DESCRIPTION
These instructions will guide the installer on how to convert
from nVent RAYCHEM NGC-UIT-OUT to
nVent RAYCHEM NGC-UIT2-HAZ and are intended only for
personnel experienced in panel construction.
TOOLS REQUIRED
• Masking tape
• #7 (.201) drill bit
• 11/32 in. Nut Driver
• 3/8 in. drill bit
• Metal file
• In-line torque wrench with 3/8 socket
• Zipcut Disc for cutting Stainless Steel panels
(5.0 in x 0.45 in x 7/8 in)
Note: the Zipcut disc is used to cut the opening in the door for the
NGC-UIT2-HAZ display. Other cutting type tools can be used.
The NGC-UIT2-HAZ is an electronic unit.
During installation, take the following
precautions to avoid damage to its
electronic components.
• Handle with care to avoid mechanical
damage.
• Keep electronics dry.
• Avoid exposure to static electricity.
• Avoid contamination with metal filings,
liquids, or other foreign matter.
• Take care to protect the user interface
board on the enclosure door.
• Use agency-approved conduit bushings,
adapters, and cable glands to keep the
enclosure protected from dust and fluids.
WARNING:
General
Area of Use
Nonhazardous or hazardous locations,
indoors or outdoors (Type 4X, IP66)
Supply Voltage
90–240 Vac
Operating Temperature
32°F to 140°F (0°C to 60°C) without
space heater
–22°F to 140°F (–30°C to 60°C) with
space heater
Min. Storage Temperature –40°F to 149°F (–40°C to 65°C)
Dimensions
13.43 in W X 10.87 in H X 3.63 in D
(341 mm W X 276 mm H X 92 mm D)
Alarm Outputs
Via External Alarm Module Three relay outputs, Form C contacts,
switching module up to 250 Vac/5 A
User to Drive External
Relays
Relays may be assigned for alarm
outputs
LCD Display
Display
LCD is a 10.4 in SVGA, color TFT
transflective device with integral LED
backlight
Network Connection
Local/Remote Port
RS-232/RS-485 (via external converter)
ports may be used to communicate
with host computer (RAYCHEM
Supervisor software) or DCS
Local RS-232
A non-isolated, 9 pin D sub male
Remote RS-232 to RS-485
using external converter #2
2 wire isolated,, Using a standard 9 pin
D sub female to 9 pin D sub male cable.
Data Rate
9600 to 57600 baud
Maximum cable length
For RS-485 not to exceed 4000 ft
(1200 m). Cable to be shielded
twisted pair.
Field Port
RS-232/RS-485 (via external converter)
port used to communicate with external
devices, such as NGC-30-CRM, CRMs
and RMM2.
Field RS-232 to RS-485
using external converter #1
2 wire isolated,, Using a standard 9 pin
D sub female to 9 pin D sub male cable.
Data Rate
9600
Maximum Cable Length
For RS-485 not to exceed 4000 ft
(1200 m). Cable to be shielded
twisted pair.
LAN
10/100 Base-T Ethernet port with Link
and Activity Status LEDs
NGC-UIT-OUT to NGC-UIT2-HAZ
CONVERSION INSTRUCTIONS