background image

8

nuaire.co.uk 

029 2085 8400

28. 07. 20. Leaflet Number  671838

Installation and Maintenance

The MRXBOXAB-ECO4-1Z Range of Units

Telephone 02920 858 400 

[email protected]

11.0 REPLACEMENT OF PARTS

Should any component need replacing, Nuaire keep extensive stocks 

for quick delivery. Ensure that the unit is electrically isolated, before 

carrying out any work.
Note: The supply cable must be replaced by an electrically competent 

person. 
When ordering spare parts, please quote the serial number of the unit 

and the ARC number of the purchase, if possible. (This information will 

be available on the fan label).

12.0 WARRANTY

The 5 year warranty starts from the day of delivery and includes parts 

and labour for the first year and parts only for the remaining 4 years. 
This warranty is void if the equipment is modified without 

authorisation, is incorrectly applied, misused, disassembled, or not 

installed, commissioned and maintained in accordance with the details 

contained in this manual and general good practice. 
The product warranty applies to the UK mainland and in accordance 

with Clause 14 of our Conditions of Sale. Customers purchasing from 

outside of the UK should contact Nuaire International Sales office for 

further details.

Filter

Filter cover

Outer enclosure cover

MVHR unit cover

Heat exchanger

Figure 19. Removing the two filter covers on the front panel of the 

unit. The filters can be removed by pulling on the black tab on the 

visible end of the filters.

9.1 Frost Protection

In the event of the intake air temperature at the unit dropping below 

the predetermined set point (-5°C as standard), the supply fan will 

reduce to minimum speed. Once the temperature rises above the set 

point, the fan will return to its commissioned speed.
Please note this mode will only activate after ten days of continuous 

run time. If commissioning of the unit is outside of this timeframe, 

please notify the after sales department prior to site visit.

Nuaire recommend that filters are inspected every 6 months and 

replaced every 12 months. A flashing LED (section 8.0) will indicate that 

a filter change is required. This indication repeats every 12 months and 

will turn off automatically after 5 Days.
Remove the filter covers on the front panel of the unit by gripping the 

two circular tabs either end of the filter covers and pulling away from 

the unit. The filter can now be extracted by pulling the removal loop on 

the front edge of the filter. Once the filters have been inspected return 

or replace them as necessary. 
Inspect the heat exchanger every 5 years. Generally check for damage 

and security of components. Refit cover.

IMPORTANT

Isolation - Before commencing work make sure that the unit, 

switched live and Nuaire control are electrically isolated from the 

mains supply and switched live supply.

10.0 MAINTENANCE

9.0 INTEGRAL AUTOMATIC HX BYPASS

Intake and extract temperatures are monitored at the point the 

airflows enter the unit. If the range falls within the set parameters, the 

bypass damper is opened automatically to target an indoor comfort 

temperature all year round.
Note:  The extract temperature is an average from all wet rooms. If 

this exceeds 25°C, the unit may go into bypass depending on outside 

temperatures.

13.0 AFTER SALES

For technical assistance or further product information, including spare 

parts and replacement components, please contact the After Sales 

Department.

Summary of Contents for MRXBOXAB-ECO4-1Z

Page 1: ... appropriate standards Ensure that the mains supply Voltage Frequency and Phase complies with the rating label Please note a clear working space is required around the installed unit to allow the cover to be removed and provide sufficient access for maintenance such as filter change A minimum of 480mm is required in front of the unit The fan must be installed indoors on a suitable structure away f...

Page 2: ...of the enclosure can be removed and discarded the remaining screws securing the bracket to the MVHR unit can be loosened allowing the bracket to be removed before fully tightened to secure the panel in place 2 1 Mounting the MVHR Unit Due to the size and weight of the unit floor mounting is the preferred mounting method If this is not possible a solid wall is required however a structural engineer...

Page 3: ...ation 6 l s Number of bedrooms in dwelling 1 2 3 4 5 Whole dwelling ventilation rate l s 1 2 13 17 21 25 29 1 The condensate must be discharged under a water level in a U trap drainpipe or an alternative drain method which acts as an airlock 2 The condensate discharge drain is a 32mm male threaded connection 3 If using a U trap please ensure the U trap has been filled to a suitable level of water ...

Page 4: ...ons given in ADF 2010 can be used where security is not an issue In this case minimum high extract rate for the sanitary accommodation should be omitted from the step 2 calculation Step 3 The required airflow rates are as follows The maximum whole dwelling extract ventilation rate e g boost should be at least the greater of step 1 and step 2 Note that the maximum individual room extract rate shoul...

Page 5: ...ms in ceilings via AirValve Insulated extract duct Insulated extract duct MVHR unit Nuaire MVHR DRAIN Condensate drain uninsulated drain pipe with min 5 o fall running to SVP MVHR unit Nuaire MVHR DRAIN Condensate drain uninsulated drain pipe with min 5 o fall running to SVP Exhaust air from kitchen bathroom to outside via air brick Minimum distance as specified in building regulations Intake air ...

Page 6: ...ples Of Typical Wiring Layouts MAINS 230V 50Hz N L 3 Position Switch Ancillary code MRXBOX95 3SWITCH Blue Green yellow Brown Black Supply cord from unit Grey L 1 2 Fuse 5A MAINS 230V 50Hz N L 3 Pole Isolator 3 Position Switch Ancillary code MRXBOX95 3SWITCH Blue Green yellow Brown Black Supply cord from unit Grey L 1 2 Fuse 5A 2 Pole Isolator light Room Light switch Double Pole MAINS 230V 50Hz N L...

Page 7: ...emoving front cover C C Ecosmart Connector Removable Plate 1 For required air flow rates please refer to the design specification for the property follow 2 4 or refer to building regulations ADF 2010 2 The unit should be run for a minimum of 10 minutes to reach steady state before commencing commissioning 3 The humidity sensor is initially set to its least sensitive position this should be adjuste...

Page 8: ...as standard the supply fan will reduce to minimum speed Once the temperature rises above the set point the fan will return to its commissioned speed Please note this mode will only activate after ten days of continuous run time If commissioning of the unit is outside of this timeframe please notify the after sales department prior to site visit Nuaire recommend that filters are inspected every 6 m...