NuAire SQFT Installation Manual Download Page 3

04. 02. 20. Document Number  671835

3

Nuaire | 

Western Industrial Estate 

Caerphilly 

CF83 1NA 

|

 

nuaire.co.uk

SQFT

Installation Manual

AV mounts available
as an ancillary item

Mounting feet 
(supplied).

FLOW

FLOW

Mounting feet 

(supplied).

Support beam

AV Mounts

Flexible 

connector

Dampers

Fan 1

L

N

230V 1 phase 50 Hz only 

Mains supply via local isolator (not shown)

X L N

Fan 2

L

X

N

Auto 

change-over 

control 

(by others)

W1       V1 

  U1

W2       V2    U2

Fan 1

Fan 2

W1 

  U1

     V1 

V2 

W2      

  U2

L1

L2

L3 

Auto 

control 

   

change-over 

(by others)

460V 3 phase 60 Hz supply 

400V 3 phase 50 Hz supply 

380V 3 phase 60 Hz supply 

Mains supply via local isolator (not shown)

Horizontal Discharge - Mounting Feet (Supplied) Supported Via 
A.V. Mounts

Vertical Discharge - Mounted On Support Beam Via A.V. Mounts

Wiring - Single Phase - Single Speed

Wiring - Three Phase (3kW and Below) - Single Speed

The ducting must be the same dimension as the fan for at least 1m 
at the discharge of the fan before any transition. This is to allow the 
free movement of the dampers and to minimise pressure losses. 
We recommend the use of anti-vibration mounts to minimise the 
transmission of vibration into the building structure.

Rotate the fan impeller by hand to ensure free and smooth rotation and 
that no handling or transit damage has occurred, observe the direction 
of flow/direction of rotation arrow and ensure that:

All optional accessories such as support brackets, attenuators, 
guards, flexible connectors etc. are assembled to the fan.

Support brackets are fitted appropriate for the installed 
attitude - vertical or horizontal.

When offering the fan to the ducted system that both inlet 
and outlet connections are perfectly aligned.

It is advisable to fit flexible connectors on either side of the fan unless 
there is an open-ended inlet or discharge and the fan should be 
supported on AV mounts. The A.V.s should be levelled off to maximise 
isolation and the flexible connectors correctly aligned with the fan at 
the correct tension.

IMPORTANT

A.V. mounts isolate the fan only. Silencers / backdraught 

dampers and other "significant mass" accessories should form 

part of the fixed ductwork after the flexible connection.

4.2 Electrical installation

All installation work must be planned and carried out by consideration 
all relevant regulations including CDM, health and safety and wiring 
regulations.

Ensure the electrical supply is suitable for the fan and is suitably 
protected by correctly selected fuses or MCB.

For 3 phase units, the electrical connections are made directly onto the 
terminal boxes of the motors.

For single phase units, the electrical connections are made at 
termination boxes at the motor mounting brackets.

Note that 3 phase motors up to 3kW (inclusive) must be wired in STAR. 
Motors of 4kW and above must have DELTA as the final connection 
arrangement.

4.3 Electrical installation - Motors

Motors are totally enclosed and protected to IP55 (Dust and low 
pressure water jets). 

Please note the requirements for maintenance of the motor. Failure to 
comply with regulations will invalidate any warranty claim. 

4.4 Wiring

These units are not supplied with any control or isolators, their 
selection and provision is the responsibility of the specifier/contractor.

IMPORTANT

When the unit is operated in emergency mode smoke extract 

operation - all controls must be bypassed.

Summary of Contents for SQFT

Page 1: ...ving any covers During installation maintenance ensure all covers are fitted before switching on the mains supply All pole disconnection from the mains as shown in the wiring diagram must be incorpora...

Page 2: ...off emergency use 2 1 Code Description SQFT 4 5 T 1 2 3 4 1 Range Square Twin In line Fan 2 Motor Poles 4 or 6 3 Size 1 2 3 4 5 or 6 4 Pole Motors Only 1 2 3 or 4 6 Pole Motors Only 4 Control Type No...

Page 3: ...al When offering the fan to the ducted system that both inlet and outlet connections are perfectly aligned It is advisable to fit flexible connectors on either side of the fan unless there is an open...

Page 4: ...n the entire ventilation circuit housing fins motor cover fan if fitted driven fan Ensure the motor runs normally when switched on for a few minutes iii Bearing check C3 or C4 play Run the motor durin...

Page 5: ...ich can be largely recycled when the product reaches its end of life Fans motors controls actuators cabling and other electrical components can be segregated into WEEE recycling streams Sheet metal pa...

Page 6: ...04 02 20 Document Number 671835 6 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk SQFT Installation Manual NOTES...

Page 7: ...04 02 20 Document Number 671835 7 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk SQFT Installation Manual NOTES 7...

Page 8: ...t the equipment only Other system components must have separate provision for support 4 3 Flanges and connection spigots are provided for the purpose of joining to duct work systems They must not be u...

Reviews: