2
SPECIFICATIONS
2OAC
MODEL: 2OAC
1211 1811 2412 3612 3632 3634 6012
6032 6034
COOLING CAPACITY
11,800
16,800
24,020
VOLTAGE (V/Phase) at 60Hz
208-230/3 460/3 208-230/1 208-230/3 460/3
AMPS
10.4
14.1
14.9
19.6
17.2
8.7
32.0
20.4
14.8
TOTAL WATTS
1180
1670
2700
IN-RUSH CURRENT (AMPS)
60
75
68
113
93
60
178
162
87
PLUG TYPE
5-15P
5-20P
6-20P
6-30P
L15-30P L16-20P
6-50P
L15-30P L16-20P
EER
8.9
COMPRESSOR HP
1
1 1/2
2
COMPRESSOR RLA
9.5
12.3
10.5
13.6
8.8
5.0
27.6
18.1
9.0
COMPRESSOR LRA
50
63
48
83
77
35
158
137
62
EVAP CFM
400
600
810
EVAP MOTOR HP
CONDENSER CFM
580
930
1010
COND MOTOR HP
1/3
CONDENSATE
R-410A CHARGE (oz.)
18
40
37
(A) HEIGHT (in.)
37-3/4
(B) WIDTH (in.)
20
(C) DEPTH (in.)
25
NET WEIGHT (lb.)
180
400
520
SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE
2OACSPECS010119
2200
1
1
1/8
1/3
1390
1/8
24
27-1/2
365
30
35
39-1/2
260
485
5 Gallon Condensate Tank - STANDARD (Pump Optional)
Pump - STANDARD (20 ft. Lift)
66
80
45-3/4
50-1/4
51-3/4
115/1
1200
1950
208-230/1
60,100
36,050
3620
6000
10.0
10.0
3
5
NOTES
* Dedicated Circuit and Time Delay fuse or Circuit Breaker are recommended
* Cooling Capacity is total BTUH at 80°DB/67°WB return air, with 95° DB Condenser Air
* CFM with free discharge
* Cooling EER is determined at high fan speed, with condenser air ducted into another area
* Sound Pressure, dB at 5 feet, commercial operation
* Amps and Watts at 208 Volts (208-230V Models)
COOLING AMBIENT OPERATING RANGE 65° TO 105°
May COOL down to 55° if equipped with hot gas bypass (factory installed)