3.INSTALLATION AND CONNECTION

8

3.4 Swimming Pool Heat Pumps Plumbing 

Location: Connect the unit in the pool pump discharge (return) line downstream of all filter 
and pool pumps, and upstream of any chlorinators, ozonators or chemical pumps.

Standard model have slip glue fittings which accept  32mm or 50 mm PVC pipe for 
connection to the pool or spa filtration piping. By using a 50 NB to 40NB you can plumb 40NB 

Give serious consideration to adding a quick coupler fitting at the unit inlet and outlet to allow 
easy draining of unit for winterizing and to provide easier access should servicing be 
required. 

Condensation: Since the Heat pump cools down the air about 4 -5

, water may condense on 

the fins of the horseshoe shaped evaporator. If the relative humidity is very high, this could 
be as much as several litres an hour. The water will run down the fins into the basepan and 
drain out through the barbed plastic condensation drain fitting on the side of the basepan. 
This fitting is designed to accept 20mm clear vinyl tubing which can be pushed on by hand 
and run to a suitable drain. It is easy to mistake the condensation for a water leak inside the 
unit. 

NB: A quick way to verify that the water is condensation is to shut off the unit  and keep the 
pool pump running. If the water stops running out of the basepan, it is condensation. AN 
EVEN QUICKER WAY IS to TEST THE DRAIN WATER FOR CHLORINE - if the is no chlorine 
present, then it's condensation. 

To  pool

From pump

PVC COUPLER
RECOMMENDED(Provided)

CONDENSATION
DRAIN
BARB FTG

The Swimming Pool Heat Pumps exclusive rated flow titanium heat exchanger requires no 
special plumbing arrangements except bypass(please set the flow rate according to the 
nameplate). The water pressure drop is less than 10kPa  at max. Flow rate. Since there is no 
residual heat or flame Temperatures, The unit does not need copper heat sink piping. PVC  
pipe can be run straight into the unit.

7

3.INSTALLATION AND CONNECTION

The unit will perform well in any outdoor location provided that the following three factors are 
presented: 

1. Fresh Air - 2. Electricity - 3. Pool filter piping 

The unit may be installed virtually anywhere outdoors. For indoor pools please consult the 
supplier. Unlike a gas heater, it has no draft or pilot light problem in a windy area. 

DO NOT place the unit in an enclosed area with a limited air volume, where the units
discharge air will be re-circulated. 
DO NOT place the unit to shrubs which can block air inlet. These locations deny the unit of a 
continuous source of fresh air which reduces it efficiency and may prevent adequate heat 
delivery.

3.2 Swimming Pool Heat Pumps Location

Normally, the pool heat pump is  installed within 7.5 metres of the pool. The longer  the 
distance from the pool, the greater the heat loss from the piping. For the most part ,the piping 
is buried. Therefore, the  heat loss is minimal for runs of up to15 meters(15 meters to and from 
the pump = 30 meters  total), unless the ground is wet or the water table is high. A very rough 
estimate of heat loss per 30 meters  is 0.6 kW-hour,(2000BTU) for every 5 

 difference in 

temperature between the pool water and the ground surrounding the pipe, which translates to 
about 3% to 5% increase in run time.

3.3 How Close To Your Pool? 

Air inlet

Air outlet

30

0m

m

700

mm

30

0m

m

5

0

0

m

m

700

mm

Summary of Contents for OASIS Ci 21

Page 1: ...SWIMMING POOL HEAT PUMP UNIT Installation Instruction Manual...

Page 2: ......

Page 3: ...Electrical Wiring 3 6 Initial Start up of the Unit 4 Operation and Use 4 1 4 2 4 3 4 4 5 Maintenance and Inspection 6 Appendix Installation illustration Swimming Pool Heat Pumps Location Color screen...

Page 4: ...cording to the recommended time and frequency as stated in this manual Use genuine standard spare parts only Failure to comply with these recommendations will invalidate the warranty Swimming Pool Hea...

Page 5: ...nnection Water Flow Volume Water Pressure Drop max Unit Net Dimensions L W H Unit Ship Dimensions L W H Net Weight Shipping Weight kW Btu h kW Btu h kW A W RPM dB A mm 3 m h kPa mm mm kg kg Nominal He...

Page 6: ...Dimensions L W H Net Weight Shipping Weight kW Btu h kW Btu h kW A W RPM dB A mm 3 m h kPa mm mm kg kg Nominal Heating Capacity By 50Hz Range KW A OASIS Ci 17 11 5 39100 4 6 19 5 15640 66300 0 37 3 94...

Page 7: ...Pool Heat Pump Unit OASIS Ci 10 unit mm unit mm Water inlet 40 Water outlet 40 350 100 1051 767 435 630 410 396 447 430 868 1163 470 815 Water inlet 40 Water outlet 40 A 100 2 SPECIFICATION 4 OASIS Ci...

Page 8: ...2 SPECIFICATION 5 2 2 The dimensions for Swimming Pool Heat Pump Unit Water inlet 40 Water outlet 40 470 100 OASIS Ci 21 OASIS Ci 25 unit mm 1163 1275 790 430 470 447...

Page 9: ...time 1 Open valve and charge water 2 Make sure that the pump and the water in pipe have been filled with water 3 Close the valve and start the unit ATTN It is necessary that the water in pipe is highe...

