NuAire MRXBOXAB-ECO-LP2OHSW Installation Manual Download Page 7

7

18. 02. 21. Document Number  671876

Nuaire | Western Industrial Estate | Caerphilly | CF83 1NA | nuaire.co.uk

MRXBOXAB-ECO-LP2SW

Installation Manual

4.3.2 Unit Serving Kitchen & 2 Bathrooms

4.3.3 Summer / Winter Switch

 

Black

2 core cable
from unit

Red

Volt free Summer / Winter Switch (supplied with unit)
Polarity is inconsequential
Warning! - Do not connect to mains! 

14 

Wiring Diagram - Summer / Winter Switch

5.0 COMMISSIONING

The filters fitted inside the unit are protected with a plastic film. 
Prior to commissioning remove the covers (Figure 15), take off the 
film and replace.

For the required air flow rates please refer to the design 
specification for the property, follow Section 3.5, or refer to 
building regulations ADF 2010.

The unit is supplied with independent control for both normal and 
boost airflows (Figure 15).

Correct commissioning is essential to ensure the ventilation air 
flowrates are met. It also ensures the unit is not over ventilating 
and causing excessive power consumption.

Commissioning should be carried out in accordance with building 
regulations document “Domestic ventilation compliance guide”. 
 
A calibrated moving vane anemometer and hood will be required 
to carry out commissioning.

Adjustment valves should be locked in place to prevent further 
adjustment.

Once commissioned the home owner / tenant should be informed 
that the unit should not be adjusted as it will have a detrimental 
effect on the indoor air quality and could result in condensation 
and mould growth. The label covering the control has an adhesive 
panel which should be removed post commissioning to prevent 
tampering.

Control module

Speed 1

Speed 2

Speed 1

Speed 2

15 

Commissioning Controls

6.0 CONTROLS

6.1 Integral Automatic HX Bypass (AB Units Only)

Intake and extract temperatures are monitored at the point the 
airflows enter the unit, if the range falls within the set parameters the 
bypass damper is opened automatically to target an indoor comfort 
temperature all year round.

6.2 Summer / Winter Switch

When the switch position is set to Summer, the integral automatic 
summer bypass is fully operational. In the alternative Winter position, 
the HX bypass is disabled to ensure the unit is constantly in heat 
recovery mode. 

6.3 Speed 3 Operation (SW Units Only)

Speed 3 will be non-operational if the intake temperature is greater 
than the extract temperature.

6.4 Frost Protection

In the event of the intake air temperature at the unit dropping below 
the predetermined set point (-5°C as standard) the supply fan will 
reduce to minimum speed, once the temperature rises above the set 
point the fan will return to its commissioned speed.

This mode will only activate after ten days of continuous run time. 
If commissioning of the unit is outside of this time frame please 
notify the after sales department prior to site visit.

Disconnection from the 
supply mains must be 
incorporated within the 
fixed wiring in accordance 
with the wiring 
regulations and shall 
have a minimum contact 
separation  of 3mm.

3A Fuse

 (BS 1362)

MAINS

230V

50Hz

Room

Lights

Light

 Switches

 (Double

 Pole)

N

L

3 Pole

Isolator

Kitchen Switch

Blue

Green / Yellow

Brown

Black

Supply Cord 
From Unit

Optional 3 Speed Switch

Grey

13 

Wiring Diagram - Kitchen & 2 Bathrooms

Summary of Contents for MRXBOXAB-ECO-LP2OHSW

Page 1: ...ven supervision or instruction concerning the safe use of the appliance by a person responsible for their safety Children shall not play with the appliance Cleaning and user maintenance shall not be c...

Page 2: ...is required around the installed unit to allow the cover to be removed and provide sufficient access for maintenance such as filter change The fan must be installed indoors in a suitable ceiling void...

Page 3: ...r of bedrooms in dwelling 1 2 3 4 5 Whole dwelling ventilation rate l s 1 2 13 17 21 25 29 1 In addition the minimum ventilation rate should be no less than 0 3 l s per m2 of internal floor area This...

Page 4: ...be at least those given in table 1 for minimum high rate The minimum air supply rate should be at least the whole building ventilation rate found in step 1 For Scotland refer to BRE Digest 398 For fu...

Page 5: ...k Supply and extract ducts from external air bricks to the unit needs to be insulated Top of ceiling void Minimum distance as specified in Building Regulations Intake air from outside via air brick 3...

Page 6: ...to the mains supply 4 1 Electrical Information Electrical details Voltage 240V 1ph 50Hz Consumption 1 3 Amp This unit must be earthed The cable from the mains power supply should be connected to a fix...

Page 7: ...ontrol has an adhesive panel which should be removed post commissioning to prevent tampering Control module Speed 1 Speed 2 Speed 1 Speed 2 15 Commissioning Controls 6 0 CONTROLS 6 1 Integral Automati...

Page 8: ...nd general good practice The product warranty applies to the UK mainland and in accordance with Clause 14 of our Conditions of Sale Customers purchasing from outside of the UK should contact Nuaire In...

Reviews: