OIC-406 Manual
Page 11
7 Specifications
7.1 Specifications OIC-406 probe
Temperature:
-
Temperature range: -
50⁰C..+100⁰C
-
Accuracy: ± 0.1⁰C (10-30 ⁰C)
Humidity:
-
Humidity: 0..100%RH
-
Accuracy: ± 0.8 %RH (10-
30 ⁰C)
-
Long term drift: <1%RH/annum
7.2 Specifications Meteolink general
Basic node
SMART node
Remarks
Voltage
12..24 Vdc
12..24Vdc
Power consumption
<1W
< 1.5W
Without sensors
Max current pass through via
SUPPLY &
GND(SUP)
(terminal 1,2 & 9,10 & 13,14)
10A
10A
For linking through nodes
Max total current via SUPPLY
&
GND(sensor)
500mA
500mA
Total of all sensor
connections per node.
Max current CMOS_SUPPLY
50mA
50mA
IP rating
IP 65
IP 20
SMART node must be
installed indoors.
Terminals wire size
0.5 .. 2.5 mm2
0.5 .. 2.5 mm2
push in cage type
NMEA in
2
2
NMEA out / return*
2
2
2
nd
is either return or
output.
Serial in (RS232/422/485)
1
2
2
nd
is 485 connection on
the same port!
Analogue in 0-5 VDC
1
2
Analogue in 0
– 24 mA
1
1
Rain (pulse) input
-
1
UTP
-
1
Configuration only
QNH, QFE & Dewpoint calc
-
yes
Custom string converter
-
yes