background image

50  |  nVent.com/ERICO 

NOTICE

Users are advised that the nVent ERICO System 

3000

 Lightning Protection System 

may not function to its full efficiency under ice or snow conditions or on chimneys or 
stacks emitting gasses or pollutants. For advice on temperature or corrosion concerns, 
please contact your local nVent ERICO Distributor.

When performing a 

3

–pole ground 

resistance test, it is essential that the probe 
is placed outside the sphere of influence of 
the ground electrode under test. 

To test the accuracy of the results and to 
ensure that the ground stakes are outside 
the spheres of influence, reposition the inner 
stake (probe) 

1

 meter in either direction and 

take a fresh measurement.

If there is a significant change in the reading 
(

30

%), you need to increase the distance 

between the ground rod under test, the inner 
stake (probe) and the outer stake (auxiliary 
ground) until the measured values remain 
fairly constant when repositioning the inner 
stake (probe).

MAINTENANCE RECORD

Date of 

Inspection

Lightning 

Event Counter 

Reading

Ground 

Resistance 

Readings

Check of 

Maintenance 

Points 

1

 

to 

11

Comments

Inspected 

by

1

2

3

Summary of Contents for ERICO System 3000

Page 1: ...nVent com ERICO 1 nVent ERICO System 3000 Installation Operation and Maintenance Manual...

Page 2: ...llation Operation and Maintenance Manual Due to ongoing research into the phenomena of lightning and lightning protection technology and product improvement nVent ERICO reserves the right to alter any...

Page 3: ...unding Systems 11 Bonding the Lightning Protection Ground to Other Service Grounds 11 Conductor to Grounding System Connection 12 Labelling 12 Ericore Downconductor 13 Downconductor Hauling 13 Penetra...

Page 4: ...for Long Lengths of Ericore Downconductor 35 Telecom Towers 35 Buildings 35 Proposed Ericore Lengths 35 Ericore Maximum Lengths 37 Installation Methods for Ericore Exceeding 70 m 37 Parallel Splicing...

Page 5: ...employs additional lightning parameters in its striking distance formulae namely electric field intensification factor and structure height and physical shape The formula in the CVM also takes into a...

Page 6: ...ance 4 Improper installation misuse misapplication or other failure to completely follow nVent ERICO s instructions and warnings may cause product malfunction property damage serious bodily injury and...

Page 7: ...LLATION Before installation perform following inspection Terminal s nVent ERICO Dynasphere terminals have not been dented The correct finial tip has been installed based on the overall height of the a...

Page 8: ...ith authorities having juristiction Available space location Natural soil conditions including resistivity moisture temperature and chemical content Location of underground services Power Communicatio...

Page 9: ...opper conductors are welded to the ground rods using Cadweld The copper tape or 2 0 copper conductor are encased in Ground Enhancement Material GEM25A Conductive Saddles Ericore Cable Inspection Well...

Page 10: ...tor Inspection Well Lower Termination Enclose in Weatherproofing Mastic Copper Ground Tape Typical lengths minimum of 5 m 17 ft Lengths are dependant upon soil resistivity reading 600 mm 24 in depth o...

Page 11: ...nd supplied when the existing soil mass has a high resistivity GEM25A can be used to increase the total surface area of grounding conductors thereby reducing the ground resistance impedance GEM25A req...

Page 12: ...system connection to the grounding system at the first available opportunity The practice of running nVent ERICO Ericore downconductor for long horizontal lengths at the ground level to reach a desig...

Page 13: ...its performance It is VERY IMPORTANT that when removing these tubes they are not removed with a knife or cut in any way as this will damage the outer layer of the termination e g It is suggested that...

Page 14: ...nated end hauled from the ground to the top of the structure Downconductor preterminated end on the inside of the drum DO NOT cut plastic cover over terminated downconductor as this may damage the ter...

Page 15: ...ssure seal etc use a standard professional method of protection Figure 8 Correct incorrect cable routing methods Routing The route taken by the downconductor is very important and must follow these ru...

