3.0 Electrical Details

To gain access to the units power supply and control panels

remove the access cover as shown in figure 8.

3.1 Connections

3

Installation and Maintenance

OPUSDC-SA-60 Student Accomodation Duct Mounted Extract Fans

Figure 10. Ecosmart control (PCB).

Figure 9. 24V power supply.

SWL

N

L

Min   Max  Run On  Pwr  Standby  Fan 1  Fan 2

Fan 1 

Fan 2

Figure 8.

Mains cable 
and clamp.

‘Net’ connections for
Ecosmart devices.

Switch to activate
continuous trickle.

230V
1N
50Hz
Mains

Power Consumption

ES-Opus  ES-Opus  ES-Opus ES-Opus 

DC 40

DC 60

DC 75

DC 110

Unit input power (watts)

18

44

33

90

Full load running current (amps) 0.14

0.32

0.26

0.61

Ecosmart control 

(see figure 10)

(a) Net -

the 4 IDC plug-in connectors are provided for the

connection of compatible sensors, manual controls and for

linking the fans together under a common control. If more

than 4 connections are required, the junction box (product

code ES-JB) should be used.

NOTE: Do not run the SELV data cable in the same

conduit as the mains cable and leave a 50mm

separation with any power cables.

(b) Volt Free Relay Contacts

Note that the volt free contacts are not fused. If these are

used to power any external equipment, the installer must

provide adequate fusing or other protections. These

contacts are rated at 5A resistive, 0.5A inductive.

(c) Run connections

These contacts are closed when the fan is running.

Fault connections - No fault

= the contacts are closed.

Fault 

= the contacts are opened (this includes no power

supply at the unit).

(d) Data Cable installation

A 4-core SELV data cable is used to connect devices such

as sensors to the fan and for interconnecting multiple fan

units.

Do not run data cable in the same conduit as the mains

cables and ensure there is a 50mm separation between 

the data cable and other cables. The maximum cable run

between any two devices is 300m when it is installed in

accordance with the instructions.

Please note that the total data cable length used in any

system must be less than 1000m. Keep the number of cable

joints to a minimum to ensure the best data transmission

efficiency between devices.

(e) Maximum number of devices

The maximum number of devices (including fans) that can

be connected together via the cable is 32, irrespective of

their functions.

(f) LED Indication

PWR

GREEN: Power on and OK, RED:

Standby

LED on when fan is not running.

Fan 1

GREEN: Fan 1 is running, RED: Fan 1 faulty.

Fan 2

GREEN: Fan 2 is running, RED: Fan 2 faulty.

Volt free relay 
contacts.

RUN FAULT

ON

OFF

IMPORTANT

Isolation - Before commencing work make sure that the 

unit, switched live and Nuaire control areelectrically 

isolated from the mains supply.

12. 05. 17. Leaflet Number 671739