6.APPENDIX
(2) Cable specification
1. Single phase unit
Nameplate
maximum
current
Phase line
Earth line
MCB
Creepage protector
Signal line
No more
than 10A
2
×
1.5mm
2
1.5mm
2
20A
30mA less than 0.1 sec
n
×
0.5mm2
10~16A
2
×
2.5mm
2
2.5mm
2
32A
30mA less than 0.1 sec
16~25A
2
×
4mm
2
4mm
2
40A
30mA less than 0.1 sec
25~32A
2
×
6mm
2
6mm
2
40A
30mA less than 0.1 sec
32~40A
2
×
10mm
2
10mm
2
63A
30mA less than 0.1 sec
40 ~63A
2
×
16mm
2
16mm
2
80A
30mA less than 0.1 sec
63~75A
2
×
25mm
2
25mm
2
100A
30mA less than 0.1 sec
75~101A
2
×
25mm
2
25mm
2
125A
30mA less than 0.1 sec
101~123A
2
×
35mm
2
35mm
2
160A
30mA less than 0.1 sec
123~148A
2
×
50mm
2
50mm
2
225A
30mA less than 0.1 sec
148~186A
2
×
70mm
2
70mm
2
250A
30mA less than 0.1 sec
186~224A
2
×
95mm
2
95mm
2
280A
30mA less than 0.1 sec
2. Three phase unit
Nameplate
maximum
current
Phase line
Earth line
MCB
Creepage protector
Signal line
No more
than 10A
3
×
1.5mm
2
1.5mm
2
20A
30mA less than 0.1 sec
n
×
0.5mm2
10~16A
3
×
2.5mm
2
2.5mm
2
32A
30mA less than 0.1 sec
16~25A
3
×
4mm
2
4mm
2
40A
30mA less than 0.1 sec
25~32A
3
×
6mm
2
6mm
2
40A
30mA less than 0.1 sec
32~40A
3
×
10mm
2
10mm
2
63A
30mA less than 0.1 sec
40 ~63A
3
×
16mm
2
16mm
2
80A
30mA less than 0.1 sec
63~75A
3
×
25mm
2
25mm
2
100A
30mA less than 0.1 sec
75~101A
3
×
25mm
2
25mm
2
125A
30mA less than 0.1 sec
101~123A
3
×
35mm
2
35mm
2
160A
30mA less than 0.1 sec
123~148A
3
×
50mm
2
50mm
2
225A
30mA less than 0.1 sec
148~186A
3
×
70mm
2
70mm
2
250A
30mA less than 0.1 sec
186~224A
3
×
95mm
2
95mm
2
280A
30mA less than 0.1 sec
When the unit will be installed at outdoor, please use the cable which can against UV.