NGC-UIT-ORD kit shown
installed in user’s panel
DESCRIPTION
The nVent RAYCHEM NGC-UIT-ORD is a panel mounted display
used in conjunction with other approved RAYCHEM control
and monitoring devices. The NGC-UIT-ORD is rated NEMA 12,
and the display can best be viewed indoors. The NGC-UIT-ORD
kit includes all hardware required for mounting in a suitable
electrical panel. These instructions describe how to mount the
NGC-UIT-ORD in an electrical panel and are intended only for
personnel experienced in panel construction.
TOOLS REQUIRED
• Masking tape
• #16 (3/16) drill bit
• 11/32 inch nut driver
• Metal file
• Jig saw (recommend using carbon steel blade with 24 TPI)
APPROVALS/CERTIFICATIONS
General
Supply voltage
100 – 240 Vac ±10%, .25 A max/25 VA,
50/60 Hz
Operating
temperature
–40°F to 149°F (–40°C to 65°C)
EMC
Immunity – Industrial
Emission – Commercial / Light Industrial
Vibration
Unit tested to IEC-60068-2-6
Shock
Unit tested to IEC-60068-2-27
Dimensions
10 1/4 in wide X 6 5/8 in high X 3 in deep
(260 mm wide X 168 mm high X 76 mm deep)
Control Outputs
Relay outputs
Three relay outputs, Form C contacts, switching
loads up to 277 Vac/3 Amps
Relays may be assigned for alarm outputs
11 position Phoenix-style pluggable screw
terminal connector with retaining screws
Status LEDs
Relay
Three LEDs showing the ON/OFF Status for
each relay, LED ON indicates relay is energized
Field
Transmit and Receive activity
Local/Remote
Transmit and Receive activity
NGC-UIT-ORD
User Interface Terminal for nVent RAYCHEM NGC Systems
Installation Instructions
LR67275
Nonhazardous Locations