5.2 Stage Selection
S2 positions 1-4 select the number of output stages.
Switch S2
Position
→
1
2
3
4
Label
→
STP3
STP2
STP1
STP0
Stages
1
OFF
OFF
OFF
OFF
2
OFF
OFF
OFF
ON
3
OFF
OFF
ON
OFF
4
OFF
OFF
ON
ON
5
OFF
ON
OFF
OFF
6
OFF
ON
OFF
ON
7
OFF
ON
ON
OFF
8
OFF
ON
ON
ON
9
ON
OFF
OFF
OFF
10
ON
OFF
OFF
ON
11
ON
OFF
ON
OFF
12
ON
OFF
ON
ON
13
ON
ON
OFF
OFF
14
ON
ON
OFF
ON
15
ON
ON
ON
OFF
16
ON
ON
ON
ON
5.3 Output Mode Selection
LIFO (last in first out) and FIFO (first in first out) modes are both available by
setting of S2 position 6.
Switch S2
Position
→
6
Label
→
FIFO
Output Mode
LIFO
OFF
FIFO
ON
LIFO
mode is the normal default mode. In this mode the output stages
respond to the command input like a level bar graph.
FIFO
mode circulates the on stages to promote even use of the contactors
and elements. For example, the first stage that was turned on when the
power was increasing will be the first stage turned off when the power is
decreasing.