background image

89059119

- 9 -

TEMPERATURE CONTROL

The electromechanical thermostat is factory preset to 75 F/23 C. To change the temperature setting, remove 

the nylon plug from the front face of the unit. Use a standard screwdriver to adjust thermostat. For cooler 
temperatures turn clockwise, for warmer temperatures turn counterclockwise. Setpoint differential is 6 F.

UNITS WITH HEAT

With a dial setting of 75 F, heat will turn on @ 70 F and turn off @ 75 F. Cooling will turn on @ 85 F and turn off 
at 80 F.

There is a 10 F difference between the heater off setpoint and cooling on setpoint to prevent both from operating 

at the same time.

The dial range of the thermostat is 50-95 F.

PRINCIPLES OF OPERATION

If electrical power to the air conditioner is interrupted and reapplied immediately, (within 3 to 5 seconds), 
the compressor may not restart due to the high back pressure of the compressor. It takes a minimum of one 

(1) minute after shut-down for the compressor suction and discharge pressures to equalize in order for the air 
conditioner to restart.

Operating the air conditioner below the minimum ambient temperature or above the maximum ambient 

temperatures indicated on the nameplate voids all warranties.

It is recommended that the warranty section of this manual be read in order to familiarize yourself with 

parameters of restricted operation.

The moisture that the enclosure air can contain is limited. If moisture flows from the drain tube continuously this 

can only mean that ambient air is entering the enclosure. Be aware that frequent opening of the enclosure’s door 
admits humid air, which the air conditioner must then dehumidify.

Units with the optional malfunction switch have a normally open connection between the red & yellow wires and 
normally closed with the red and blue wires. During alarm the red and yellow wires will be closed and the blue and 
red wires will be open.

Maximum electrical ratings for the switch are 13A for 120 VAC and 10A for 240 VAC.

C-NET INDUSTRIAL LTD. | +44(0)121 544 8608 | [email protected] | WWW.CNET-IS.CO.UK

Summary of Contents for T 15

Page 1: ...T15 Instruction Manual ...

Page 2: ... 2019 nVent 89059119 Rev I P N 10 1008 194 T SERIES Air Conditioner t15 Model INSTRUCTION MANUAL ...

Page 3: ...STING THE AIR CONDITIONER 3 INSTALLATION INSTRUCTIONS 4 Design Data 4 Dimensional Drawing 4 Mounting Cutout Dimensions 5 Components List 5 Wire Diagrams 6 Without Heat 6 With Heat 7 Schematics 8 TEMPERATURE CONTROL 9 Units With heat 9 PRINCIPLES OF OPERATION 9 MAINTENANCE 10 Compressor 10 Inlet Air Filter 10 How To Remove Clean or Install a New Inlet Air Filter 10 Condenser and Evaporator Air Move...

Page 4: ...efer to the nameplate for proper electrical current requirements and then connect the power cord to a properly grounded power supply Minimum circuit ampacity should be at least 125 of the amperage shown in the design data section for the appropriate model No other equipment should be connected to this circuit to prevent overloading Operate the air conditioner for five 5 to ten 10 minutes No excessi...

Page 5: ...be taken to keep it from kinking or being elevated above the exit point of the air conditioner The drain tube must be on a continuous downward slope A slight elevation of the tube could result in secondary trap FAILURE TO FOLLOW THESE INSTRUCTIONS COULD RESULT IN OVERFLOWING OF THE CONDENSATE DRAIN PAN 7 Refer to top of nameplate for electrical requirements Connect the power cord to a properly gro...

Page 6: ...02 15 1001 02 Coil Condenser Coated 15 1001 01 15 1001 01 Coil Evaporator 15 1001 03 15 1001 03 Compressor 10 1016 82 10 1026 101 Filter Air Reusable 89057626 89057626 Filter Dryer 52 6028 03 52 6028 03 Freeze stat 10 1033 26 10 1033 26 Service Cord 52 6035 140 52 6035 141 Terminal Block 10 1003 03 10 1003 03 Thermal Overload Compressor 10 1007 67 10 1007 68 Thermostat SPST 55 100F 10 1061 16 10 1...

Page 7: ...89059119 6 WIRE DIAGRAMS WITHOUT HEAT C NET INDUSTRIAL LTD 44 0 121 544 8608 INFO CNET IS CO UK WWW CNET IS CO UK ...

Page 8: ...89059119 7 WITH HEAT C NET INDUSTRIAL LTD 44 0 121 544 8608 INFO CNET IS CO UK WWW CNET IS CO UK ...

Page 9: ...89059119 8 SCHEMATICS With Heat Without Heat C NET INDUSTRIAL LTD 44 0 121 544 8608 INFO CNET IS CO UK WWW CNET IS CO UK ...

Page 10: ...ut down for the compressor suction and discharge pressures to equalize in order for the air conditioner to restart Operating the air conditioner below the minimum ambient temperature or above the maximum ambient temperatures indicated on the nameplate voids all warranties It is recommended that the warranty section of this manual be read in order to familiarize yourself with parameters of restrict...

Page 11: ...ut down of the unit The above described shutdown is symptomatic of a clogged or dirty filter thus causing a reduction in cooling air flow across the surface of the compressor and condenser coil Do not run the air conditioner for extended periods of time with the filter removed Particles of dust lint etc can plug the fins of the condenser coil which will give the same reaction as a plugged filter The co...

Page 12: ...the factory to insure against refrigeration leaks Shipping damage or microscopic leaks not found with sensitive electronic refrigerant leak detection equipment during manufacture may require repair or recharging of the system This work should only be performed by qualified professionals generally available through a local reputable air conditioning repair or service company Refer to the data on the...

Page 13: ...tive thermostat Open motor winding Stuck fan motor Obstructed blades Repair or Replace defective part 6 Carefully check the compressor for operation motor should cause slight vibration and the outer case of the compressor should be warm Is the compressor showing signs of this YES wait 5 minutes then proceed to step 7 NO possible problem Defective thermostat Defective capacitor Defective overload D...

Page 14: ...stem Getting water in enclosure Drain plugged Drain tube kinked Enclosure not sealed allowing humidity in Mounting gasket damaged For additional technical information i e amp draw pressures temperatures contact nVent Equipment Protection at 800 896 2665 F GAS INFORMATION T150116GXXX T150126GXXX Refrigerant Kühlmittel Chłodziwo R134a R134a GWP 1430 1430 Factory Charge Füllmenge durch Hersteller Opł...

Page 15: ...89059119 14 NOTES C NET INDUSTRIAL LTD 44 0 121 544 8608 INFO CNET IS CO UK WWW CNET IS CO UK ...

Page 16: ...89059119 15 NOTES C NET INDUSTRIAL LTD 44 0 121 544 8608 INFO CNET IS CO UK WWW CNET IS CO UK ...

Page 17: ...89059119 Rev I P N 10 1008 194 nVent com nVent 2100 Hoffman Way Anoka MN 55303 USA 1 763 422 2211 1 763 576 3200 C NET INDUSTRIAL LTD 44 0 121 544 8608 INFO CNET IS CO UK WWW CNET IS CO UK ...

Page 18: ...C NET Industrial Solutions Limited Suite 12 Sandwell Business Centre Oldbury Road Smethwick B66 1NN United Kingdom 44 0 121 544 6808 info cnet is co uk ...

Reviews: