2
GENERAL MAINTAINED EMERGENCY LUMINAIRE INSTRUCTIONS
(SUFFIX .../M3)
These instructions should be followed in conjunction with the standard luminaire instructions. Please read
carefully and pass to the end user/responsible person for retention and future reference.
INSTALLATION
1. Following the installation of the luminaire in accordance with the standard luminaire installation instructions, a
separate permanent live supply should be terminated in the 4-pole terminal block in the luminaire, in the
connection marked ‘L PERM’. The permanent supply MUST be taken from the same phase as the corresponding
switched supply and MUST be wired at the switchboard so that upon instances of tests, it is isolated at the same
time as the switched supply.
2. Connect the battery to the module via the ‘plug and mate’ connector, ensuring correct polarity is observed. Failure
to observe correct battery polarity will result in permanent damage to the emergency module/driver.
3. Upon restoration of the power supply to the luminaire, check that the indicator LED fitted within the luminaire
illuminates green. This indicates that the batteries are charging and that the charging circuit is healthy.
4. Allow the battery to charge for an uninterrupted period of not less than 24 hours prior to carrying out a full
discharge test.
MAINTENANCE
5. The battery pack in this luminaire must be replaced when it is no longer able to satisfy its full rated duration.
6. In emergency mode the light level of the luminaire will be at a reduced output. Regular maintenance and gentle
cleaning is recommended so as to ensure that the Emergency Output Factor (E.O.F) remains at pre-determined
levels.
7. Isolate the supply before servicing.
8.
DO NOT INSULATION TEST
***************************IMPORTANT WARNING ****************************
This unit is using Lithium Ion Phosphate cells (LiFePO4) in its battery pack. These batteries
require close monitoring and protection circuitry to operate safely. The same ‘battery’ pack will
be required when exchanging battery packs in the future during maintenance.
TESTING FOR EMERGENCY LUMINAIRES
Recommended routine test procedures in line with BS 5266-1:2016 & BS EN 50172:2004.
MICROWAVE SENSOR C/W DIP SWITCHES INSTRUCTIONS
(SUFFIX .../MW)
These instructions are in addition to the standard luminaire instructions that were also supplied with the product
you have purchased. They should be read carefully & luminaire installed as per both sets of instructions, then
pass on to the appropriate person for retention for future reference & maintenance.
DESCRIPTION
The micro-wave sensor option offers presence detection to provide automatic control of lighting loads. It is installed inside
the luminaire so does not affect external aesthetics or IP rating. Manual adjustments on the sensor allow it to be
individually tailored to suit your application.