Odyssey
│
Installation and Operation Instructions - Field Wiring
CT80-250
26
8.0 BOILER PIPING
Boiler Water
Pressure - Odyssey boilers are intended to solely for use in pressurized closed-loop heating systems operating
with a “fill pressure” between 12-15 psi at the boiler outlet and a Relief Valve pressure of 30 psi (maximum
working pressure of the boiler).
Oxygen Elimination - The Odyssey boiler is designed to operate in a pressurized closed-loop heating system,
free of air and other impurities. To avoid the presence of oxygen, ensure all of the air is removed from the system
during commissioning via strategically placed, adequately sized air-removal devices located throughout the
heating system and the boiler piping (Figure 8-1). Immediately repair any leaks in the system plumbing to avoid
the addition of make-up water; make-up water provides a source of oxygen and minerals that may lead to heat
exchanger failure, poor performance, unnecessary wear of system components, and premature failure.
Closed System - The Odyssey is not approved for operation in an “open system”, thus it
cannot be used for direct potable water heating or process heating of any kind.
Antifreeze - If using antifreeze, use an inhibited propylene glycol specifically designed for hydronic systems.
NTI recommends against exceeding 35% concentration of glycol.
Near Boiler Plumbing
Install boiler piping for central heat and domestic hot water as shown in Figure 8-1.
Gauges -
The temperature and pressure gauges (Ttridicator) is factory supplied and must be field installed in the
front of the boiler or on the coil plate.
Relief Valve -
A 30 psi relief valve is factory supplied and must be field installed.
Piping -
The closed loop piping system must be in accordance with the central heat piping illustration. All piping
joints must be secure and water tight or the boiler warranty is void.
Water Supply - Pressure regulating “fill valve” (12-15 psi) and back flow preventer are required (Figure 8-1).
Boiler Venting -
Hot waters boilers are designed to operate with the airless water in the system. The NY Thermal
boilers are designed with a built-in air trap, to purge air at the ¾” relief valve nipple. An air vent must be installed
here or the boiler warranty is void.
Low Water Cut Off (LWCO) - To take advantage of the HydroStat’s LWCO feature, the
Odyssey is equipped with a special immersion well call the Electro-well™. Failure to use
the Electro-well™ provided with the boiler will over-ride the LWCO feature and allow the boiler to operation
during low water conditions which may result in over heating, fire, serious injury, or death.
Verify LWCO is Active - Ensure the LWCO active light is illuminated on the HyrdroStat
3250 when using the Electro-well™. If the indicator light is not illuminated than the
LWCO feature is not active. Refer to manufacturer’s instructions included with the HydroStat 3250.
Removing Air - Do not fill the boiler with water until you are ready to fire the burner.
Once filled with water, bring the boiler up to temperature and remove the air.
Removing Air from the Boiler:
1.
Open automatic air vent 1 turn.
2.
Bleed air from system. Starting at the lowest point in the building, open air vents one at a time and leave them
open until water comes out. Close all air vents, except the automatic air vent.
3.
Refill to correct pressure, 12-15 psi.