Mounting instructions PYROLINE
®
Rapid fire protection duct
EN | 29
Direct mounting on the ceiling, wall or floor
5 5
Creating a wall/ceiling penetration
With wall or ceiling penetrations, for the achievement of the fire resistance
class I30–I90, it is sufficient to plug the cavities around the duct with min-
eral wool and seal them with filler (see Fig. 28 and Fig. 29).
However, if I120 is to be achieved, then seal both sides of the penetration
with a wall connection fitting BSKM-WA 0711 or BSKM-WA 1025 (see
“5.6.6 Mounting a reducer” on page 36). The wall connection fitting is
only available for BSKM 0711 and BSKM 1025.
The wall penetration can be created in a solid wall or a dry construction
wall (lightweight construction wall). When the wall connection fitting is
used, the ducts must run to the wall or ceiling at a 90° angle.
If there is a fire, to prevent heat transfer within the wall inside a duct to the
connection duct, the wall may not be penetrated with a single duct piece.
Instead, the ducts must be mounted separately within the wall with a gap
width of 5‒10 mm.
The two following examples show the mounting of wall penetrations. The
ceiling penetration is mounted in essentially the same way.
5 5 1
Wall penetration in solid wall
The mounting process described below allows achievement of a fire re-
sistance class I90, depending on the fire resistance length of the wall. For
I 120, see “5.6.6 Mounting a reducer” on page 36.
5-10 mm
BSKM 0407/0711/
1025
I30
I60
I90
BSKM 0407/0711/
1025
1
5
6
4
2
3
Fig 28:
Wall penetration through solid wall
1
Ceiling
2
Mineral wool insulation, mater-
ial class A 1, melting point
> 1,000 °C, e.g. OBO MIW
3
Solid wall
4
Sealing with filler
5
For BSKM 1025: insert lid
supports BSKM-DS 1025
6
Gap between ducts: 5‒10 mm