Page 16: ...m 20 in is maintained Parallel routing with other services Minimum separation 2 m 80 in Try to isolate as much as possible from other services If the downconductor must cross other services ensure tha...

Page 17: ...t one turn If the downconductor is damaged during installation it is no longer usable and must be replaced Securing the Downconductor Securing of the downconductor not only provides a mechanical attac...

Page 18: ...ing to other structures such as angle iron i e radio towers structural beams etc use nVent CADDY brand of beam clamps and suitable cable clamps from nVent ERICO If the downconductor is to be routed ab...

Page 19: ...stributor Structure Bonding Braid To ensure that the upper end of the downconductor can be adequately electrically bonded to the structure a Structure Bonding Braid has been provided at the base of th...

Page 20: ...UST be secured with nVent ERICO brand of saddles to the mast at 1 m 40 in intervals max The mast in turn must be electrically bonded to the nearest conductive structural point In this case the structu...

Page 21: ...oncrete reinforcing Structural Steel Work To upper termination kit bonding braid or mast base Cadweld bolted or other suitable electrically bonded method To upper termination kit bonding braid or mast...

Page 22: ...ents salt or acid atmosphere Warning Do not install the nVent ERICO Dynasphere without installing the correct finial tip Ensure the air terminal is supplied with the finial tip secured in place There...

Page 23: ...ure 18 Mast Wind Loading nVent ERICO does not warrant the installation of the nVent ERICO System 3000 only the components All installations approved by nVent ERICO Engineering are listed in nVent ERIC...

Page 24: ...it point The maximum mast diameter that the inline coupling is able to clamp onto is 70 mm 2 in OD On both U bolt connectors and in line couplers the maximum torque is 55 kg cm 45 in lb Figure 18 Base...

Page 25: ...o suit the application The guying material is made up of light weight plastic coated fiberglass which is non conductive If a customized guy kit has been supplied then the actual guy length can be dete...

Page 26: ...60 from horizontal It is recommended that 8 mm in diameter stainless steel guying saddles are used for the base guy anchor points If these are to be anchored to a concrete surface then 6 mm in diamet...

Page 27: ...he lift before attempting it If the mast is to be raised by hand ensure that it can be safely and easily managed manually It is recommended that the use of a crane or other suitable equipment be used...

Page 28: ...lifting i e if the cable exits from the mast base it must be protected and not used as the pivot point for the mast Maintain a minimum bending radius of 500 mm 20 in The mast can be easily and safely...

Page 29: ...e structure bonding cable has been attached correctly The nVent ERICO Dynasphere terminal is NOT used as a slinging point When slinging the mast ensure that the slings or ropes can not foul the nVent...

Page 30: ...window for easy counter reading The Lightning Event Counter is a device for registering and recording the number of strikes that the nVent ERICO System 3000 has intercepted The nVent ERICO LECV is th...

Page 31: ...system is neglected or poorly implemented the pipes tanks scaffolds and catwalks may develop dangerous potential differences and generate sparks which can cause explosions Conventional Cable as the Do...

Page 32: ...nductors Using the Mast as a Downconductor A stainless steel mast system is the preferred method recommended by nVent ERICO for installation of the System 3000 with conventional conductor nVent ERICO...

Page 33: ...the nVent ERICO System 3000 to the structure nVent ERICO manufactures components to assemble this type of system with utility poles and other shorter free standing masts For these applications single...

Page 34: ...olves a long single length of Ericore cable additional measures may be needed to ensure that the voltage build up will not exceed the voltage withstand rating of the cable during a lightning strike Wh...

Page 35: ...stance The following examples give typical guidance TELECOM TOWERS Most towers would be less than 70 m 230 ft or so in height so that a single Ericore downconductor would suffice However where the tow...

Page 36: ...ay level at the proposed installation site A single length of nVent ERICO Ericore is acceptable No additional action is required Additional measures ae required Read on further in this section Figure...

