background image

   PAGE 6

OBLICA

 | ELEMENTS INSTALLATION AND USER MANUAL

3. INSTALLATION

Cowl (Chinaman Hat)

8” Outer Case

10” Outer Case

8” Outer Case

10” Outer Case

6” Active Flue

CEILING RING

RUBBER
DEKTITE FLASHING

8” Flue

6” Active Flue

Fireplace outlet

8” Flue

3.1  Installing flue kit

Ensure flue is installed as per Australian 
standards (see the following diagrams below).

NOTE:

The active flue must go around the fireplace 
outlet on the outside.

Summary of Contents for skantherm

Page 1: ...ELEMENTS MODEL SPECIFICATIONS 1 TECHNICAL DATA 2 2 PRE INSTALLATION 3 3 INSTALLATION 5 4 OPERATION 13 5 TESTING 14 Keep for future use...

Page 2: ...MINED UNDER TEST CONDITIONS Nominal thermal output 7kW Efficiency Australian Test 69 Emissions Australian Test 0 6 g Kg 8 Flue 400mm 806mm 203mm MINIMAL CONFIGURATION WEIGHT AND DIMENSIONS Dimensions...

Page 3: ...nal flue and engage the firebox Ensure the floor has adequate protection CAUTION Using components or parts other than those provided by the manufacturer or modifying the specification of components ma...

Page 4: ...fice on 03 9416 0400 or email info oblica com au IMPORTANT Frames must also be considered Timber window frames must be treated as combustible surfaces see 2 3 Aluminium frames can be treated as non co...

Page 5: ...d chimney stove Please ensure sufficient ventilation of the room Never close air supply openings or convection shafts of the stove The fire chamber door of a stove operating independently of ambient a...

Page 6: ...ase 8 Outer Case 10 Outer Case 6 Active Flue CEILING RING RUBBER DEKTITE FLASHING 8 Flue 6 Active Flue Fireplace outlet 8 Flue 3 1 Installing flue kit Ensure flue is installed as per Australian standa...

Page 7: ...must be a minimum distance of 3 meters from any higher section of roof 40 cm 40 cm 40 cm 3 m 90 cm 3 m 90 cm 90 cm 40 cm 40 cm 40 cm 3 m 90 cm 3 m 90 cm 90 cm The top of the flue must be 9000mm above...

Page 8: ...th non combustible material laid directly onto the concrete Joist Insulative board 9mm non combustible finish Non combustible finish eg tiles Concrete Combustible floor eg timber Joist Insulative boar...

Page 9: ...tible floor eg timber Combustible floor eg Timber Floor protector 800mm 800mm 100mm 200mm 200mm Non combustible finish eg tiles Concrete Combustible floor eg timber Combustible floor eg Timber Floor p...

Page 10: ...directly outwards with a combustion air conduit type FC41x or to the air channel of an air exhaust chimney LAS type FC51x The pressure loss of the combustion air conduit may not be higher than 3 Pa W...

Page 11: ...emostones Top view Top view Lockable door Wooden drawer For fire protection requirements each element that can be used as a heating box or storage space e g for the storage of flammable materials such...

Page 12: ...mpact on the function of pace makers and implanted defibrillators As a person concerned you should keep a sufficient distance to such magnets Please warn other people wearing such devices before they...

Page 13: ...s to start or rekindle the fire Do not use flammable liquids or aerosols in the vicinity of the fireplace when operating Do not store fuel within prescribed installation clearance distances The use of...

Page 14: ...for determination of Power Output and Efficiency and AS NZS 4013 2014 for Flue Gas Emission using hardwood fuel ISSUE DATE 23 04 2015 INVESTIGATING OFFICER Steve Marland RESULTS The appliance particul...