nVent.com | 5
E. SERVICING
The NGC-UIT-ORD contains no user-serviceable parts.
Contact your nVent representative for service and an
authorization number if required.
F. CLEANING
The touch screen area of the NGC-UIT-ORD may be cleaned
with a damp or dry cloth. Typical window cleaning agents
may be applied to aid in the removal of dirt, dust and grease.
Do not use abrasive cleaners.
G. CONFIGURATION SWITCHES
The configuration switches are found on the side of
the NGC-UIT-ORD. Refer to the table below for settings.
H. RESET SWITCH
The Reset switch can be found on the side of the NGC-UIT-ORD. A pointed object is required to press the reset switch and
restart the NGC-UIT software.
Switch
Position
Comments
On
Off
TERM R-FIELD
(Field Port
Termination Select)
Terminates local
RS-485 network.
120 Ohm
Termination
Enabled
(Factory Default)
Termination
Disabled
For the local FIELD RS-485
network. If this NGC-UIT is the
first or last RS-485 device in
the network, it must be set to
ENABLED/ON. If the NGC-UIT
is NOT the first or last device,
it must be set to DISABLED/
OFF.
TERM R-REMOTE
(Remote Port
Termination Select)
Terminates remote
RS-485 network
connected to PC and
RAYCHEM Supervisor
software.
120 Ohm
Termination
Enabled
Termination
Disabled
(Factory De-
fault)
For the REMOTE RS-485
network connected to a PC.
If this NGC-UIT is the first
or last RS-485 device in the
remote network, it must be
set to ENABLED/ON. If the
NGC-UIT is NOT the first or
last device, it must be set to
DISABLED/OFF.
WDT
(Watch Dog Timer)
WDT Enabled
(Factory Default)
WDT Disabled
WDT should normally be
enabled
Side View