Page 10: ...us source of fresh air which reduces it efficiency and may prevent adequate heat delivery 3 2 Swimming Pool Heat Pumps Location Normally the pool heat pump is installed within 7 5 metres of the pool T...

Page 11: ...o the basepan and drain out through the barbed plastic condensation drain fitting on the side of the basepan This fitting is designed to accept 20mm clear vinyl tubing which can be pushed on by hand a...

Page 12: ...me Delay The unit is equipped with a 3 minute built in solid state restart delay included to protect control circuit components and to eliminate restart cycling and contactor chatter This time delay w...

Page 13: ...n is green Click to turn on off silent function and to set timing Low speed function Click to view fault history Temp curve Silent setting Click to lock the screen Input 22 to unlock the screen by pre...

Page 14: ...s designed for single automatic mode or single thermal mode the mode can not be switched 1 Booting and shutdown In shutdown status click then the unit will be booted In booting status click then the u...

Page 15: ...utton interface displays as follows 3 Clock setting Click on the time Settings button interface displays as follows Note if the input format is not correct the wrong time will be saved by clicking con...

Page 16: ...start setting function Start green End gray Open red End gray Click this button to start or end timing end setting function Button color Timing star b tutton Timing on setting Timing end button Timin...

Page 17: ...ming setting as follows Click the silent setting button and the interface displays 4 1 The silent button Click the silent button the unit will enter the silent mode and interface displays as follows C...

Page 18: ...unuse the timing silent but if the unit is in timing silent mode it will exit silent timing immediately Click timing silent button and interface displays as follows Colur Use green Unused gray Used r...

Page 19: ...re record the main interface will display static if you check the failurerecord the main interface will displays static Failure record is in reverse order according to the happening time Press the Cle...

Page 20: ...6 2 The average power curve 2 6 1 Temperature recording curve is as follows Temperature curve automatically updates every one hour and the curve record can be stored for 60 days Start from the latest...

Page 21: ...heck or change the temp Sensor Check or change the temp Sensor Check or change the temp Sensor Check the pressure switch and cold circuit Check or change the temp Sensor Check the pressure switch and...

Page 22: ...g voltage check requency conversion board hardware Check whether current return wires connected motor Check and adjust the current measurement Check the input voltage measurement Check the input volta...

Page 23: ...Default Refrigeration target temperature set point Heating the target temperature set point Automatic target temerature set point 4 OPERATION AND USE AC L OUT1 OUT2 OUT3 AC N OUT4 OUT5 PC1002 GND GND...

Page 24: ...0 230VAC Low speed of fan output 220 230VAC Live wire input 220 230VAC Neutral wire input 220 230VAC Emergency switch input Water flow switch input System low pressure input System high pressure input...

Page 25: ...erve energy The operation pressure of the refrigerant system should only be serviced by a certified technician Discharge all water in the water pump and water system so that freezing of the water in t...

Page 26: ...andled separately from domestic waste must be taken to a recycling centre for electric and electronic devices or handed back to the dealer when purchasing an equivalent appliance 6 Directive 2002 95 E...

Page 27: ...page protector Signal line 2 n 0 5mm Nameplate maximum current Earth line No more than 10A 20A 32A 40A 40A 63A 80A 100A 125A 160A 225A 250A 280A 2 1 5mm 2 2 5mm 2 4mm 2 6mm 2 10mm 2 16mm 2 mm 25 2 mm...

Page 28: ...Model and code OASIS Ci 10 A 6 APPENDIX 25 6 3 Explosive view of the unit...

Page 29: ...Pipe Needle reducing straight way reducing straight way Filter pressure switch pressure switch check valve 4 way Valve and fittings Electronic Expansion Valve electronic box compressor right panel flo...

Page 30: ...27 6 APPENDIX Model and code OASIS Ci 13 A...

Page 31: ...ure sensor Needle Needle Filter pressure switch pressure switch 4 way Valve and fittings Electronic Expansion Valve electronic box compressor right panel flow switch top cover heat exchanger Electrica...

Page 32: ...29 Model and code OASIS Ci 17 6 APPENDIX A...

Page 33: ...le T Pipe Colorful display reducing straight way Chassis Filter pressure switch pressure switch check valve 4 way Valve and fittings Electronic Expansion Valve electronic box compressor right panel fl...

Page 34: ...31 Model and code OASIS Ci 21 1 2 3 4 6 5 8 7 10 9 11 14 12 13 15 16 17 18 19 21 20 22 23 25 24 26 27 29 28 30 31 32 33 34 35 36 37 38 6 APPENDIX...

Page 35: ...heck valve fluid reservoir Electric box lining board Front Plate Colorful display fan protection net Fan Guard Fan Blade back protection net fan motor heat exchanger Fan Motor Support Supporting Plate...

Page 36: ...33 Model and code OASIS Ci 25T 6 APPENDIX 44 45 46 1 2 3 4 6 5 8 7 10 9 11 15 12 13 16 17 18 19 21 20 23 25 24 26 28 31 29 32 33 34 14 22 27 30 35 36 37 38 39 40 41 42 43...

Page 37: ...p Low p W Check valve Junction e v Pressure sensor T C Fluid reservoir I Electric box lining board b b Terminal Terminal Terminal plate Three phase filter ZL10 V3 Three phase ac monitor Front late Co...

Page 38: ...Note...

Page 39: ......

Page 40: ...Code 20170818 0002...

Reviews: