background image

 

 

 

SPARTAN 3CCT SELECTABLE IP65 LED BULKHEAD INSTRUCTIONS  

Issue 02 on 6

th

 March 2021 

 

THANK YOU

 for buying this product.  To help ensure it gives complete satisfaction please install it according to these 

instructions and then pass the instructions to the appropriate person for retention and future reference. 

 

SAFETY

  This is a mains powered product.  It is designed to be installed by suitably qualified personnel 

only and in accordance with the applicable building and electrical regulations.  Before installation or 
maintenance the electrical supply to the product must be isolated.  

 

INSTALLATION SUPPORT 

If installation advice or accessories are required please contact us at the 

above address.  We will do our best to help.  When reporting a suspected fault or seeking installation support the problem 
is likely to be resolved most quickly if you have full product details to-hand, as well as details of when and where it was 
purchased. 

 

INSTALLATION 

   

 

 

         

 

1.  Loosen the 3 diffuser fixing screws & remove the diffuser geartray assembly from the base by unhooking the 

retention strap. 

2.  Prepare the mains supply cable & fixing points on the chosen mounting surface ensuring it is able to retain the 

weight of the luminaire. 

3.  Pass the mains supply cable through the cable entry hole, offer the base to the mounting surface & secure using 

the screws provided.  

Note! It is the installer’s responsibility to ensure the fixing points & cable entry point are appropriately 
sealed to maintain the IP rating 

4.  Route the mains supply cable to the terminal block on the gear tray & terminate ensuring correct polarity is 

observed. 

Note! This luminaire must be earthed

 

5.  Select the required CCT by sliding the switch on the back of the gear tray to the allocated colour 
6.  Refit the diffuser gear tray assembly (opposite of point 1) & secure by retightening the screws. 
7.  Reconnect power supply & check for correct operation. 

Note! Luminaires fitted with electronic drivers are exempt from insulation resistance tests as this may 
cause damage to the drivers. 

8.  For suffix ../M3 and suffix…/MW  versions see further instructions below.

 

 

BEZEL TRIMS 

If this option has been selected, then install as follows: 

1.  Offer the bezel trim to the main luminaire aligning the lugs in the trim with the screw slots in the diffuser (3 

places). 

2.  Push fit until it clips into position. 

Note! If eyelid trim is selected then care will need to be taken to ensure slots are in the correct position when 
securing the base. 

 

MAINTENANCE 

1.  Cleaning should be carried out at regular intervals so as not impair photometric performance or thermal safety of 

the luminaire. 

 
 
 
 
 
 
 

 

Summary of Contents for SPARTAN 3CCT

Page 1: ...e luminaire 3 Pass the mains supply cable through the cable entry hole offer the base to the mounting surface secure using the screws provided Note It is the installer s responsibility to ensure the fixing points cable entry point are appropriately sealed to maintain the IP rating 4 Route the mains supply cable to the terminal block on the gear tray terminate ensuring correct polarity is observed ...

Page 2: ... discharge test MAINTENANCE 5 The battery pack in this luminaire must be replaced when it is no longer able to satisfy its full rated duration 6 In emergency mode the light level of the luminaire will be at a reduced output Regular maintenance and gentle cleaning is recommended so as to ensure that the Emergency Output Factor E O F remains at pre determined levels 7 Isolate the supply before servi...

Page 3: ...ix to a vibrating surface Avoid metallic objects directly in front of the sensor head These sensor kits are capable of switching controlling more than one luminaire in a master slave set up This is done by linking non sensored fittings slaves to the one with the sensor fitted master using the live output from the sensor Note DO NOT link other fittings containing MW sensors together in this way as ...

Page 4: ...the live supply to the circuit is good If the supply wiring are good check the LUX setting Increase the LUX level setting to allow the sensor to turn on at a higher ambient light level Fault Lights do not go off Ensure that the area is left unoccupied for longer than the selected timer setting Make sure that the sensor is not adjacent to circulating air heaters or lamps If the unit false triggers ...