NuAire NALTF Series Installation And Maintenance Manual Download Page 3

Isolation - Before commencing work make sure

that the unit, and any control are 

electrically isolated from the mains supply.

3

NALTF/TRF 

Roof and Plantroom Twinfans

15. 05. 17. Leaflet Number 671269

Electrical Installation Basic Layout

Figure 8. Basic internal layout.

NOTES:

Because the run and start currents depend upon the duty

and associated ductwork of an individual unit, the values

quoted in the table are nominal.

Run currents will be exceeded if the unit is operated with 

its cover removed. The unit must NOT run for more than 

2 minutes in this condition.

Electrical Wiring

Figure 9.

The fan will only operate when a 230V mains signal is 

present at the SL terminal. 

When the SL signal is switched off the fan will continuue to

run for a preset period (1-60 minutes). Adjust the overrun

time at the pot marked ‘-SL RUNON’.

Ensure the local isolator (by others) also isolates 

the switched live.

400V  3 ph  50Hz  Suppl

y

L

L

N

L3

L2

L1

N

FAN UNIT 

Fan live applies to 

Direct Drive fans only

(Link to be left in) 

Fault indicating

voltage free 

contacts

Note: relay is 

energised if no 

fault is present

i.e. COM - N O 

is connected if 

there is no fault

N O

N C

COM

SL

230V Switched live signal. 

Remove L/SL link when using

Switched live overrun 

adjustment

NAL-RFI Remote fan 

indicator (supplied)

Basic fan wiring diagram for

NALTRF 9-15 and NALTF 9-15 only

Controls for NALTF/NALTRF 9-15

The NALTF/NALTRF 9-15 fan units incorporate an integral

auto-changeover controller which provides 12 hour duty

share operation and automatic selection of the standby fan

should the duty fan fail.

Fault indication to an external device is provided via volt free

contacts of a relay. 

Note: the relay is energised when no fault is present.

Note: It is the responsibility of the installer to provide a 

suitable switchable local isolator for maintenance purposes

etc.

NALTF/NALTRF 16-24 Inclusive

These fan units are supplied without any controls fitted.

The electrical power is connected directly to the motor.

Note that the motors are 5.5kW or higher and STAR-DELTA

starting or a Soft Starter should be used in the motor control

panel (by others).

4.0 Electrical Details

Run currents etc.

400V 3 Phase 50Hz 

Unit  Code

Speed

Power

f lc

sc

Weight  

rpm

(kW)

(amps)

(amps)

kg

NALTF/TRF 9 

1225

0.75

2.1

9.5

84.4

NALTF/TRF 10 

1400

1.1

2.9

13.0

90.4

NALTF/TRF 11 

1085

1.5

3.7

8.5

125

NALTF/TRF 12 

1225

2.2

5.4

27.0

134

NALTF/TRF 13

1040

2.2

5.4

27.0

168.7

NALTF/TRF 14 

1040

4.0

10.0

60.0

193.6

NALTF/TRF 15 

1260

3.0

6.9

38.0

174.6

NALTF/TRF 16 

1260

5.5

12.0

75.0

231.6

NALTF/TRF 17

1440

5.5

12.0

75.0

231.6

NALTF/TRF 18 

700

5.5

12.0 

75.0 

730

NALTF/TRF 19  

800

4.0

10.0

60.0

716 

NALTF/TRF 20 

800

11.0

23.0

154.0

794

NALTF/TRF 21 

1000

5.5

12.0

75.0

730

NALTF/TRF 22 

1000

11.0

23.0

154.0

794

NALTF/TRF 23 

1100

11.0

23.0

154.0

794

NALTF/TRF 24 

1200

11.0

23.0

154.0

794

Summary of Contents for NALTF Series

Page 1: ...sing is manufactured from heavy gauge Aluzinc aluminium zinc coated mild steel A full size internally lined access panel is fitted to the top face and is fully detachable for inspection purposes The motor plate and frames are supported on the base by resilient mountings allowing the fan unit to be operated without the need for separate anti vibration fan case mountings The units incorporate two in...

Page 2: ...d of mounting used is the total responsibility of the installer The lower edge of the casing has an internal skirt allowing the unit to be located on an upstand or prefabricated curb if desired The units must be securely screw fixed to the upstand curb to prevent vibration and or wind damage It is the installers responsibility to drill the case to provide access for the electrical cables Care shou...

Page 3: ...TRF 9 15 and NALTF 9 15 only Controls for NALTF NALTRF 9 15 The NALTF NALTRF 9 15 fan units incorporate an integral auto changeover controller which provides 12 hour duty share operation and automatic selection of the standby fan should the duty fan fail Fault indication to an external device is provided via volt free contacts of a relay Note the relay is energised when no fault is present Note It...

Page 4: ...kg Changing a Drive Belt To replace a belt remove the two bolts from the motor mounting furthest from the fan and slacken the remaining two bolts Lift the motor plate and remove the belt Replacing the belt is the reverse of this procedure Figure 12 Adjusting the Drive Belts larger units Adjusting Drive Belt Tension larger units All belt drive units incorporate belt tensioning devices To adjust the...

Page 5: ... of the part required 7 0 Warranty The unit has a one year warranty The warranty starts from the date of delivery and covers faulty materials or workmanship and includes parts and labour The labour element is subject to full free and safe access to the equipment as recommended by the CDM regulations This warranty is void if the equipment is modified without authorisation is incorrectly applied mis...

Page 6: ...s given for the individual product the following general requirements should be noted 5 1 Where access to any part of equipment which moves or can become electrically live are not prevented by the equipment panels or by fixed installation detail eg ducting then guarding to the appropriate standard must be fitted 5 2 The electrical installation of the equipment must comply with the requirements of ...

Reviews: