NuAire MRXBOXAB-ECO4-AEOHSC Installation Manual Download Page 8

8

16. 03. 21. Document Number  671863

Nuaire | 

Western Industrial Estate 

Caerphilly 

CF83 1NA 

|

 

nuaire.co.uk

MRXBOXAB-ECO4-AE(SC/SW)

Installation Manual

5.0 COMMISSIONING

The filters fitted inside the unit are protected with a plastic film. 
Prior to commissioning remove the covers (Figure 20), take off the 
film and replace.

1. For the required air flow rates please refer to the design specification 

for the property, follow Section 3.8, or refer to building regulations 
ADF 2010.

2. The unit should be run for a minimum of 10 minutes to reach steady 

state before commencing commissioning.

3. The humidity sensor is initially set to its least sensitive position, this 

should be adjusted during commissioning.  Depending on storage 

and site conditions, the unit may boost due to high relative humidity 

levels, this will continue until the level drops below the specified set 

point.

4. The unit is supplied with independent control for both normal and 

boost airflows (Figure 18). 

5. Correct commissioning is essential to ensure the ventilation air flow 

rates are met. It also ensures the unit is not over ventilating and 
causing excessive power consumption. 

6. Commissioning should be carried out in accordance with building 

regulations document “Domestic ventilation compliance guide”. 

www.planningportal.gov.uk/building regulations/approved 
documents/partf/associated. 

A calibrated moving vane 

anemometer and hood will be required to carry out commissioning.

7. Adjustment valves should be locked in place to prevent further 

adjustment. 

8. Once commissioned the home owner / tenant should be informed 

that the unit should not be adjusted as it will have a detrimental 
effect on the indoor air quality and could result in condensation and 
mould growth. The clear panel covering the control has an adhesive 
panel which should be exposed and sealed post commissioning to 
prevent tampering. 
 

18 

Unit Control On Front Panel

+

-

Post commissioning remove
adhesive backing and seal 

061021

Power  Fan

Failure

+

-

Ventilation Controls

- +

+

- +

-

Speed 1 

- +

Speed 2 

Speed 3

Supply  Extract  Supply  Extract  Supply  Extract

Humidistat adjustment

(access by removing front cover)

6.0 CONTROLS

6.1 Humidity Adjustment

This product contains an internal humidity sensor fitted into the air-

flow extracting from the wet rooms. When the unit senses that the 

humidity exceeds the set point, the unit will boost to that set by the 

commissioned boost speed. The set point can be found on the front 

of the unit

 

(Figure 18) and is at its least sensitive when turned fully 

clockwise. Note that the sensor is measuring humidity from all the wet 

rooms at the same time and should not be relied on to solely boost the 

unit. 
Additional switch should be used local to the wet rooms (Section 4.2).

6.2 Status Indication

The status of the unit is indicated by a series of LED’s on the front cover. 

The variants are listed below.

The display on the unit control panel will not indicate when a 

higher speed setting has been triggered by an external source, such 

as an ES-PIR2 etc.

 

 

19 

Unit Control On Front Panel

 (Standard Configuration Only)

HX Bypass

(AB units only)

Speed 1

Speed 2

Speed 3

Supply Fan Fault

Extract Fan Fault

Frost Protection

Filter Change

6.3 Integral Automatic HX Bypass

Intake and extract temperatures are monitored at the point the 

airflows enter the unit, if the range falls within the set parameters the 

bypass damper is opened automatically to target an indoor comfort 

temperature all year round.
The extract temperature is an average from all wet rooms. If this 

exceeds 25°C the unit may go into bypass depending on outside 

temperatures.

6.4 Summer / Winter Switch

When the switch position is set to Summer the integral automatic 
summer bypass is fully operational, in the alternative Winter position 
the HX bypass is disabled to ensure the unit is constantly in heat 
recovery mode.

6.5 Speed 3 Operation (SW Units Only)

Speed 3 will be non-operational if the intake temperature is greater 
than the extract temperature.

6.6 Frost Protection

In the event of the intake air temperature at the unit dropping below 

the predetermined set point (-5°C as standard) the supply fan will 

reduce to minimum speed, once the temperature rises above the set 

point the fan will return to its commissioned speed.
Frost protection will only activate after ten days of continuous run 

time. If commissioning of the unit is outside of this time frame please 

notify the after sales department prior to site visit.

Summary of Contents for MRXBOXAB-ECO4-AEOHSC

Page 1: ...fe use of the appliance by a person responsible for their safety Children shall not play with the appliance Cleaning and user maintenance shall not be carried out by children 1 1 Hazard Symbols REFER TO INSTRUCTION MANUAL Read and understand the installation and maintenance manual before installing operating or maintaining this product 1 2 Important Information This manual contains important infor...

Page 2: ...and building fabric This appliance is not intended for use by persons including children with reduced physical sensory or mental capabilities or lack of experience and knowledge unless they have been given supervision or instruction concerning the use of the appliance by a person for their safety Children should be supervised so that they do not play with the appliance 3 1 Transport Fixings To pre...

Page 3: ... in insulated to prevent freezing Nuaire recommend MVHR DRAIN be used as the primary condensate take off Figures 8 and 9 3 5 Extract Input Areas The unit is designed to extract air from all wet rooms e g bathroom kitchen en suite utility room with sink WC s do not need to be ventilated if openable windows are fitted Supply air should be to all habitable rooms e g bedrooms and lounge Extract input ...

Page 4: ...t and the air outlet duct from the unit these ducts should be insulated Ducting must be installed in such a way that resistance to airflow is minimised Bends should be kept to a minimum A minimum distance of 300mm between the appliance and any bends in ductwork is recommended Ideally 150mm diameter or 220 x 90mm rectangular ducting should be used refer to dwelling design drawing Figures 11 12 Duct...

Page 5: ...te e g boost should be at least the greater of step 1 and step 2 Note that the maximum individual room extract rate should be at least those given in ADF 2010 Extract Ventilation Rates table The minimum air supply rate should be at least the whole building ventilation rate found in step 1 For Scotland refer to BRE Digest 398 For further information refer to Domestic Ventilation Compliance Guide ww...

Page 6: ...ings via AirValve MVHR unit Nuaire MVHR DRAIN Condensate drain uninsulated drain pipe with min 5 o fall running to SVP Insulated extract duct 3 10 2 Rectangular Ducting 12 Typical Rectangular Ducting Arrangement For Wall Mounted Units Exhaust air from kitchen bathroom to outside via air brick Minimum distance as specified in building regulations Intake air from outside via air brick All duct betwe...

Page 7: ...ixed wiring in accordance with the wiring regulations and shall have a minimum contact separation of 3mm 4 2 1 Unit Only MAINS 230V 50Hz N L 3 Position Switch Ancillary code MRXBOX95 3SWITCH Blue Green yellow Brown Black Supply cord from unit Grey L 1 2 5A Fuse BS1362 2 Pole Isolator 14 Wiring Diagram Unit Only 4 2 2 Unit Serving One Bathroom 15 Wiring Diagram One Bathroom 5A Fuse BS1362 MAINS 230...

Page 8: ...cover 6 0 CONTROLS 6 1 Humidity Adjustment This product contains an internal humidity sensor fitted into the air flow extracting from the wet rooms When the unit senses that the humidity exceeds the set point the unit will boost to that set by the commissioned boost speed The set point can be found on the front of the unit Figure 18 and is at its least sensitive when turned fully clockwise Note th...

Page 9: ...ication plate attached to the unit casing Telephone 02920 858 400 aftersales nuaire co uk Technical or commercial considerations may from time to time make it necessary to alter the design performance and dimensions of equipment and the right is reserved to make such changes without prior notice 7 0 MAINTENANCE It is important that maintenance checks are recorded and that the schedule is always ad...

Page 10: ...10 16 03 21 Document Number 671863 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk MRXBOXAB ECO4 AE SC SW Installation Manual NOTES ...

Page 11: ...11 16 03 21 Document Number 671863 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk MRXBOXAB ECO4 AE SC SW Installation Manual NOTES ...

Page 12: ...12 16 03 21 Document Number 671863 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk MRXBOXAB ECO4 AE SC SW Installation Manual NOTES ...

Reviews: