5- Instruction for the fitter:

 

The fitter has to read the following notice and explain the instructions to the user.

 

5-1      Devices of control and safety:

 

 

The heat pump is equipped with: 

2 control devices: 

 

A defrost temperature probe located on the evaporator, starts the defrost sequence. 

 

A thermal probe located on the exchanger, ensures the cut of the heat pump when the temperature of the water reaches 

the temperature instructed 

The meaning of code name: 

T1: water temperature 

T2: ambient temperature 

T3: exhaust temperature from compressor 

T4: coil temperature in outdoor heat exchanger 

TC: water temperature setting 

Control function: 

 

1.      TC  can  be  set  between  10

-60

  in  heating  mode.  Original  TC  is  45

.  When  T1≤TC-1

,  Compressor  and  fan  motor 

start; When T1≥TC+1

, Compressor and fan motor stop. 

When compressor is running, if T2≤14

, the four way valve2 on; if T2≥16

, the four way valve2 off. 

 

5-2        Defrost operation:

 

 

 

1. Defrost: 

The system begins to defrost if the following three terms are met in the same time: 

a. T4

-7

    lasts for a while; 

b. compressor runs continuously for more than 5 minutes 

c. Compressor runs accumulative total for 45 minutes(the interval between two defrost is a cycle, time accumulates) 

While  the   system  begin  to  defrost,  compressor  and   fan   motor   stop   at  first  and   four  way  valve1  is   on   after  1   
minutes  and 

begins  to  work,  compressor  restarts  after  it  stop  for  3  minutes.  If  the  sensor  for  T4  is  damaged,  the  system  begins  defrosting 

after compressor runs continuously for 45 minutes. 

 

2. Terms of defrost exiting: 

 

When defrosting time reach 3  minutes  and  T4 reaches  10

    or defrosting time reaches 8  minutes, defrost exits and enter 

heating  water  mode.  While  defrost  exiting,  after  compressor  and  fan  motor  stop  for  1  minute,  four  way  valve1  is  off. 

Compress restart after it stops for 3 minutes, the system will run the mode the same as before defrost. 

 

5-3        Instruction    of    the    solar    coil   

 

 

Instruction of the solar coil 

Type 

Data

 

 

150L

 

 

200L

 

 

300L

 

 

Thickness (mm)

 

 

1.0

 

 

1.0

 

 

1.0

 

 

Length (m)

 

 

19

 

 

19

 

 

19

 

 

Diameter(mm)

 

 

15.88

 

 

15.88

 

 

15.88

 

 

Connecting Size (inch)

 

 

1/2’ male thread

 

 

1/2’ male thread

 

 

1/2’ male thread

 

 

16 

Summary of Contents for KS25-C120

Page 1: ...AIR SOURCE HEAT PUMP All in one type TOP DISCHARGE WITH DOUBLE DUCTS Installation And Operating Instructions MODEL KS25 C120 KS25 C150 KS25 C200 KS35 C300 FEB 2010...

Page 2: ...he animals or the objects On no account the importer of this apparatus could not be made responsible for this damage Use of the heat pump this heat pump is intended exclusively with use for which it w...

Page 3: ...lectric connections p12 3 4 Running of reversible heat pump p12 3 5 Description of the screen of display and control p13 4 Use in standard mode p14 5 Instruction for the fitter 5 1 Devices of control...

Page 4: ...le to result in death Any wrong handling can cause serious damage to the user and the machine TO NOT DO To follow attentively To be sure of the electric connections To be sure of the disconnection of...

Page 5: ...ore all the button OFF Do not draw on the power supply cable Well have in hand the plug to disconnect it Fire hazard could occur due to the wrenching of the electric cable Do not touch the plug with w...

Page 6: ...2 1 Outside 4 3 9 2 8 5 1 11 12 10 7 6 Power Plug Control pannel Air Inlet Air Outlet Temperature Sensor Drainage hole Cold Water Inlet Hot Water Oulet 9 Service valve 10 solar coil inlet 11 solar coi...

Page 7: ...5 Plastic Base 19 Capillary 33 6 Water tank 20 Defrost sensor 34 7 Motor Capacitor 21 Assistant unit of air outlet 35 8 Compressor capacitor 22 Fan motor 36 9 Compressor 23 Electrical Box 37 10 Circu...

Page 8: ...695 1825 Air ducts Dimension mm 150 150 Net weight Gross weight kg 55 64 66 75 73 82 81 90 Water Connection Inch 1 1 Capacity of the water tank L 120 150 200 300 Power Supply V Ph Hz 220 240 1 50 220...

Page 9: ...agram below 0 5m UNIT 0 5m 0 5m 0 5m The ventilator should not blow towards the windows or crossing place There must be more than 1 5M space on the top of the unit The fixing board of the unit must be...

Page 10: ...lve to fill water Meanwhile open the hot water out valve till water spill over from the hot water out valve It means the tank is full of water Close the tap water in valve check leakage by storing ful...

Page 11: ...choice Option B Installation in the laundry washing room Hot water heating from room air Optional use laundry drying decalcified water for steam iron Dehumidification Option C Installation in the same...

Page 12: ...BEFORE THE STARTUP OF HEAT PUMP IT IS SIGNIFICANT TO INCLUDE UNDERSTAND THE OPERATING AND THE SETTINGS OF WHICH YOU WILL TAKE NOTE IN THE FOLLOWING PARAGRAPHS 3 4 Running of reversible heat pump By u...

Page 13: ...and down It sets the temperature of water and time of dose the heater OFF CLOCK On off To adjust the current hour and functioning timetable To adjust the hour 2 WITHOUT WATER TANK ASSISTANT ELECTRICA...

Page 14: ...minutes lights Press the button or for increasing or decreasing the minutes Validate in pressing on or wait 10 seconds the display will leave this setting mode by it self Setting of running selected...

Page 15: ...ifference of compressor star 3 C to 15 C adjustable 3 After setting the value the defrosting setting will exit automatically after several seconds And the system will memorize the last value of each s...

Page 16: ...the following three terms are met in the same time a T4 7 lasts for a while b compressor runs continuously for more than 5 minutes c Compressor runs accumulative total for 45 minutes the interval betw...

Page 17: ...ient temperature is more than 4 2 Compressor electric heater Working conditions A When the compressor is not working and ambient temperature is less than 0 electric heater will start B When ambient te...

Page 18: ...8 Gas Flow Diagram 18...

Page 19: ...OTOR T2 YV1 CURRENT INDUCTOR FOUR WAY VALVE 1 XT1 YV2 PUBLIC TERMINAL FOUR WAY VALVE 2 C2 FAN MOTOR CAPACITOR 2 XT POWER TERMINAL With Water Tank Electrical Heater RED S CM C BLACK C1 Y G WIRING DIAGR...

Page 20: ...k plastic conduit to evacuate the condensates is not connected or is stopped The condensates are entailed by the condensation of the humid air on the wings of the evaporator It s quite natural Install...

Reviews: