Plenum Kit
Duct/Flange 2OAC12
2OAC18
2OAC24
2OAC36
2OAC60
FILTERS
DEP-10
10 inch
✓
(1) 10”x20”x1”
2DEP-12
12 inch
✓
✓
(1) 16”x24”x1”
DEP-16
16 inch
✓
✓
(1) 10”x30”x1”
(1) 12”x30”x1”
Maximum
Equivalent
Feet
25
50
60
70
80
Est. External
Static
Pressure
(.20)
(.25)
(.25)
(.25)
(.50)
ACCESSORIES
EVAPORATOR RETURN AIR PLENUM
Evaporator return air plenums are available for installations where it is required to
duct air to the inlet of the evaporator. The evaporator return air plenum allows the
user to connect round duct (flexible or rigid) to the return air intake to reduce air noise
and increase the number of options for solving difficult application problems. The
plenum attaches to the front of the unit, replacing the return air grille. Refer to the
table below for configuration and application information.
DEP-10
for 2OAC12
transitions the return air opening to a 10-inch round duct.
2DEP-12
for 2OAC18 & 2OAC24
transitions the return opening to a 12-inch round
duct.
DEP-16
for 2OAC36, 60
transitions the return opening to a 16-inch round duct.
NOTE
—
When an evaporator return air plenum is installed, it is recommended to set
the evaporator blower speed to high, to avoid coil freeze-up.
FILTER(S)
EVAPORATOR
RETURN AIR PLENUM
13