3.5 Swimming Pool Heat Pumps Electrical Wiring 

NOTE: Although the unit heat exchanger is electrically isolated from the rest of the unit, it 
simply prevents the flow of electricity to or from the pool water. Grounding the unit is still 
required to protect you against short circuits inside the unit. Bonding is also required.

3.INSTALLATION AND  CONNECTION

3.6 Initial startup of the Unit  

NOTE- In order for the unit to heat the pool or spa, the filter pump must be running to 
circulate water through the heat exchanger.

Start up Procedure - After installation is completed, you should follow these steps: 
1. Turn on your filter pump. Check for water leaks and verify flow to and from the pool.
2. Turn on the electrical power supply to the unit, then press the key ON/OFF of wire  
controller, It should start in  several seconds.
3. After running a few minutes make sure the air leaving the top(side) of the unit is 
cooler(Between 5-10 

)

4. With the unit operating turn the filter pump off. The unit should also turn off automatically, 
5. Allow the unit and pool pump to run 24 hours per day until desired pool water emperature is 
reached. When the water-in temperature reach setting, The unit just shuts off. The unit  will 
now automatically restart (as long as your pool pump is running)when the pool temperature 
drops more than 2

below set temperature.  

Time Delay- The unit is equipped with a 3 minute built-in solid state restart delay included to 
protect control circuit components and to eliminate restart cycling and contactor chatter. 
This time delay will automatically restart the unit approximately 3 minutes after each control 
circuit interruption. Even a brief power interruption will activate the solid state 3 minute 
restart delay and prevent the unit from starting until the 5 minute countdown is completed. 
Power interruptions during the delay period will have no effect on the 3 minute countdown. 

11

The unit has a separate molded-in junction box with a standard electrical conduit nipple 
already in place. Just remove the screws and the front panel, feed your supply lines in 
through the conduit nipple and wire-nut the electric supply wires to the three connections  
already in the junction box (four connections  if three phase). To complete electrical hookup, 
connect Heat Pump by electrical conduit, UF cable or other suitable means as specified (as 
permitted by local electrical authorities) to a dedicated AC power supply branch circuit 
equipped with the proper circuit breaker, disconnect or time delay fuse protection. 

Disconnect - A disconnect means (circuit breaker , fused or un-fused switch) should be 
located within sight of and readily accessible from the unit, This is common practice on 
commercial and residential air conditioners and heat pumps. It prevents remotely-energizing 
unattended equipment and permits turning off power at the unit while the unit is being 
serviced. 

All manuals and user guides at all-guides.com

Summary of Contents for ELITE AC9

Page 1: ...SWIMMING POOL HEAT PUMP UNIT Installation Instruction Manual All manuals and user guides at all guides com a l l g u i d e s c o m...

Page 2: ...e to Your Pool 3 4 Swimming Pool Heat Pumps Plumbing 3 5 Swimming Pool Heat Pumps Electrical Wiring 3 6 Initial Start up of the Unit 4 Usage and Operation 4 1 Function of the controller 4 2 Usage of t...

Page 3: ...ded time and frequency as stated in this manual Use genuine standard spare parts only Failure to comply with these recommendations will invalidate the warranty Swimming Pool Heat Pump Unit heats the s...

Page 4: ...T Heating capacity Heating Power Input Running Current Power Supply Compressor Quantity Compressor Fan Number Fan Power Input Fan Rotate Speed Fan Direction Noise Water Connection Water Flow Volume Wa...

Page 5: ...Input Running Current Power Supply Compressor Quantity Compressor Fan Number Fan Power Input Fan Rotate Speed Fan Direction Noise Water Connection Water Flow Volume Water Pressure Drop max Unit Net Di...

Page 6: ...ol Heat Pump Unit 2 SPECIFICATION 4 Oasis ELITE AC9 Oasis ELITEAC14 375 623 956 552 Water inlet 40 Water outlet 40 114 350 356 18 5 Oasis ELITE AH9 Oasis ELITEAH14 All manuals and user guides at all g...

Page 7: ...Oasis ELITEAC18 5 2 SPECIFICATION 1116 886 500 790 460 511 400 116 Water inlet 40 Water outlet 40 Oasis ELITEAH18 All manuals and user guides at all guides com...

Page 8: ...l when handle with the front plate in case of damage 2 During this process please attention to protect the wire between the button on the front plate and electrical box Pull up the front plate Move fo...

Page 9: ...albox and fix it at the place A as showed in the first image below After fixing it at A draw it out from the bottom of the heat pump as showed in the second image A Power cord Power cord 2 4 How the p...

Page 10: ...rge water 2 Make sure that the pump and the water in pipe have been filled with water 3 Close the valve and start the unit ATTN It is necessary that the water in pipe is higher than the pool surface 3...

Page 11: ...adequate heat delivery 3 2 Swimming Pool Heat Pumps Location Normally the pool heat pump is installed within 7 5 metres of the pool The longer the distance from the pool the greater the heat loss from...

Page 12: ...condensation drain fitting on the side of the basepan This fitting is designed to accept 20mm clear vinyl tubing which can be pushed on by hand and run to a suitable drain It is easy to mistake the co...

Page 13: ...ipped with a 3 minute built in solid state restart delay included to protect control circuit components and to eliminate restart cycling and contactor chatter This time delay will automatically restar...

Page 14: ...On off Mode Up Press this button can start up or shut down the unit cancel the current operation or back to the upper interface Press this button can switch modes or save parameter setting Press this...

Page 15: ...ter It is showed when the AUX display area gives the outlet water temperature measured value Minute It is showed when the main display area gives minute value Centigrade It is showed when the main AUX...

Page 16: ...DE SET TEMP IN C TEMP OUT MODE SET TEMP OUT MODE SET TEMP OUT MODE SET TEMP OUT MODE SET A TEMP OUT MODE SET TEMP OUT MODE SET MODE SET MODE SET MODE SET MODE SET MODE SET In the off interface press f...

Page 17: ...value or press to decrease value and press to save setting Press can not save setting parameter and back to main interface Attention If there is no operation for 5s system will remember parameter set...

Page 18: ...N C TEMP OUT MODE SET Flashing Press TEMP IN C TEMP OUT MODE SET Press or TEMP IN C TEMP OUT MODE SET Press to save hour value setting TEMP IN C TEMP OUT MODE SET Press or TEMP IN C TEMP OUT MODE SET...

Page 19: ...Attention 1 If there is no operation for 5s system will remember clock setting and back to the main interface 2 By pressing till the off flashing you can set the timer off without timer on TEMP IN C...

Page 20: ...MODE SET ON OFF TEMP IN C TEMP OUT MODE SET ON OFF Press Press or TEMP IN C TEMP OUT MODE SET ON OFF TEMP IN C TEMP OUT MODE SET Press ON OFF The timer on and off has been set Flashing Flashing Flashi...

Page 21: ...ON OFF The timer on off has been set Press for 2s TEMP IN C TEMP OUT MODE SET ON OFF ON is flashing TEMP IN C TEMP OUT MODE SET OFF The setting of timer on has been cancelled Press TEMP IN C TEMP OUT...

Page 22: ...nit is in alarming state the key lock can be removed automaticly TEMP IN C TEMP OUT MODE SET Hold on Locked TEMP IN C TEMP OUT MODE SET MODE SET 2 5 Malfunction display There will be malfunction code...

Page 23: ...aning Heating inlet target temp Adjustable Adjustable Adjustable 3 Parameter table Cooling inlet target temp Auto inlet target temp Remark Default 4 USAGE AND OPERATION All manuals and user guides at...

Page 24: ...n press the power button to turn it off then the light will also be off 4 2 When the light of power button is out it shows that the unit is stand by You can press the power button to turn it on then t...

Page 25: ...ure of the refrigerant system should only be serviced by a certified technician Discharge all water in the water pump and water system so that freezing of the water in the pump or water system does no...

Page 26: ...open or shortcircuit The water outlet temp sensor is open or shortcircuit The pipe temp sensor is open or short circuit The evaporator temp Sensor is open or shortcircuit The exhaust pressure ishigh...

Page 27: ...High speed of fan motor 220 230VAC OUT3 OUT1 No Symbol Meaning 4way valve 220 230VAC Compressor of system1 220 230VAC NET GND 12V Wire controller DI01 GND On Off Switch input no use No use Flow switch...

Page 28: ...waste must be taken to a recycling centre for electric and electronic devices or handed back to the dealer when purchasing an equivalent appliance 6 Directive 2002 95 EC RoHs This product is compliant...

Page 29: ...ector Signal line 2 n 0 5mm Nameplate maximum current Earth line No more than 10A 20A 32A 40A 40A 63A 80A 100A 125A 160A 225A 250A 280A 2 1 5mm 2 2 5mm 2 4mm 2 6mm 2 10mm 2 16mm 2 mm 25 2 mm 25 2 35mm...

Page 30: ...2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 28 29 30 31 34 27 32 Oasis ELITEAC9 6 APPENDIX 28 All manuals and user guides at all guides com...

Page 31: ...y 5 terminal Note 1 1 1 1 1 1 1 1 1 1 1 1 1 Code 2001 3605 32012 210303 40000 320033 32012 210288 32012 210297 3500 2701 32012 210284 3404 3301 32012 210290 32012 210300 32012 210302 32008 120037 2000...

Page 32: ...2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 28 29 30 31 32 34 27 33 OasisELITE AC14 6 APPENDIX 30 All manuals and user guides at all guides com...

Page 33: ...tactor Pc1001 intermediate relay 5 terminal Note 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Code 2001 3605 32012 210303 40000 320033 32012 210288 32012 210297 3500 2701 32012 210284 3404 3301 32012 210290 32012 2103...

Page 34: ...19 25 20 21 22 23 24 18 26 27 28 1 2 4 3 5 17 16 15 38 29 32 31 33 30 35 36 37 34 OasisELITE AC18 6 APPENDIX 32 8 6 7 9 13 10 12 11 14 All manuals and user guides at all guides com...

Page 35: ...210286 20000 360005 32012 210310 32009 120014 20000 220013 2000 2249 2000 2250 32009 210300 95005 310145 20000 220068 2004 1437 Part name needle valve filter pressure switch Electronic expansion valve...

Page 36: ...2 3 4 5 6 7 8 9 10 11 15 16 17 18 19 20 21 22 23 24 26 27 28 29 31 25 30 Oasis ELITEAH9 6 APPENDIX 34 12 13 14 All manuals and user guides at all guides com a l l g u i d e s c o m...

Page 37: ...erminal Note 1 1 1 1 1 1 1 1 1 1 1 Code 2001 3605 32012 210303 40000 320033 32012 210288 32012 210297 3500 2701 32012 210284 3404 3301 32012 210290 32012 210300 32012 210302 32008 120037 20000 360005...

Page 38: ...2 3 4 5 6 7 10 8 9 11 12 13 14 15 16 17 18 19 20 21 22 23 24 26 27 28 29 30 32 25 31 OasisELITEAH14 6 APPENDIX 36 All manuals and user guides at all guides com...

Page 39: ...rmediate relay 5 terminal Note 1 1 1 1 1 1 1 1 1 1 1 1 Code 2001 3605 32012 210303 40000 320033 32012 210288 32012 210297 3500 2701 32012 210284 3404 3301 32012 210290 32012 210300 32012 210302 32012...

Page 40: ...19 24 20 21 22 23 18 25 26 27 8 6 1 2 4 3 5 7 9 13 10 17 16 12 11 15 14 37 28 31 30 32 29 34 35 36 33 OasisELITEAH18 6 APPENDIX 38 All manuals and user guides at all guides com...

Page 41: ...0005 32012 210310 32009 120014 20000 220013 2000 2249 2000 2250 32009 210300 95005 310145 20000 220068 20000 140150 Part name filter pressure switch Electronic expansion valve pressure switch Clapboar...

Page 42: ...NOTE All manuals and user guides at all guides com...

Page 43: ...All manuals and user guides at all guides com...

Page 44: ...Code 20150616 0001 All manuals and user guides at all guides com...

Reviews: