background image

Installation Instructions 

Model Number 1027-00 

 
 

(877) 867-2312

   

   

www.oberonwireless.com 

P/N 1411 –  Rev. 12/08/06

 

Oberon, Inc.  

  1315 South Allen Street  

  State College, PA 16801 

Copyright 2006

 

 

Figure 4 - 

Wall installation.

 

 

Assembly Components: 
- Ceiling enclosure Model 1027-00 assembly – 1 each 
- #8 - 32 screw – 4 each  
- Decorative screw covers – 4 each 
- Mounting hole legend – 1 each 
- Keys for access door lock – 2 each 
- Fire Block Foam – 1 each 
 

If any of these items are missing, contact your Oberon representative. 
 
Find a flat work surface to assemble 
the 

ceiling enclosure

access point

 

and 

antenna(s)

 prior to mounting in 

ceiling. 
 
Step 1 – 

Remove the metal hole 

cover(s) and install clamp 
connector(s). Use two clamp 
connectors if both power and data 
lines are to be installed. If only a data 
line is required (when using power 
over Ethernet), only one clamp 
connector will be required (Reference 

Figure 1

).

 

 
 
 
 
 
 
Step 2 

– 

A mounting plate is provided that supports most commonly 

used access points. Install the access point in the enclosure by 
attaching per the manufacturers instructions (Reference 

Figure 2

).  

 
For specific hole locations for various manufacturers access points, 
reference the mounting plate legend provided with the enclosure. 

 

 
Step 3 – If applicable, install the antenna(s) per the instructions 
included with optional antenna kit. After installation, connect the 

RF 

coax

 cable from the 

antenna

 to the 

access point

 
The assembled unit is now ready for wall or ceiling installation. 
 
 
 
 
 
 

 
 

Page 2 

 

Step 4 – 

To prepare the wall/ceiling for installation, cut a 

14" X 14" square hole in the gypsum board (Reference 

Figure 3

). The hole should be located centrally between 

two adjacent studs/joists. There must be a minimum of 
4" of free space available behind the wall to allow for 
clearance of the enclosure. 

 

Figure 3 - 

Prepare wall or ceiling by cutting 14" X 14" opening.

 

 
Note: Take proper safety precautions as many 
wall/ceiling areas may have electrical or plumbing 
located behind them.

 

 

 

Figure 1 - 

Cable clamp installation.

 

WALL MOUNTING:

 

Step 5 – 

To install the enclosure in the wall, bring the data 

and, if required power lines into the enclosure through the 
cable clamps. 
 
Position the enclosure so that the mounting holes are centrally 
located with the studs (Reference 

Figure 4

). 

 
For metal studs, use #10 sheet metal screws (or, for wood 
studs, use #10 wood screws). The screws should be a 
minimum of 1" in length. 
 
Securely tighten the screws, being sure that the screw is 
inserted directly into the stud*. 
 
*NOTE: Alternatively, if no studs are available for mounting, drywall anchors may be used.

 

 
CEILING MOUNTING: 

Step 6 – Run the data and power cable (if required) through the conduit connectors located on sides of the 

access point 

enclosure

.  In order to maintain a separation of signal and power, install the data and power cables through opposite sides of 

the enclosure utilizing the two knock-outs provided. Insert foam into the conduit connector and pull the data cable through far 
enough to allow attachment to the access point (8" - 10"). Carefully tighten conduit connector around fire block foam just 
enough to fill in gaps around cable. Be careful not to over tighten and crush the data cable(s), as this can affect cable 
performance. 
 

Position the enclosure so that the mounting holes are centrally located with the joists (Reference 

Figure 5

). 

 

Figure 2 - 

Install access point.

 

 
For metal joists, use #10 sheet metal screws (or, for wood joists, use #10 wood screws). The screws should be a minimum of 
2" in length. 

 
 
Page 3

Reviews: