4.3.2 Unit Serving Kitchen & 2 Bathrooms

5.0 COMMISSIONING

The filters fitted inside the unit are protected with a plastic film. 
Prior to commissioning remove the covers (Figure 14), take off the 
film and replace.

For the required air flow rates please refer to the design 
specification for the property, follow Section 3.5, or refer to 
building regulations ADF 2010.

The unit is supplied with independent control for both normal and 
boost airflows (Figure 14).

Correct commissioning is essential to ensure the ventilation air 
flowrates are met. It also ensures the unit is not over ventilating 
and causing excessive power consumption.

Commissioning should be carried out in accordance with building 
regulations document “Domestic ventilation compliance guide”. 
 
A calibrated moving vane anemometer and hood will be required 
to carry out commissioning.

Adjustment valves should be locked in place to prevent further 
adjustment.

Once commissioned the home owner / tenant should be informed 
that the unit should not be adjusted as it will have a detrimental 
effect on the indoor air quality and could result in condensation 
and mould growth. The label covering the control has an adhesive 
panel which should be removed post commissioning to prevent 
tampering.

Control module

Speed 1

Speed 2

Speed 1

Speed 2

14 

Commissioning Controls

6.0 CONTROLS

6.1 Integral Automatic HX Bypass (AB Units Only)

Intake and extract temperatures are monitored at the point the 
airflows enter the unit, if the range falls within the set parameters the 
bypass damper is opened automatically to target an indoor comfort 
temperature all year round.

The extract temperature is an average from all wet rooms. If this 
exceeds 25°C the unit may go into bypass depending on outside 
temperatures.

6.2 Frost Protection

In the event of the intake air temperature at the unit dropping below 
the predetermined set point (-5°C as standard) the supply fan will 
reduce to minimum speed, once the temperature rises above the set 
point the fan will return to its commissioned speed.

This mode will only activate after ten days of continuous run time. 
If commissioning of the unit is outside of this time frame please 
notify the after sales department prior to site visit.

6.3 Status Indication

The status of the unit is indicated by a series of LED’s on the control box 
cover. The variants are listed below.

The display on the unit control panel will not indicate when a 
higher speed setting has been triggered by an external source, such 
as an ES-PIR2 etc.

HX Bypass

(AB units only)

Speed 1

Speed 2

Speed 3

Supply Fan Fault

Extract Fan Fault

Frost Protection

Filter Change

15 

Status Indication

Disconnection from the 
supply mains must be 
incorporated within the fixed 
wiring in accordance with the 
wiring regulations and shall 
have a minimum contact 
separation  of 3mm.

3A Fuse

 (BS 1362)

MAINS

230V

50Hz

Room

Lights

Light

 Switches

 (Double

 Pole)

N

L

3 Pole

Isolator

Kitchen Switch

Blue

Green / Yellow

Brown

Black

Supply Cord 
From Unit

Optional 3 Speed Switch

Grey

13 

Wiring Diagram - Kitchen & 2 Bathrooms

Summary of Contents for MRXBOXAB-ECO-LP2

Page 1: ...supervision or instruction concerning the safe use of the appliance by a person responsible for their safety Children shall not play with the appliance Cleaning and user maintenance shall not be carri...

Page 2: ...to be removed and provide sufficient access for maintenance such as filter change The fan must be installed indoors in a suitable ceiling void away from direct sources of frost heat water spray or mo...

Page 3: ...of bedrooms in dwelling 1 2 3 4 5 Whole dwelling ventilation rate l s 1 2 13 17 21 25 29 1 In addition the minimum ventilation rate should be no less than 0 3 l s per m2 of internal floor area This i...

Page 4: ...be at least those given in table 1 for minimum high rate The minimum air supply rate should be at least the whole building ventilation rate found in step 1 For Scotland refer to BRE Digest 398 For fur...

Page 5: ...Supply and extract ducts from external air bricks to the unit needs to be insulated Top of ceiling void Minimum distance as specified in Building Regulations Intake air from outside via air brick 3 9...

Page 6: ...o the mains supply 4 1 Electrical Information Electrical details Voltage 240V 1ph 50Hz Consumption 1 3 Amp This unit must be earthed The cable from the mains power supply should be connected to a fixe...

Page 7: ...matic HX Bypass AB Units Only Intake and extract temperatures are monitored at the point the airflows enter the unit if the range falls within the set parameters the bypass damper is opened automatica...

Page 8: ...tact Nuaire International Sales office for further details Failure to maintain the unit as recommended will invalidate the warranty 9 0 END OF LIFE AND RECYCLING Where possible Nuaire use components w...

Reviews: