex OCA S600BC Arrangement for external mounting Arrangement for embedded mounting Packing shaded area Pa...

Page 31: ...t of the Adjustable Louver enable to direct output air to the desired direction Note Cooling capacity may decrease up to 5 by using the louver To keep the set angle not to be affected by external impa...

Page 32: ...or 7 mm 2 Push down the Push button with a flathead screwdriver 3 Insert a wire into the port 4 Release the screwdriver 5 Check that the wire is secured 6 For the application using crimp terminals th...

Page 33: ...f injury Never operate COOLCABI leaving the control panel door open Failure to this may lead to excessive condensation and drainage volume as well as creating the possibility to allow condensate to en...

Page 34: ...ting range 0 99 This is the function to remind you maintenance works in a timely manner 0 This function is ineffective 1 99 1 means 100 hours Notification period can be set between 100 to 9900 hours T...

Page 35: ...eriod for restarting the compressor after shutdown For prevention of frequent ON OFF of the compressor cooling operation is suspended during the set period Display of software version This is to displ...

Page 36: ...E3 E5 and SE OFF OPEN Alarm E1 and E4 OFF OPEN Alarm E4 is not output when Fo is set at 0 See page 10 Assignment table of Alarm output terminals Ao 1 AS Terminals 1 2 Terminals 2 3 Description Operati...

Page 37: ...eration will not start for a certain period of time initial setting 3 min after cooling operation has stopped even if the internal temperature goes up to the set temperature 1 Continuous run Cooling o...

Page 38: ...he air is not circulated by the internal fan For protection of the refrigerant circuit the internal fan will not stop for 5 minutes after cooling operation has stopped The internal fan runs continuous...

Page 39: ...operation 3 E4 Maintenance reminder When the cumulative operating hour reaches the set value the alarm output terminals will break and make contact as set in AS Ao and Fo to light alarm lamp See the a...

Page 40: ...rom the guide of the front panel to clean or replace Replacement filter for external suction port Model Applicable COOLCABI models CF S1 2 pcs set OCA S300BC OCA S300BCS OCA S600BC CF S2 2 pcs set OCA...

Page 41: ...eaker b Check the temperature setting and the internal temperature c Set a higher value or change the cooling unit with a one of higher capacity d This unit is unusable under a circumstance where the...

Page 42: ...ount 100g 130g 170g 400g 450g GWP 1430 1770 Outer dimensions WxHxD in mm 300 500 150 300 500 150 300 550 200 350 900 200 390 950 220 Weight 16 0kg 14 0kg 18 0kg 33 0kg 36 0kg Bottom flow Model OCA S30...

Page 43: ...y Not exceeding 85 RH free from condensation Setting temperature range 3 30 to 45 Initial setting 35 Display Internal temperature Alarm code Operating lamp Alarm lamp Function Off temperature alarm De...

Page 44: ...M6 35 6 Washer M6 4 M6 6 M6 4 M6 6 M6 6 Spring washer M6 4 M6 6 M6 4 M6 6 M6 6 Nut M6 4 M6 6 M6 4 M6 6 M6 6 Packing 1 roll Drain hose 2m Terminal board 1 Alarm explanation sheet 1 Instruction manual...

Page 45: ...units A mesh filter is attached to the cool air outlet for prevention of water scattering The adjustable louver is not included with shipment Drain pipe Outer dia 12 Warm air Air from outside Air fro...

Page 46: ...e adjustable louver is not included with shipment Top view Drain pipe Outer dia 12 External air inlet filter White Cool air Warm air Terminal board Operation panel Air from outside Air from inside Fro...

Page 47: ...filter is attached to the cool air outlet for prevention of water scattering The adjustable louver is not included with shipment Drain pipe Outer dia 12 External air inlet filter White Air from inside...

Page 48: ...user Recovery of the refrigerant should be done by an authorized waste disposer Owner s management responsibility Check of equipment The enclosure cooling unit needs simple regular inspection Daily ch...

Reviews: