 OPUS100/150-M

Installation Manual

2.0 INTRODUCTION

Manufactured in galvanised steel, the unit is designed to serve toilets, 
storerooms, small offices, restaurants, smoking areas etc. and for duct 
mounting applications usually in the ceiling or service voids above the 
areas served. For full specification, dimensions and weights etc. refer to 
catalogue.

For EMC the ambient temperature limit for the Opus plus range is  
24°C (or 25°C if the speed pot is restricted to ¼ turn above 
minimum).

Unit Airflow

2.1 Opus Fan Range 

Code

Description

Power / FLC 
at Full Speed

OPUS100-M

Single Fan Unit

100 W / 0.39 A

OPUS100-2M Twin Fan Unit (Run / Standby Auto Duty 

Share)

100 W / 0.39 A

OPUS150-M

Dual Fan Unit (Both Motors Running 
Simultaneously)

200 W / 0.78 A

3.0 Dimensions (mm) & Weights

 
 

Dimensions (mm) & Weights

500

330

50

Filters

3.

2.

Filters

2.

2.

2.

1.

4.

4.

4.

4.

End View

Airflow

Top View

200

260

2.

Key:
1. 1 x 150 Dia. Spigot Knockout
2. Cable Access
3. Single Screw Unit Fixing
4. 4 x 100 Dia. Spigot Knockouts
5. Access Panel (full length of unit)

5.

4.

4.

Side View

Airflow

Unit 

 

Weight (kg)

OPUS100-M 

10

OPUS100-2M 

11

OPUS150-M 

11

4.0 MECHANICAL INSTALLATION

Installation must be completed by competent persons, in accordance 
with good industry practice and should conform to all governing and 
statutory bodies i.e. IEE, CIBSE, etc.

The unit comprises a full-length access cover, to reveal filter and fans 
and is supplied with outlet spigot fitted and ‘knockouts’ to be removed 
at the chosen inlet positions.

Prepare the unit for installation by removing the access cover, all 
internal packaging and the fan assembly (supplied loose in the box). 
Replace the unit cover and knock out the chosen inlet spigot points and 
fit the matching spigots.

Ensure that all electrical and ducting services are compatible to the 
installation and the desired control function.

Ensure transit packing pieces A & B are removed before applying 
power to unit.

 

Removing Transit Pieces

Electrical 
terminal block

Cable grommet

Motor plate 
fixing screws (2)

Motor assembly

Earth post

A

B

4.1 Unit Mounting Bracket

Select a solid non-reverberant mounting position, remove the unit 
support bracket and fix the bracket to the chosen structure with 
appropriate anchor bolts or screws.

The fan can be installed using the integral mounting bracket supplied 
(Figure 4). Offer the unit to the bracket as shown and secure into 
position with the one point-fixing bolt. Connect inlet and outlet 
ducting.

Unit Mounting Bracket

Mounting bracket 
to structure fixings

Bracket tongues
must engage 
with case slots

Bracket tongues engage with 
case slots, then case rotated 
up to align with fixing screw 
hole