Rev. D

P/N 89130554

 

ThermoelecTric coolers

Te16202405B AND Te16204805B

INSTRUCTION MANUAL

Summary of Contents for TE16202405B

Page 1: ... 2018 nVent 89130554 Rev D P N 89130554 Thermoelectric Coolers TE16202405B AND TE16204805B INSTRUCTION MANUAL ...

Page 2: ...power cord to a properly grounded power supply Minimum circuit ampacity should be at least 125 of the amperage shown in the design data section for the appropriate model No other equipment should be connected to this circuit to prevent overloading Operate the thermoelectric cooler for five 5 to ten 10 minutes No excessive noise or vibration should be evident during this run period The ambient and ...

Page 3: ...t the thermoelectric cooler on the enclosure using the mounting fasteners provided 6 Reinstall the power alarm harness and grommet into the thermoelectric shroud 7 Reinstall the ground screw with the customer supplied grounding cable 8 Refer to the top of the nameplate for the electrical requirements Connect the thermoelectric cooler to a properly grounded power supply Class 2 or SELV power source...

Page 4: ... 2018 nVent 89130554 4 DIMENSIONAL DRAWING 89062256 ...

Page 5: ... J2 J1 RED BLK RED BLK BLACK RED FAN CONNECTOR FAN CONNECTOR BLACK BLACK RED RED RED BLK INTERNAL FAN RED BLK RED BLK FAN CONNECTOR THERMISTOR HARNESS TE2 TE2 TE1 TE1 RED LED BLUE LED DIP SWITCH FOR ADJUSTING COOLING AND HEATING SETPOINTS AND INTERNAL FAN SETTING CHANGE BULLET CONNECTOR FOR N O ALARM PLUG 2 CIRCUIT SEALED MINI UNIVERSAL MATE N LOCK P N 794894 1 TE PIN CRIMP 18 22 AWG GOLD MINI UNI...

Page 6: ... BLK J2 J1 RED BLK RED BLK BLACK RED FAN CONNECTOR FAN CONNECTOR RED BLK INTERNAL FAN RED BLK RED BLK FAN CONNECTOR THERMISTOR HARNESS TE2 TE2 TE1 TE1 RED LED BLUE LED DIP SWITCH FOR ADJUSTING COOLING AND HEATING SETPOINTS AND INTERNAL FAN SETTING CHANGE BULLET CONNECTOR FOR N O ALARM PLUG 2 CIRCUIT SEALED MINI UNIVERSAL MATE N LOCK P N 794894 1 TE PIN CRIMP 18 22 AWG GOLD MINI UNIVERSAL MATE N LO...

Page 7: ... R SETUP Cooling and heating temperature setpoints are factory set to 77 F 25 C for cooling and 59 F 15 C for heating These setpoints can be changed by adjusting the 4 position dip switch on the printed circuit board assembly S1 See Table 1 Cooling and Heating Setpoints Note The heating function includes a disabled position Table 1 Cooling and Heating Setpoints Cooling Setpoint C S1 Position 1 S1 ...

Page 8: ...links for half second ON and half second OFF for the appropriate number of times see Table 1 Cooling and Heating Setpoints 3 The TEC ramps up in cooling mode for 5 seconds The blue cooling LED flashes rapidly 4 The TEC ramps up in heating mode for 5 seconds The red heating LED flashes rapidly The controller will command the TEC to cool if the temperature read by the thermistor is above the cooling...

Page 9: ... 2018 nVent 89130554 9 NOTES ...