KIT CONTENTS

Qty Description
1 NGC-UIT2-EX
12 

6/32 in Kep nuts (locking nuts)

5-ft 9-pin RS-232 (Null Modem) cable

Provide Suitable Panel Enclosure, and Determine Locations for NGC-UIT2-EX Assembly in Panel

1.  Provide suitable panel enclosure

To protect its electronic components, the nVent NGC-UIT2-EX 

must be mounted in a panel with a minimum IP32 (Type 1) 

enclosure for non-hazardous locations. An IP54 (Type 4) or better 

ATEX/IECEx enclosure is required for Hazardous locations. An 

IP52 (Type 12) or better enclosure is recommended. The NGC-

UIT2-EX assembly comes with a sealing gasket and hardware to 

mount the enclosure.
Note: The NGC-UIT2-EX is designed for operation in ambient 

temperatures from –40°C to 60°C (–40°F to 140°F). If the ambient 

temperature is outside this range, a space heater and/or cooling 

fan will be required in the panel.

2.  Determine locations for the NGC-UIT2-EX assembly in the 

electrical panel
The NGC-UIT2-EX should be located on the front of the panel near 

eye level (for convenient viewing). The NGC-UIT2-EX assembly is 

an electronic unit and must not be located where it will be exposed 

to strong magnetic fields or excessive vibration.
Conditions of Safe Use

This equipment must be installed in a hazardous location  

classified cabinet or panel rated as follows: 

•  Internal and external ambient of: -40ºC to +60ºC

•  Minimum ingress protection rating of IP54 

•  ATEX / IECEx: Zone 2 or better

•  US / CAN: Class I Div 2 or better 

•  Can only be opened with the use of a tool

Do not connect/disconnect equipment unless power has 

been switched off or the area is known to be non-hazardous.
Ne débranchez pas l'équipement que l'alimentation est 

coupée ou que la zone est connue pour être non dangereux.

•   Use appropriately classified Limited Power Source, or 

LPS. Follow all applicable wiring codes and regulations.

•   Peripheral equipment must be suitable for the location in 

which it is used.

There are no non-incendive circuits or non-incendive field 

wiring within or associated with the unit.

WARNING:

IMPORTANT:

Network Connection

Local/ Remote Port

nVent RAYCHEM RS-232/RS-485 ports may be used to communicate with host computers  

(nVent RAYCHEM Supervisor Software) or DCS

Local RS-232

A non-isolated, 9 pin D sub male

Remote RS-485 #2

2-wire isolated, 9 pin D sub male

Data Rate

9600 to 57600 baud.

Maximum cable length

For nVent RAYCHEM RS-485 not to exceed 1200 m (4000 ft). Cable to be shielded twisted pair.

Field Port 

RS-485, 2-wire isolated. Used to communicate with external devices, such as nVent RAYCHEM NGC-30-CRM and 

RMM2. Maximum cable length not to exceed 1200 m (4000 ft). Cable to be shielded twisted pair.

Field RS-485 #1

2-wire isolated, 9 pin D sub male

Data Rate

To 9600 baud

LAN

10/100 Base-T Ethernet port with Link and Activity Status LEDs

USB Ports

USB 2.0 Host port Type A receptacle (X2)

Summary of Contents for Raychem NGC-UIT2-EX

Page 1: ...t alarm light 120 or 230 Vac Note Equivalent parts may be used CERTIFICATIONS APPROVALS NEMA 4X IP65 protection on front panel FCC Part15 Subpart B ICES 003 Class A ETL 4000758 Conforms to ANSI UL Std...

Page 2: ...it will be exposed to strong magnetic fields or excessive vibration Conditions of Safe Use This equipment must be installed in a hazardous location classified cabinet or panel rated as follows Intern...

Page 3: ...izontal surface 5 Mount the user interface assembly onto the panel door Place the NGC UIT2 EX assembly in position the twelve studs go through the twelve holes on the NGC UIT2 EX assembly mounting pla...

Page 4: ...n 88 39 mm 3 480 in 4 8 3 m m 0 1 9 0 i n X 1 2 71 48 mm 2 814 in 71 48 mm 2 814 in 71 48 mm 2 814 in Panel Cut Out Area Top of Display Drawing NOT TO SCALE Drawing NOT TO SCALE 11 1 mm 0 437 in 88 39...

Page 5: ...5 2 Debug Port not used Ethernet USB device port not used Open Collector Outputs RS 485 1 Side view RS 232 RS 485 1 Termination RS 485 2 Termination Side view RS 485 not used CAN not used Power Reset...

Page 6: ...Vdc we have used this voltage to also power the NGC UIT2 EX As a result the recommend alarm relays and lights detailed in the Additional Materials are rated for 12 Vdc Provision shall be made externa...

Page 7: ...l the two 9 pin D SUB to 10 pin terminal block on a DIN rail inside the panel enclosure Note These should be placed were the Serial cable from the bottom of the NGC UIT2 EX mounted on the panel door c...

Page 8: ...Comments Pull down As shipped default RS 485 network signal is forced to a determinate state when idle RS 485 network signal is not forced to a determinate state when idle One device typically this N...