NuAire MRXBOX95B-WHI Installation And Maintenance Manual Download Page 2

2

21. 06. 13. Leaflet Number 671556 

Installation and Maintenance

MRXBOX95B-WH1 Mechanical Ventilation with Heat Recovery & Summer Bypass

Any air intake terminal MUST be installed in accordance with the

appropriate regulation. 

As a guide, the BS5440 series of British Standards deals with

this issue and currently states that an air intake must be at a

minimum distance of 300mm from a gas boiler balanced flue.

Installers are advised to be aware of the requirements of this

standard when installing ‘through the wall’ supply air ducting.

Similarly, supply and extract air grilles should be at least

300mm apart.

Figure 5a. Wet option.
Condensate pipe 
connection to unit and 
a typical example of 
a “U” trap drainpipe.

Figure 5b. MVHR-DRAIN option. 
Condensate drain, uninsulated drain 
pipe with 10o fall running to SVP.

5

Drop

Collar

2.1 Condensate Drain

1.

Remove the front cover from the unit. 

2. Insert the drain connector through the base of the unit from 

outside. The condensate must be discharged under a water 

level in a U-trap drainpipe or an alternative drain method 

which acts as an airlock.  

3. Ensure the drain connector forms a seal with the drain tray 

applying sealant if necessary. This condensate discharge 

connection is suitable for 21.5mm dia. overflow pipe. 

Solvent cement should be used to make the joint. 

4. If using a U-trap please ensure the U-trap has been filled to 

a suitable level of water to avoid any air locks.

5. If the condensation pipe is fitted in an unheated space the 

pipe should be in insulated to prevent freezing. 

Nuaire recommend MVHR-DRAIN be used as the primary

condensate take-off. (see figure 5b/7a/7b).

2.2 Extract/input areas

The unit is designed to extract air from all wet rooms 

e.g. bathroom, kitchen, en-suite, utility room (with sink). 

WC’s do not need to be ventilated if openable windows 

are fitted.

Supply air should be to all habitable rooms e.g. bedrooms and

lounge. Extract / input grilles should be adjustable valve types

(not supplied).

External grilles to have a minimum free area of 12,250 sq mm.

2.3 Ducting

Before commencing ducting installation reference should be

made to building regulations document “Domestic ventilation

compliance guide”. This document supports ADF2010 and

details installation, testing and commissioning of all ventilation

systems.

It is recommended that rigid ducting be used it all times. 

Flexible ducting has a very high resistance and it is impossible

to calculate how much resistance will be on a system if used.

If used the flexible ducting must be kept to a minimum and

should always be pulled taut. A maximum of 500mm should 

be used on each leg.

To prevent condensation on the outside of the outside air inlet

duct and the air outlet duct from the MRXBOX95B-WH1, these

ducts should be insulated. 

Ducting must be installed in such a way that resistance to 

airflow is minimised. Bends should be kept to a minimum.

A minimum distance of 200mm between the appliance and 

any bends in ductwork is recommended.

Ideally 125mm diameter or 204 x 60mm rectangular ducting

should be used. (Refer to dwelling design drawing, figure 7a

and 7b on page 4 for further information).

Ducting joints must be sealed with silicone type sealant and

shall be adequately and reliably fixed to the appliance.

2.4 Ventilation flow rates

Table 1.

ADF2006 / 2010  – Extract ventilation rates

Room

Min high rate

Min low rate

Kitchen

13 l/s

Utility room

8 l/s

Bathroom

8 l/s

Sanitary 
accommodation

6 l/s

Table 2.

Whole dwelling ventilation rates

Number of bedrooms in dwelling

1

2

3

4

5

Whole

13

17

21

25

29

dwelling 
ventilation 
rate l/s

1, 2

Notes:

1,

In addition, the minimum ventilation rate be should be not

less than 0.3 l/s per m

2

of internal floor area. 

(This includes all floors, e.g. for a two-story building add the

ground and first floor areas).

2,

This is based on two occupants in the main bedroom and

a single occupant in all other bedrooms. This should be used

as the default value. If a greater level of occupancy is

expected add 4 l/s per occupant.

Total extract rate should

be at least the whole

dwelling ventilation rate

given in table 2.

Summary of Contents for MRXBOX95B-WHI

Page 1: ...the installed unit to allow the cover to be removed and provide sufficient access for maintenance such as filter change Please allow a minimum of 250mm in front of the unit The fan must be installed...

Page 2: ...le valve types not supplied External grilles to have a minimum free area of 12 250 sq mm 2 3 Ducting Before commencing ducting installation reference should be made to building regulations document Do...

Page 3: ...boost should be at least the greater of step 1 and step 2 Note that the maximum individual room extract rate should be at least those given in table 1 for minimum high rate the minimum air supply rate...

Page 4: ...ated supply duct Insulated supply duct Minimum 300mm Air supply to lounge via Air Valve Part no V125S in ceilings Extract air from kitchen bathroom via Air Valve Part no V125S in ceilings Air supply t...

Page 5: ...Pole isolator 3 Pole isolator Kitchen switch Kitchen switch Blue Brown Black Optional summer boost switch Supply cord from unit Green yellow Blue Brown Black Supply cord from unit Optional summer boos...

Page 6: ...ot be adjusted as it will have a detrimental effect on the indoor air quality and could result in condensation and mould growth The label covering the control has an adhesive panel which should be rem...

Page 7: ...ted 3 2 When handling the equipment care should be taken with corners and edges and that the weight distribution within the unit is considered Lifting gear such as slings or ropes must be arranged so...

Page 8: ...ings assessed under The Building Regulations 2010 specifically SAP 2009 and Approved Documents L and F Completion of this document is therefore only required for dwellings assessed by SAP 2005 Custome...

Page 9: ...r to overcome particular obstructions If flexible ducting has been used has it been pulled taut to minimise system resistance Has the number of duct bends been minimised to ensure adequate air flow an...

Page 10: ...y unit been fixed to a stable element of the building fabric e g wall or floor using manufacturer recommended supplied fixing brackets Has the condensation drain been fitted and the pipe insulated Hav...

Page 11: ...or N A Has the rating label been verified to establish suitability for the installation strategy and whether an earth is required e g voltage class I or II product status Has a local isolator been pro...

Page 12: ...tion grilles been locked where possible to minimise unapproved occupant adjustment Figure 3 Ensure all external and internal windows and doors are closed Set fan speed using manufacturer data table Se...

Page 13: ...e customer been advised that opening windows is not recommended during normal use in order to ensure the energy efficient operation and performance of the balanced system Has the customer been advised...

Reviews: