sc_warn_controller_wdt
▪
Warning triggered from the same data as
sc_fault_controller_wdt
sc_fault_stackbus_rxwdt
▪
Fault indicating that there was a receive communication failure over the Stack Bus
sc_fault_stackbus_txwdt
▪
Fault indicating that there was a transmit communication failure over the Stack Bus
sc_fault_pi_afe_wdt
▪
Fault indicating that there was a communication failure between the AFE and the Stack
Switchgear unit’s internal Power Interface module
sc_fault_linkbus_wdt
▪
Fault indicating that there was an internal communication failure relating to Link Bus data.
Please contact Nuvation Energy at
fault.
sc_fault_ram_test_wdt
▪
Fault indicating the internal RAM testing has not been executing periodically
sc_fault_rom_test_wdt
▪
Fault indicating the internal ROM testing has not been executing periodically
sc_fault_factory_verify_wdt
▪
Fault indicating the factory registers on the Stack Switchgear unit’s internal Stack Controller
module have not been periodically validated against non-volatile memory
▪
Typically disabled
pi_fault_factory_verify_wdt
▪
Fault indicating the factory registers on the Stack Switchgear unit’s internal Power Interface
module have not been periodically being validated against non-volatile memory.
▪
Typically disabled
10.1.9.1. Initialization Issues
The
stack_fault_cell_wdt
,
stack_fault_therm_wdt
,
stack_fault_ci_wdt
, and
stack_fault_open_wire_wdt
can
be uninitialized due to problems with the Link Bus. Refer to
The
sc_fault_pi_afe_wdt
and
stack_fault_power_wdt
can be uninitialized due to disabling the Stack
Switchgear unit’s internal Power Interface module’s AFE or a high amount of noise on the DC bus.
This is typically caused by incorrectly modifying the Stack Switchgear factory configuration file.
Contact
for a valid configuration file for the Stack Switchgear.
The
sc_fault_controller_wdt
can be uninitialized if there is no external controller updating the
heartbeat. Contact
to update the configuration file