Page 37: ...ethods to extend the length of Ericore 1 Parallel splicing use two Ericore cables in parallel with the Dual Terminal Adaptor kit that allows you to install two Ericore cables at the top of the mast Se...

Page 38: ...tightened with the provided bolt Each Ericore cable shall exit their respective inline couplers and be affixed to the mast assembly by stainless steel straps at the normal interval of at least every...

Page 39: ...see Figure 29 In some installations both lugs can be directly connected to a suitable conductive structural point but in some installations it will be more convenient to connect both lugs to a small...

Page 40: ...ands and Double Tape Layer 85 mm 3 in Inspection Well Downconductor lower termination bound in waterproofing mastic Ground Rod LECV LEC V LIGHTNING EVENT COUNTER YY MM DD 00 00 00 00 0 00 Hrs Set OK C...

Page 41: ...the grounding system Refer to the lower termination installation manual for more details The lower termination consists of many intricate steps that have to be followed precisely to assemble lower ter...

Page 42: ...n the cable and bring it safely to the grounding system Refer to the upper termination installation manual for more details The upper termination consists of many intricate steps that have to be follo...

Page 43: ...in height of the nVent ERICO Dynasphere 2 Inspect the nVent ERICO Dynasphere to ensure that it is not dented or physically damaged in any way Operation and Maintenance 3 Inspect the finial tip on top...

Page 44: ...stem then measure record in column 3 of ground resistance readings G At the lower termination of the downconductor disconnect the 2 5 mm2 12 AWG bonding wire from under the hose clamp H With a multime...

Page 45: ...tor Disconnected from Lightning Protection Ground Structure Bonding Cable Disconnected from Lightning Protection Ground Lightning Protection Grounding System To Upper Termination 2 5 mm2 12 AWG Wire T...

Page 46: ...ure Bonding Cable Disconnected from L P Ground LP Grounding System Figure 38 Grounding and downconductor continuity testing B C Disconnect the downconductor from the grounding system B If possible dis...

Page 47: ...downconductor continuity testing I H G At the lower termination of the downconductor disconnect the 2 5 mm2 12 AWG bonding wire from under the hose clamp G If possible measure the continuity between...

Page 48: ...able Disconnected from L P Ground LP Grounding System Figure 42 Grounding and downconductor continuity testing Figure 43 Grounding and downconductor continuity testing Reconnect the 2 5 mm2 12 AWG bon...

Page 49: ...orage real time display analysis report generation and system configuration 3 Point Fall of Potential measurement with manual or automatic frequency selection EST4630 Measures ground resistance 2 and...

Page 50: ...round electrode under test To test the accuracy of the results and to ensure that the ground stakes are outside the spheres of influence reposition the inner stake probe 1 meter in either direction an...

Page 51: ...tor to safely convey the lightning energy to ground while minimizing side flashing Diameter 36 mm 1 in Weight 1 2 kg m 13 oz ft FRP Mast Purpose designed Fiberglass Reinforced Plastic manufactured fro...

Page 52: ...Weight 0 36 kg 0 794 lb Terminal Lug Coupling The terminal lug coupling allows for connection of a conventional downconductor such as 25 mm x 3 mm copper tape bar to the Dynasphere See Upper Terminati...

Page 53: ...teel 316 Length 114 5 mm 4 in Thickness 1 2 mm in Fixing Hole Diameter 6 mm in Width 25 5 mm 1 in Stainless Steel Cable Tie Purpose designed cable ties for securing of Ericore downconductor to the mas...

Page 54: ...to the structure earth or has a substantial metallic mass Fastenings Bolts screws masonry anchors or other hardware used to secure anchors to the structure FRP Fiberglass Reinforced Plastic Insulated...

Page 55: ...nVent com ERICO 55...

Page 56: ...nd logos are owned or licensed by nVent Services GmbH or its affiliates All other trademarks are the property of their respective owners nVent reserves the right to change specifications without notic...

Reviews: