4.OPERATION AND USE
4.OPERATION AND USE
(6) Temperature curve
In the main interface, click the curve display button,
interface displays as follows:
6-2 The average power curve
2.6.1 Temperature recording curve is as follows:
Temperature curve automatically updates every one hour,
and the curve record can be stored for 60 days;
Start from the latest curve saved time, if power is off and
curve data collecting time is less than one hour, the data
in this period will not be saved;
4.3 Parameter list and breakdown table
(1) Electronic control fault table
Low temperature protection
Can be judged according to the remote controller failure code and
troubleshooting
Protect/fault
Standby
Normal boot
Amibent Temp. Sensor Fault
Outlet Temp. Sensor Fault
Coil Temp. Sensor Fault
Secondary A
nti-freezing P
rot.
Anti-freezing Prot
Suction Temp. Sensor Fault
Low Pressure Prot.
Flow Switch Prot.
Inlet and outlet temp. too big
Discharge Temp. Sensor
Fault
High Pressure Prot.
Exhaust Air over Temp Prot.
Comp. Overcurrent Prot.
Communication Fault
Primary Anti-freezing Prot.
Fault
display
Non
Non
P01
P02
P04
P05
P07
E02
E07
E03
E29
E06
P081
Non
E051
E08
E19
E01
P082
Reason
Elimination methods
Antifreeze Temp. Sensor Fault
Waterway Anti-freezing Prot.
EC fan feedback Fault
P09
E05
F051
Check the wire connection between
remote wire controller and main board
Check whether the system of the compressor
running normally
Check whether the system of the compressor
running normally
Check the pipe water flow and whether
water system is jammed or not
Check the pipe water flow and whether
water system is jammed or not
Check the pipe water flow and water pump
Check or change the temp. Sensor
Check or change the temp. Sensor
Check or change the temp. Sensor
Check or change the temp. Sensor
Check or change the temp. Sensor
Check the pressure switch and cold circuit
Check or change the temp. Sensor
Check the pressure switch and cold circuit
check and replace this temp sensor
Check whether fan motor is broken or locked
or not
Inlet Temp. Sensor Fault
PP
Pressure sensor Fault
The temp. Sensor is broken
or short circuit
The temp. Sensor is broken
or short circuit
The temp. Sensor is broken
or short circuit
The temp. Sensor is broken
or short circuit
The environment temp. is low
The ambient temp. Is low
Water flow is not enough
and low differential pressure
Water flow is not enough
The temp. Sensor is broken
or short circuit
Low pressure1 protection
No water/little water in
water system
The temp. Sensor is broken
or short circuit
The high-preesure switch is
broken
The compressor is overload
The ambient temp. Is low
Communicat ion failure between
wire controller and mainboard
The compressor is overload
antifreeze temp sensor is
broken or short circuited
water temp.or ambient temp.
is too low
There is something wrong with fan
motor and fan motor stops running
The pressure Sensor is broken
F031
Fan Motor1 Fault
1. Motor is in locked-rotor state
2.The wire connection between
DC-fan motor module and fan
motor is in bad contact
1.Change a new fan motor
2.Check the wire connection and make sure
they are in good contact
Check or change the pressure Sensor
or pressure
Summary of Contents for OASIS Ci 10
Page 1: ...SWIMMING POOL HEAT PUMP UNIT Installation Instruction Manual ...
Page 2: ......
Page 28: ...Model and code OASIS Ci 10 A 6 APPENDIX 25 6 3 Explosive view of the unit ...
Page 30: ...27 6 APPENDIX Model and code OASIS Ci 13 A ...
Page 32: ...29 Model and code OASIS Ci 17 6 APPENDIX A ...
Page 38: ...Note ...
Page 39: ......
Page 40: ...Code 20170818 0002 ...