Operating manual
DHR - classic DHR - comfort DHR - expert
18
4.8
Adjusting the heating curve
Due to the deviation of room temperature to outside temperature each time, chan-
ges should be made as follows:
Changes are only processed slowly by the building. For this reason,
only one change should be made per day.
Operation step
Operation
Display
Select function
Set the heating curve.
Example:
Heating curve 1.2
Select another function
or close the cover
The setting is stored
The selected function or
the standard display
appears
Outside
temperature
during the day
Room temperature
too cold
too warm
+5 until +15 °C
Set slope of heating curve
to
- 0.2 and base
to + 5 K.
Set slope of heating curve
to
+ 0.2 and base
to - 5 K.
-20 until +5 °C
Set slope of heating curve
to + 0.2
Set slope of heating curve
to - 0.2.
A
B